background image

NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 2 

Installation Instructions, Volume 2                                                                                                                         Page 57 

"Service Message" occurs, a service message will display on the keypad and if programmed will report to Telco 1 and/or 
Telco 3.  A service message "E24-00 Time for Service" may be programmed to appear at the GEMC-BK1 Burg keypad and 
report to central station using the Quickloader Event scheduler. 

 

Shed Burg on AC Fail 

        This feature specifies the amount of time the GEMC-BM or GEMC-BM/PS Burglary Modules will continue to operate using 

battery power after no AC is detected by the motherboard.   

        Program a number (0-255) of 10-minute intervals for the selection of untimed (program "0") or 10 through 2550 minutes 

(program "1-255").  

Note:

  If the number selected is non-zero and less than or equal to 4 hours and 30 minutes (program 

"27"), the selection timeout is 4 hours and 30 minutes. 

        When using a GEMC-BM/PS, program zero (untimed) as the GEMC-BM/PS battery backup automatically sends a "very low 

battery" status to the motherboard when voltage drops below 10.2V.  When this "very low battery" status is received by the 
motherboard, the GEMC-BM/PS will stop accepting status changes from the burglary system to prevent false alarms. 

        When a GEMC-BM (Burg Module without an onboard power supply) is used, program at least "27" (4 hours and 30 minutes); 

if the system battery standby can adequately supply power, this time can be extended.  When the programmed time expires, 
the Burglary system will stop functioning and all power will be removed to conserve the batteries for the Fire system.  The 
GEMC-BM will stop accepting status changes from the Burglary system, thus preventing false Burglary alarms. 

 

Smart Download 
Smart Upload 

        Quick method of communications that compares the sum-checks of sections of panel program to determine if they are differ-

ent from the account sections and only communicates data that is different. 

 

Split Reporting

   See 

Report Telco 3

 

 

Start Exit Delay After Ringback 

        When a closing report is successfully received, the central station will acknowledge by returning a kissoff signal.  When the 

kissoff is received by the communicator, a 2-second ringback tone will sound at the keypad.  Start Exit Delay After Ringback 
will cause the exit delay to start after the ringback sounds. 

        If this option is chosen and no ringback sounds shortly after the control panel is armed, exit delay will not start and opening 

the exit/entry door will cause an instant alarm.  To manually start the exit delay, select the START EXIT TIME function, then 
press 

ENTER 

to execute. 

        Note:   

(1) If this feature is selected, Exit/Entry Follower Zones will not arm until either a ringback sounds or the START EXIT 

TIME function is used.  (2) If communicator, telephone lines or central-station receiver is not in service, the system will be 
armed without communication capability.  

Note:

  The Entry Sounder feature cannot be turned off in Keypad Configuration 

mode.  

 

Status Report   

See 

Closing Report

 

 

Subscriber Identification Numbers 

        If reporting openings and/or closings, program Subscriber Opening/Closing Identification Numbers for each area for each tele-

phone number used.  If reporting events, program Subscriber ID Numbers for each area for each telephone number used.  
Subscriber ID numbers must be programmed for each area and telephone number, even if all are the same.  Start with the 
left-most location. 

 

Supervise Burg Bell Output 

        When this option is enabled, a 2.2K ohm resistor must be installed across the bell or sounding device terminals.  In the event 

that the Burg Bell is cut, or the circuit is opened, an 

E51-00 BURG BELL TRBL 

trouble condition will occur.  

Note:

  E51 trou-

ble may also be generated with a GEMC-BM or GEMC-BM/PS trouble.  

Note:  

Due to a constant loop current flowing through 

the Burg Bell Output circuit for supervision, some sirens or siren drivers may emit a low volume hum or buzz if the 2.2K EOL 
resistor is not installed.  If a supervised Burg Bell output is not required, this can be eliminated by programming the option in 
PCD-Windows Quickloader (

System Assignment 

screen, 

System Options 

tab, 

Supervise Alarm Output 

checkbox).  

 

Suppress "BYPASSED" Icon When Armed 

 

        Program to inhibit the LCD "

BYPASSED

" display while armed.  (This option is located in the PCD-Windows Quickloader

 Key-

pad Features

 screen).   

 

Swinger Shutdown  

        Swinger Shutdown is a common term used in the burglary alarm industry.  It is a feature of an alarm panel that prevents multi-

ple false alarms from being generated from faulty detectors (or wiring) by limiting the number of alarms a zone may report 
during a single arming period.  NAPCO has this programmable-by-zone feature named 

Swinger Shutdown,

 and has been 

available on its panels for years.  The SIA False Alarm Reduction standard CP-01 requires the SIA definition of "swinger shut-
down" on all non-Fire zones.  Our programmable feature allows three trips per arming period which is unacceptable in CP-01 
installations.  Therefore, to reduce confusion, the following defines both definitions of "Swinger Shutdown", namely (1) the 

BURGLARY GLOSSARY 

Summary of Contents for GEMINI GEMC-128

Page 1: ...COMMUNICATOR Installing the GEMINI C Series Control Panels with the GEMC FK1 Keypad and the GEMC BK1 Keypad GEMC FK1 Keypad GEMC BK1 Keypad INSTALLATION INSTRUCTIONS VOLUME 2 R Publicly traded on NASD...

Page 2: ...d by implications or otherwise under any patent or patent rights of Napco Microsoft and Windows are registered trademarks of the Microsoft Corporation All other trademarks cited in this manual are for...

Page 3: ...C RM2 FWC FSLC SOM1 Devices 15 Mapping Zones to Outputs 16 Burglary Outputs 17 Fire Output Option Chart 18 Fire Burg Output Devices 19 Fire Glossary 21 37 Burglary Glossary 38 62 CP 01 Quick Reference...

Page 4: ...Failure A problem has been detected either in a wireless transmitter or a burglary SLC Point XXXXXX The wireless SLC device 6 digit ID map number NNN associated zone number Fire Burg Keypads WL SLC TR...

Page 5: ...the bus class A or B and or an open on a class A loop Consider moving Receiver location or repairing SLC loop Fire Burg Keypads Auto Reset RECrf slc TRBL E16 NN E17 NN SYStrbl E17 xxx MM DD YY HH MM R...

Page 6: ...he external output number followed by a programmed 29 character NAC description multiple X characters For Burglary systems a GEMC BSLC RLY is not responding or its relay is not working correctly Fire...

Page 7: ...but not mapped programmed to any zone Fire Keypad Only Latching E94 000 SYStrbl E94 xxx MM DD YY HH MM FslcRec NoRespon E94 000 SERVICE For Fire Systems A response failure in the GEMC FW SLC Fire SLC...

Page 8: ...g S2 for a total of 2 5A Rule 3 All notification appliances in the same field of view must use the same sync pattern The maximum current draw from Smart Synchronized circuits on either the GEMC XXXMB...

Page 9: ...ollows 1 Do not select option Coded Alarms by Zone in the NAC Output Options screen 2 Select Silenceable and Smart for each NAC 3 Program the selected NAC to activate on fire alarm or specific zone al...

Page 10: ...d SILENCE is pressed Subsequent alarms that occur after silence but before all fire zones are restored will reinitiate the cadence alarm Method 3 Coded Alarm by Zone The third method of synchronizatio...

Page 11: ...an over current condition indicating a RlyTbl E35 NN followed by the programmed description of the associated NAC GEMC NACXX NAC Over Current protection when con nected to a Gemini C Series Control Pa...

Page 12: ...he Fire bus c Fire Wireless transmitter points maximum 125 Fire and Burg wireless devices d Fire SLC Points 2 Burg Zones a Burg GEMC EZM8 zones GEMC EZM8 wired to the Burg bus b Burg GEMC BK1 Burg key...

Page 13: ...with no other devices on the same zone Fire Wireless transmitter points require all GEMC RECV wireless receivers to be wired to the Fire bus of the mother board preventing faults on the Burg bus from...

Page 14: ...evices and or lack of suf ficient standby battery power There are many ways to wire zones into the Gemini C Series Panels Careful planning will allow the panel to support virtually any desired combina...

Page 15: ...external outputs enabled in 11 groups of eight and enabled only on the addressed device Each group of eight is distinctly addressed as group 1 through group 11 and only one group of the same address m...

Page 16: ...ART fur ther in this manual In addition the selected module must also be configured for the correct relay group 1 8 using the RELAY dip switch located on the module PC board For more information see W...

Page 17: ...for relay contact failure that also display as outputs with descriptions on the GEMC FK1 keypad Supervised Burglary outputs require that they be configured as external relay 1 40 therefore the first 4...

Page 18: ...EO15 N A N A N A EXT OUT 16 EO16 N A N A N A EXT OUT 17 EO17 Circle one None Burg Output on 4 wire Burg Bus BURG GEMC RM3008 or BURG GEMC OUT8 Fire Output on 4 wire Fire Bus FIRE GEMC RM3008 or FIRE...

Page 19: ...Output on Fire SLC 2 GEMC FW FSLC 2 GEMC NACXX 2 118 2 0 9 2 1 2 NAC 1 EXT OUT 10 EO10 2 117 2 1 0 2 2 2 NAC 2 EXT OUT 11 EO11 2 116 2 1 1 2 3 2 NAC 3 EXT OUT 12 EO12 2 115 2 1 2 2 4 2 NAC 4 EXT OUT 1...

Page 20: ...OUT 58 N A 8 68 8 5 9 8 3 N A N A EXT OUT 60 N A 8 67 8 6 0 8 4 N A N A EXT OUT 61 N A 8 66 8 6 1 8 5 N A N A EXT OUT 62 N A 8 65 8 6 2 8 6 N A N A EXT OUT 63 N A 8 64 8 6 3 8 7 N A N A EXT OUT 64 N A...

Page 21: ...ng the access number If the communicator must delay before dialing the access number in stead of attempting to recognize the dial tone find out how many 4 second delays must be programmed Alarm Output...

Page 22: ...the line from the house phones as well as the answering machine and the connection will subse quently be established Note For Fire systems the GEMC FK1 Fire keypad must be unlocked before downloading...

Page 23: ...e silence able NAC output typically all NAC outputs for Enable Cadence in the NAC Output As signment screen click the NAC Output Assignments tab then check the Enable checkbox for the selected output...

Page 24: ...it also has Selective Call Waiting and confirm the disable code with the telephone company Then program this code B70 directly before the phone numbers after dial tone detection or pre dial delay in...

Page 25: ...keypad The message will remain until the time and date have been re programmed This option is located in the PCD Windows Quickloader Keypad Features screen Enable Telco Line 1 Enable Telco Line 2 When...

Page 26: ...v Memory Failure The GEMC FW SLC program does not match the panel program Fire SLC Recv No Resp GEMC FW SLC stopped responding to polls due to malfunction incorrect address or connector missing or inc...

Page 27: ...he shunt from OFF to ON to enter Burg Service Mode when maintenance or changes to the Burglary hardware must be performed while keeping the Fire system in operation Entering Burg Service Mode will pre...

Page 28: ...ry System Trouble E02 A low battery system trouble will annunciate at the keypad when the motherboard battery terminal voltage drops below nor mal and or the charging voltage drops below the nominal 2...

Page 29: ...other Fire alarm zone initiates an alarm before all Fire zones have reset This feature is typically selected for audible Fire alarm sounding appliances Resetable To turn off a NAC programmed for Reset...

Page 30: ...through Telco 1 or Telco 3 for all UL Commercial Fire reporting or Burg Commercial Fire reporting accounts Disabled Report Disabled Only the four integral NAC A through NAC D circuits or the followin...

Page 31: ...detectors activate each pull station etc When detected by the system all output circuits programmed to activate when the associated zone is in alarm will sound a single momentary chirp 5 Restore the...

Page 32: ...MX 8000 Surgard MLR 2 Osbourne Hoffman 2000e NAPCO Net Link NL RCV RMPCUL Ademco 685 Relay Event Relay outputs can be programmed to activate on a particular event or combination of events Select the...

Page 33: ...er Test This keypad Function Menu feature TEST COMMUNICATOR will send a programmed report code to the central station Note that in this case the report code received is not indicative of a system trou...

Page 34: ...nciators not used for evacuation sounder or required strobes To turn off these auxiliary outputs the GEMC FK1 Fire keypad must be unlocked and the option Turn Off Aux Outputs selected Smart See NAC Fe...

Page 35: ...wire smoke detector circuit Subscriber Identification Numbers If reporting openings and or closings program Subscriber Opening Closing Identification Numbers for each area for each telephone number u...

Page 36: ...one Dialing with Rotary Backup see the Burglary Glossary 2 Wire 4 Wire Smoke Detectors See Smoke Detectors User Assignment Controls user authority levels The tabs are as follows User System Codes Type...

Page 37: ...Assignment screen System Reporting and Outputs tab to allow the re porting to the central station when any Fire User Code is used to unlock a Fire keypad Waterflow Waterflow Retard Time A Waterflow Zo...

Page 38: ...ction option locations on the Wireless Keyfobs screen in PCD Windows Quickloader This feature also requires a valid time to be entered into the Burg PGM 1 Access Control in the Time Selection screen I...

Page 39: ...11 12 13 R 1 UL INSTALLATIONS 1 Cutting the R jumper will provide Dry Contacts for the Aux Relay no voltage on COM N C and N O contacts for use with exter nal power supplies and or loads see wiring d...

Page 40: ...ced Subscriber Opening Closing ID Numbers and Event ID Numbers if reporting System Trouble Subscriber ID Number If Priority Area Arming is selected the Priority Area must be armed before the Arming Ar...

Page 41: ...e system and must be installed even if AC power is present Change the batteries every 4 years or as required If the GEMC BM PS is used it requires 12V battery backup BE Bypass Enable Alarm Code featur...

Page 42: ...gram this fea ture in the Quickloader System Assignment screen System Reporting and Outputs tab Burg SLC No Resp GEMC BSLC stopped responding to polls due to malfunction incorrect address or connector...

Page 43: ...d Access the ACTIVATE CHIME function to enable or disable the Chime Mode from the keypad This feature is programmable by zone and for duration of tone see Time Selection A time in seconds must be prog...

Page 44: ...Trouble on Short the trouble reported will be that programmed under Day Zone Trouble Open and or Day Zone Trouble Short Note Do not program a Day Zone Trouble for 24 hour protection The keypad will a...

Page 45: ...ypad Features screen See Selective Bypass Disable Code Required for FM Function Mode Level 1 Intended primarily for residential applications this feature eliminates the user code requirement to access...

Page 46: ...er code Do not program Easy Arming in UL installations If closings are reported Easy Arming will report as User 199 Easy Exit Not Evaluated by UL While armed in the Interior Bypass Stay Mode Easy Exit...

Page 47: ...E message will be displayed Enable Report Test Mode Start End At the initiation of a test the control panel sends a message to the central station that a test is in progress The Fault Find function a...

Page 48: ...een armed with Exit Delay Restart enabled when the exit door is opened and then closed the pro grammed exit delay will restart at 60 seconds Thus if a long exit delay is programmed it will be reduced...

Page 49: ...full protec tion in ARMED AWAY mode by arming without the E button The next time the zone is disarmed the zone will be come a full protected zone Interior zones can be made to be normally bypassed by...

Page 50: ...pad is desired also program a Panel Access Code Keyfob Disarm Activates Entry Lighting Disarming with a keyfob can activate Remote Relays or X 10 Devices by programming the event Ext Burg Rel 1 or Ext...

Page 51: ...Code must be Bypass Enabled 2 Press the B button The display will read BYPASS ENABLED 3 Press the B button again 4 Enter the zone The display will read BYPASSED ZONE 5 To bypass another zone repeat st...

Page 52: ...enabled a chime will sound at the keypad while armed or disarmed when that zone is opened This feature is suggested for use as a driveway monitor or similar application NL MOD IP Address Panel IP Addr...

Page 53: ...ut a correct PC security code Each sub field of the PC security code is ranged from 0 to 255 The user can toggle to the next sub field by either pressing the tab key or the key This PC security code w...

Page 54: ...articular event or combination of events Select the event s in the Quick loader NAC Output Assignment screen NAC Output Events tab Click in the Event Alarm Type Condition column and the Relay Event di...

Page 55: ...mode Select option by enabling the Program Change located in the System Assignment screen System Reporting Outputs tab Required in Fire reporting ac counts RF Receiver Trouble An trouble is generated...

Page 56: ...s the Burg Bell to chirp instead of the Burg Module PGM1 Output upon remote arming Selective Bypass Disable Code Required for EZ Bypass Not for UL installations Any or all zones 1 255 programmed for S...

Page 57: ...it entry door will cause an instant alarm To manually start the exit delay select the START EXIT TIME function then press ENTER to execute Note 1 If this feature is selected Exit Entry Follower Zones...

Page 58: ...E ARMED ENABLE BURG RF RECEIVER TAMPER SOUND BURG ALARM ONLY IF ANY AREA ARMED Removing the cover of an expansion zone module will cause the sounder to pulse and the SYS TBL reminder to flash The keyp...

Page 59: ...BOX Remember that a zero entry represents 10 Example Program Entry Delay 1 for 1 minutes 1 Entry Delay 1 is in units of seconds thus delay time is 90 seconds 2 Divide by 16 90 16 5 quotient 10 remaind...

Page 60: ...BURG PGM2 MINUTES 4 HR 15 MIN 255 MIN 2 N A CHIME SECONDS 63 25 SEC 255 QTR SEC 3 N A BURG AUX RELAY MINUTES 4 HR 15 MIN 255 MIN N A BURG PGM1 MINUTES 4 HR 15 MIN 255 MIN 2 N A BURG PGM1 ACCESS CONTR...

Page 61: ...each code can be assigned four different Authority Levels 0 1 2 or 3 and five Attributes Initially Off BV User Program BE and Overview and can be assigned to Area s 2 8 with Area 1 being reserved for...

Page 62: ...include a Panic Zone as part of any Group Auto Reset must be programmed for each Zone ANDing Zone Note Any zone that is bypassed or goes into Swinger Shutdown will automatically disable Zone Anding f...

Page 63: ...ble time is 255 seconds The panel uses the existing programmable by zone feature Entry Exit 1 to comply with CP 01 At least one Entry Exit zone must be programmed for each area The existing programmab...

Page 64: ...tation that Test Mode is in progress Fault Find can not be initiated from an armed panel and all digital dialer reporting in same area is inhibited while in Fault Find Keypad will display the followin...

Page 65: ...ed less than 10 seconds after the Ambush Code for an ambush report to be sent When ENABLE GLOBAL AMBUSH is selected and no Ambush code has been entered and the keypads have been selected for AMBUSH th...

Page 66: ...em Sensor Format thus requiring System Sensor Synchronized Horn Strobes be installed All 4 NAC s are synchronized not offset as required for more than 4A total alarm current The AUX Fire relay is prog...

Page 67: ...24V7A and GEMC BM 2 12V 7AH 7 154 225 2 5A 3 5A 0 750 2 12V 8AH 8 190 278 2 5A 4A 0 750 4 12V 7AH 14 405 591 2 5A 7A 0 750 4 12V 8AH 16 480 700 2 5A 7A 0 750 6 12V 7AH 21 667 974 2 5A 7A 0 750 6 12V 8...

Page 68: ...0 0 500 4 12V 8AH 16 480 700 2 5A 7A 0 750 0 500 6 12V 7AH 21 667 974 2 5A 7A 0 750 0 500 6 12V 8AH 24 780 1138 2 5A 7A 0 750 0 500 8 12V 7AH 28 930 1357 2 5A 7A 0 750 0 500 8 12V 8AH 32 1100 1400 2 5...

Page 69: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 2 Installation Instructions Volume 2 Page 69 NOTES...

Page 70: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 2 Page 70 Installation Instructions Volume 2 NOTES...

Page 71: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 2 Installation Instructions Volume 2 Page 71 NOTES...

Page 72: ...red by others improperly installed improperly used abused altered damaged subjected to accident nuisance flood fire or acts of God or on which any serial numbers have been altered defaced or removed N...

Reviews: