Supervised Alarm / Relay / Power Expansion Unit 8
CONFIGURATION
PC Board Layout: Alarm/Relay Board (CICP1300IOBD)
12V IN
Powers the
relay coils
I/O SERIAL SIGNAL and LOGIC POWER
Connect to control panel or pass-thru connector
using the modular cable supplied.
ADDRESS
A jumper must be set to X1, X2, or X3.
Each Board must be set to a different address.
INDICATORS
•
EVENT
- Flashes on/off to indicate a change in any
Alarm Input status.
•
OK
- Flashes steadily to indicate a working connec-
tion to the control panel.
•
RELAY
- Indicates working power connection via
12V IN.
•
LOGIC
- Working 5 volt power from control panel.
•
LEDs near Relays
indicate activation of individual
relay.
S I X T E E N S U P E R V I S E D
ALARM INPUTS
May be configured as Normally-
Open / Normally Closed; Super-
vised (requiring termination resis-
tors) or Unsupervised (requiring
plain electrical contacts).
RELAY CONTACTS
Normally-Open and Nor-
mally-Closed contacts
available. Contacts rated
2A 24V AC/DC.
Figure 2 - PC Board Layout