background image

N.C. EXTERNAL 

CONTACT(S) 

ON POINT 1 

N.C. EXTERNAL 

CONTACT(S)  

ON POINT 2 

REED 

SWITCH 

WIRING 

The GEMC-WL-WD2 may be wired in any of the following configurations; refer to the diagrams below:  

Note:

  For Commercial and Resi-

dential Fire installations, only ONE initiating device may be connected to this transmitter (only normally open contacts used for Fire).  For 
Commercial Burglary installations, multiple initiating devices may be used as long as the devices all serve the same function (i.e. door, win-
dow, motion, etc.). 

Notes:    

1.  

Caution:  

Changes or Modifications not approved by Napco may void the user's authority to operate the equipment. 

2.   This device may not cause interference. 
3.   This device must accept any interference, including interference that may cause undesired operation of the device. 
4.   Only loop 1 is supervised. 

J1 JUMPER INSTALLED 

FUNCTION 

 

 External Contacts Enabled

 for both point 1 and 2.  

(DEFAULT) 

1. 

2. 

J1 JUMPER NOT INSTALLED 

FUNCTION 

 

Internal Contact Enabled

 for point 1. External contacts may be used for point 

1 or point 2. 

180K EOL 

N.O. EXTERNAL 
CONTACT TYPE 

DEVICES SUCH 

AS PULL STA-

TIONS, THERMAL 

DETECTORS, 

WATERFLOW 

SUPERVISION 

SWITCHES, ETC. 

SHORT 

POINT 2 

180K 

EOL 

SHORT 

POINT 2 

REED 

SWITCH 

180K 

EOL 

REED 

SWITCH 

N.C. EXTERNAL 

CONTACT(S) ON 

POINT 2 

180K RESISTOR 

COLOR CODE (FROM LEFT TO RIGHT): 

BROWN (1), GRAY (8), YELLOW (0), GOLD (5%) 

N.C. EXTERNAL 

CONTACT(S) 

ON POINT 1 

N.C. EXTERNAL 

CONTACT(S) 

ON POINT 2 

A.  FIRE     Class B, Style A, B 

B.  BURGLARY 

A.  BURGLARY 

B.  BURGLARY 

C.  BURGLARY 

180K EOL 

180K EOL 

SUPERVISED 

LOOP 

UNSUPERVISED 

 LOOP 

 (DO NOT USE) 

SUPERVISED 

LOOP 

UNSUPERVISED 

LOOP 

SUPERVISED 

LOOP 

UNSUPERVISED 

LOOP 

SUPERVISED 

LOOP 

UNSUPERVISED 

LOOP 

SUPERVISED 

LOOP 

UNSUPERVISED 

LOOP 