20
Y-KH15-007A Rev.3
Current output can be checked with a check terminal (+CH) without
removing any wiring. Use an ammeter with an internal res
istance of 10Ω
or less during checking.
Avoid electrostatic charge.
To clean the appearance of the product, use a water-soaked soft
cloth. Do not use thinner and benzine that cause degradation or
failures.
■
12.2 Adjustment
Remove the terminal box lid to adjust the output of this product. When removing the lid, you will see
the plate as shown in Figure 8-7 below. The characters “Z” and “S” printed on the plate are trimmers
for zero and span adjustment respectively.
Do not perform an adjustment when the surface of the product is
wet. Moisture getting inside the product will cause a failure.
Never cause short circuits with a driver (be sure to use a resin or
ceramic driver).
After powering on, wait at least 5 minutes for warm-up in an
energizing state before performing an adjustment.
Care should be taken to prevent excessive load on trimmers.
Otherwise, trimmers (circuit parts) may be damaged.
For adjustment, use the reference pressure gauge and
measuring instrument with traceability ensured.
CAUTION
CAUTION
KH15-J-
□□
(current output)
KH15-K-
□□
(current output)
< Figure 12-1 >
Span trimmer
Zero trimmer
Plate
Zero trimmer
Plate
Span trimmer