Technical
Manual
SMCI36
Connections and wiring
Setting the RS485 module address
Hardware setting
The RS485 module address can be set by hardware via two HEX coded switches on
the printed circuit board.
The 16's place is set with switch 1 (left) and the 1's place is set with switch 2 (right).
Module address
Switch 2 (right)
Switch 1 (left)
Software setting
0
0
1 1 0
2 2 0
... ... ...
15 F
0
16 0
1
17 1
1
... ... ...
32 0
2
... ... ...
64 0
3
... ... ...
80 0
5
... ... ...
96 0
6
... ... ...
112 0
7
... ... ...
255 F
F
When the power supply is applied, the controller checks which address is set with the
2 hardware switches. This hardware address is then adopted. After the address is
changed, the power supply must be briefly switched off and on again.
Software setting
Both switches are set to 0 at delivery. With this setting, the address can be changed in
the software as of firmware status 04 December 2008 or later. See the separate
NanoPro manual.
Issue: V 1.0
19