11. WHEN UNIT IS IN OPERATION THE PANELVIEW DISPLAY ON THE
ENCLOSURE DOOR WILL SHOW THE DRYER STATUS AND
ANY ALARM CONDITIONS.
12. WHEN AN ALARM CONDITION IS ACTIVE THE PANELVIEW
DISPLAY WILL DISPLAY THE ALARM CONDTION ACTIVE, ALSO THE
COMMON ALARM LIGHT WILL BE ON WHEN AN ALARM IS ACTIVE
AND THE COMMON ALARM RELAY INSIDE THE ENCLOSURE WILL DE-
ENERGIZE. AFTER PROBLEM HAS BEEN CORRECTED THE ALARM
CONDITION WILL RESET AUTOMATICALLY.
(NOTE: A SET OF DRY COMMON ALARM CONTACTS FOR REMOTE
INDICATION ARE AVAILABLE INSIDE THE ENCLOSURE SEE
ELECTRICAL DWG. FOR TERMINAL NUMBERS)
13. HEATER TEMPERATURE CONTROLS ARE ALL FACTORY SET AND
NOT ADJUSTABLE.
14. THE DRYER CYCLE TIME IS:
4 HOURS DRYING
3 HOURS HEATING
50 MINUTES COOLING
10 MINUTES REPRESSURIZATION
Shut-down procedure
Note: this type of dryer operates best if left on whenever possible with air
supplied to the unit.
The unit can be left pressurized after the dryer is switched off.
If the dryer needs to be turned off and depressurized, do the
following:
1.
Slowly OPEN the by-pass valve.
2.
Slowly CLOSE the Inlet and outlet "shut-
off” valves.
3.
Slowly open the purge exhaust valves and the dryer system starts to
depressurize. Switch off electrical power after both towers have been
depressurized.(The Dryer can also be depressurized through the valve
on the After Filter drain and through the Inlet Filter drain.)