L1
Flashing slowly
L2
-
P1
-
Valve
On for a maximum of 20 seconds.
Alarm
-
Cleaning routine 1
Even if the valve is opened, the minimum level is not reached within 20 seconds. The condensate
drain tries with repeated on/off cycles to unblock the situation probably caused by clogging.
L1
-
L2
Flashing slowly
P1
-
Valve
1.
On for 2 seconds.
2.
Off for 2 seconds.
3.
Repeated 30 times.
Alarm
-
Cleaning routine 2
After cleaning routine 1, the minimum level has not been reached. The condensate drain continues
to operate as a timer, continuing with the on/off sequence and continues with alarm modalities.
L1
-
L2
Flashing quickly
P1
-
Valve
1.
On for 3 seconds.
2.
Off for 60 seconds.
Alarm
On
Irreversible error
A fault has occurred in the system. Try with the reset function. If the problem reoccurs, a technical
intervention is required.
L1
-
L2
On
P1
-
Valve
1.
On for 3 seconds.
2.
Off for 60 seconds.
Alarm
On
Manual condensate draining
When the test button is pressed, the condensate is discharged manually.
L1
Flashing quickly
Instruction book
2920 7213 30
15