NAUTILUS 10●520
Three phase in/out
Rev.00
– 09 Luglio 2015
3
1. Safety
Important safety instructions
– Save these instructions
There exists dangerous voltage and high temperature inside the UPS. During the installation, operation
and maintenance, please abide the local safety instructions and related laws, otherwise it will result in
personnel injury or equipment damage. Safety instructions in this manual act as a supplementary for the
local safety instructions. Our Company will not assume the liability that caused by disobeying safety
instructions..
1.1 Safety Notes
1. Even with no connection with utility power, 220/230/240VAC voltage may still exist at UPS outlet
!
2. For the sake of human being safety, please well connect to earth the UPS before starting it.
3. Don
’t open or damage battery, for the liquid spilled from the battery is strongly poisonous and do
harmful to body
!
4. Please avoid short circuit between anode and cathode of battery, otherwise, it will cause spark or fire
!
5. Don
’t disassemble the UPS cover, or there may be risk of electrical shock
!
6. Check if there exists high voltage before touching the battery
7. Working environment and storage way will affect the lifetime and reliability of the UPS. Avoid the UPS
from working under following environment for long time
◆
Area where the humidity and temperature is out of the specified range (temperature 0 to 40
℃
,
relative humidity 5%-95%)
◆
Direct sunlight or location nearby heat
◆
Vibration Area with possibility to get the UPS crashed.
◆
Area with erosive gas, flammable gas, excessive dust, etc
8. Keep ventilations in good conditions otherwise the components inside the UPS will be over-heated
which may affect the life of the UPS.
1.2 Symbols used in this guide
WARNING! Risk of electrical shock
WARNING! Read this information carefully to avoid damage on equipment
2. Main Features
2.1 Summary
This is a UPS series On-line double conversion at high frequency with three-phase input and output. It use
a modular architecture, with N+X redundancy. The number of power modules installed may change
according to the load. This scalability features may help to optimize the Total Cost of Ownership.
The UPs may solve most of the problems of electrical network, such as blackouts, overvoltage,
undervoltage, voltage dips, voltage surge, fluctuations, overcurrent, current peaks, harmonic distortion
(THD), interference noise, frequency oscillations, etc.
The UPS may be installed in many different applications: data centers, IT installations, telecommunication
systems, industrial systems, POS, etc.
2.2. Functions and Characteristics
◆
Digital Control
◆
Standard 19” cabinet with height 1400 - 1600 – 2000cm according to the application’spec.
◆
Modular design.
◆
High power-density design.
Each Power module is 3U high. The cabinet 1400cm high may contain up to 5 Power modules, while
2000cm cabinet may host up to 10 modules.
◆
N+X parallel redundancy
In fact, this series is designed for a N+X redundant architecture. The user can set the type of redundancy
based on the importance and type of load. Through the settings of the LCD display it is possible to
configure the number of modules necessary for the parallel operation. When the load exceeds the range
of the redundant units, the UPS will report it immediately. When the load exceeds the redundancy setting,