INSTALLATION
ACGW007 – MODBUS RTU TO BACnet / IP & MS / TP Gateway
INSTALLATION OUTLINE
1.
Mount unit.
2.
Connect to fan filter network using factory provided RJ45 inline coupler and serial cable.
3.
Connect 3-pin screw terminals to BACnet MS/TP or BACnet IP network.
4.
Verify switch settings (next page).
5.
Connect to power (9 – 30 VDC, 12 – 24 VAC, 2.5 W).
6.
Verify operation (see ACGW007 User Guide).
MOUNTING
The ACGW007 can be mounted to a flat surface or to a DIN rail.
Remove the DIN rail cleat prior to mounting to a flat surface (so
that the two mounting flanges will be in contact with the surface
and not raised).
Page 14 of 24
9/18 IOM-FFDINST