background image

SUGGESTED SPECIFICATION:
MODEL: 1290F

Provide and install, as shown on plans and/or schedules True Round Fire Dampers, as manufactured by Nailor Industries,
meeting or exceeding the following criteria: Frame/integral sleeve shall be roll-formed from 20 ga. (1.0) galvanized steel,
beaded for structural strength and grooved to accept 20 ga. (1.0) galvanized steel retaining plate. Required sleeve length shall
be field verified by contractor. Each damper shall be complete with retaining plate and 20 ga. (1.0) galvanized steel damper
plate, supplied by the damper manufacturer to ensure proper fit and installation. Blade shall be of two 20 ga. (1.0) galvanized
steel pieces laminated together with an equivalent thickness of 14 ga. (2.0). Blades axles shall be 1/2" (13) dia. plated steel
double bolted to blade. Hex or square friction-fit or press-fit axles are not acceptable. Bearings shall be self lubricating oilite
bronze type.

Fire dampers shall meet the requirements of NFPA 80, 90A & 101, and shall be manufactured, tested and labeled in accordance
with UL 555 Safety Standard for Fire Dampers – Sixth Edition, June 1999, including Dynamic Closure Test. Dampers shall be
classified for dynamic closure against an airflow velocity of 2000 fpm (10.16 m/s) at 4" w.g. (1 kPa) static pressure differential
(across closed damper).
Each fire damper shall bear a UL 1 1/2 hour fire resistance rating label, in addition to label verifying the airflow and closure
pressure ratings as established by the Dynamic Closure Test. Each fire damper shall also be marked with the words "For use
in dynamic systems". Dampers marked "For use in static systems only" are not acceptable.

Each fire damper shall be complete with a 

(specifier select one)

165°F (74°C) 

or

212°F (100°C) UL listed fusible link that will

cause the damper to close and lock in closed position by means of an over-center/knee lock linkage for assured closure. Each
fire damper shall be supplied with a manual quadrant for setting and locking of blades in desired position. Contractor shall
provide and install an access door at each fire damper, of appropriate size to allow for inspection, testing and fusible link
replacement. Information submitted for approval shall include independent pressure drop data and confirmation of UL
qualifications in addition to manufacturer’s installation instructions. Each shipment of fire dampers shall include same
installation instructions. Standard of acceptance: Nailor Industries Model 1290F.

E22

TRUE ROUND FIRE DAMPERS

MODEL: 1290F

PERFORMANCE DATA:

3
0
0

1
0
0

2
0
0

3
0
0
0

4
0
0
0

6
0
0
0

7
0
0
0

.40

.02

.03

.04

.05

.06

.07

.08

.09

.20

.50

.60

.70

.30

1
5
0
0

5
0
0

7
0
0

4
0
0

2
0
0
0

1
0
0
0

.10

.25

.15

5
0
0
0

.015

.01

6" dia.

8" dia.

10"dia.

12"dia. 14"dia. 16"dia.18"dia.

Air Volume in CFM (through face area)

Static Pressure Dr

op in inc

hes w

.g.

.3

.2

3

4

4

.2

.3

.4

.5

.6

.7

.8

.9

2

5

6

7

3

1.5

.5

.7

.4

2

1

1.0

2.5

1.5

5

.15

.1

18" dia.

Air Leakage in CFM/ sq. ft. (through face area)

Static Pressure in inc

hes w

.g.

PRESSURE DROP (damper fully open)

AIR LEAKAGE (damper closed)

Tested per AMCA standard 500-D, Fig. 5.3.

Tested per AMCA standard 500-D, Fig. 5.5.

Imperial figures shown.

To convert to SI

(metric) system:

Multiply:

CFM x .4719 = liters

per second

inches w.g. x .2486

= kilopascals

fpm x .00508 = meters

per second

cfm per sq. ft. x 5.08 =

liters/second per 

sq. meter.

E

MUL

TI-BLADE

FIRE

DAMPERS

E22

Revised September 7, 2004

HOW TO SPECIFY

Previous View

Contents

Dimensions

Performance

Specification

Home

Specification Text File

Summary of Contents for D1200 Series

Page 1: ...E1 E1 MULTI BLADE FIRE DAMPERS MULTI BLADE FIRE DAMPERS Nailor Industries Inc Previous View Contents Dimensions Performance Specification Home...

Page 2: ...ic 1 1 2 Hour E17 Round Fire Dampers Model Series 1290F Dynamic 1 1 2 Hour E21 Options Variables Closure Temperatures Fusible Link Temperature Ratings E24 Optional Seals JSM Jamb Seals E24 BSP Blade S...

Page 3: ...ire and combination fire smoke dampers and accessories available at a reasonable cost and in a timely fashion Nailor s multi blade type fire dampers are available in several blade and frame styles inc...

Page 4: ...ings of less than 3 hours Model 1200 GENERAL PRODUCT OVERVIEW MODEL 1290F TRUE ROUND FIRE DAMPER FOR STATIC OR DYNAMIC SYSTEMS Model 1290F is suitable for use where building codes require a fire dampe...

Page 5: ...r the majority of today s applications MODELS D1200 1 1 2 HR LABEL D1200 3 3 HOUR LABEL AIRFOIL BLADE FIRE DAMPERS E5 E MULTI BLADE FIRE DAMPERS AIRFOIL QUALIFICATIONS UL 555 CLASSIFIED DYNAMIC FIRE D...

Page 6: ...rtical mount 34 x 46 864 x 1168 Horizontal mount 30 x 46 762 x 1168 Multiple Section Assembly Model 1203 Vertical mount 70 x 46 1778 x 1168 or 34 x 94 864 x 2388 Horizontal mount 62 x 46 1575 x 1168 o...

Page 7: ...R 300 MLS 300 Switch Pack SIDE MTG PLATE SMP Side Mounting Plate required for mounting of MLS 300 without sleeve RETAINING ANGLES QS1 One Quick Set retaining angle QS2 Set of two Quick Set retaining a...

Page 8: ...e shall be zero maintenance concealed in frame out of airstream Fire dampers shall meet the requirements of NFPA 90A and shall be manufactured tested and labeled in accordance with UL 555 Safety Stand...

Page 9: ...x 7 8 x 16 ga 127 x 22 x 1 6 galvanized steel hat channel Blades 14 ga 2 0 equivalent galvanized steel formed airfoil on 5 1 2 140 centers Opposed action Sleeve 16 x 20 ga 406 x 1 0 galvanized steel...

Page 10: ...TION SHOULD BE SIZED 1 2 13 LARGER IN ALL DIRECTIONS TO ALLOW FOR SLEEVE THICKNESS 2 FOR PERFORMANCE DATA SEE MODEL D1200 MODEL D1221 OW OUT OF WALL MOUNTING A Typical 2 hour rated vertical concrete o...

Page 11: ...JSM Flexible Metal Jamb Seals ACCESSORIES CODE DESCRIPTION POSITION INDICATOR 300 MLS 300 Switch Pack RETAINING ANGLES QS1 One Quick Set retaining angle E11 OUT OF WALL MULTI BLADE FIRE DAMPERS E MUL...

Page 12: ...ity of 2000 fpm 10 16 m s at 4 w g 1 kPa static pressure differential across closed damper Each fire damper shall bear a UL 1 1 2 hour fire resistance rating label in addition to label verifying the a...

Page 13: ...hand locking quadrant to hold blades in open position or balance the system the 1200 Series is available with factory fitted sleeve ready for installation and choice of transition styles to suit duct...

Page 14: ...n Vertical mount 34 x 46 864 x 1168 Horizontal mount 30 x 46 762 x 1168 Multiple Section Assembly Model 1203 Vertical or Horizontal mount 142 x 94 3658 x 2388 8 203 SLEEVE DAMPER 16 406 STANDARD B ENC...

Page 15: ...S 300 Switch Pack SIDE MTG PLATE SMP Side Mounting Plate required for mounting of MLS 300 without sleeve RETAINING ANGLES QS1 One Quick Set retaining angle QS2 Set of two Quick Set retaining angles FL...

Page 16: ...blade to provide positive locking connection Hex or square friction fit or press fit axles are not acceptable Bearings shall be self lubricating oilite bronze type Blade linkage shall be zero mainten...

Page 17: ...ork Board of Standards and Appeals Cal No 460 88 SA Meets NFPA 80 90A and 101 as well as IBC and NBC Canada and associated building code requirements Maximum velocity 2000 fpm 4 w g 10 m s 1 kPa up to...

Page 18: ...bly Vertical mount 46 1168 diameter Horizontal mount 38 965 diameter 8 203 OVERALL H NOM DUCT SIZE W NOM DUCT SIZE D 2 51 D NOM DUCT DIA D 2 51 SLEEVE DAMPER CCW TO OPEN C ENCLOSURE BOTH ENDS D 1 8 3...

Page 19: ...ON CO Oval Type C Transitions CSR Square Rect Type C Transitions DAMPER LOCATION L8 8 204 from Sleeve End IN SLEEVE L0 Specify Dimension from Sleeve End OPTIONAL JAMB SEALS JSM Flexible Metal Jamb Sea...

Page 20: ...uirements of NFPA 90A and shall be manufactured tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers Sixth Edition June 1999 including Dynamic Closure Test Dampers shall be cl...

Page 21: ...TRUE ROUND FIRE DAMPERS E21 E MULTI BLADE FIRE DAMPERS CCW TO OPEN 5 3 4 146 16 406 STANDARD NOM DIA 1 8 3 DRIVE SHAFT INSTALLATION RETAINING PLATES INCLUDED Wall Minimum Thickness Sleeve Length 4 to...

Page 22: ...able Each fire damper shall be complete with a specifier select one 165 F 74 C or 212 F 100 C UL listed fusible link that will cause the damper to close and lock in closed position by means of an over...

Page 23: ...S E23 ROUND FIRE DAMPER MODEL 1290F HOW TO ORDER Select model number and size then select from each variable as applicable Choose accessories as desired See above for description of variables and acce...

Page 24: ...ION CODE BSP PVC BLADE SEALS Fusible links for Model Series D 1200 D1250 and 1290F fire dampers are available with a choice of several melting temperature ratings Nailor fire dampers are provided as s...

Page 25: ...ming and troublesome procedure Eight conventional angles must be custom fabricated for each damper either in a sheet metal shop or at the job site and sized to suit each individual damper Invariably t...

Page 26: ...The following indicates model numbers to order for multi blade fire dampers with factory fitted Type A sleeves All fire dampers require a steel sleeve of correct length and gauge in order to be insta...

Page 27: ...ems are approved as breakaway connections for connecting a multi blade fire damper Type A sleeve 22 or 20 gauge to ductwork They may be used in place of the approved slip joints shown in standard inst...

Page 28: ...E28 MULTI BLADE FIRE DAMPERS E MULTI BLADE FIRE DAMPERS E28 Notes www nailor com Previous View Contents Dimensions Performance Specification Home...

Reviews: