User should use internal and external accessories provided by Nader so as to endure their
quality; Nader should not be held reliable for purchase of accessories from other companies or
authorized modifications.
在执行维护操作前,必须先完成下列操作:
Follow following steps before conducting maintenance:
(1)使断路器分闸;
Open the breaker;
(2)断开电源与断路器的连接(包括主电路、辅助电路);
Disconnect power supply and breaker (including main circuit and auxiliary circuits)
(3)将断路器从安装位置上卸下(一般用于插入式,固定式最好也如此)
Remove the breaker from its installation position (normally for plug-in installation; it is
recommended to
do so for a fixing one).
断路器维护在正常操作条件下每年一次,在非正常条件下每半年一次,以下为维护内容:
Maintenance of breaker is carried out yearly under normal use and every six months under
abnormal use. The maintenance includes following procedures:
(1)再扣断路器,合、分断路器,在断路器合闸时用脱扣按钮使断路器脱扣,往复操作 5 次,断路器
应能可靠进行再扣、合、分、脱扣动作;
(2)清除断路器表面及连接处的灰尘(用清洁、干燥的抹布擦拭);
(3)清洁隔弧板,如必要则需要更换隔弧板;
(4)绝缘测试(见 7.1)
(5)检查所有连接情况,用砂布擦除氧化物,用可溶解剂清洁,拧紧螺栓和螺母;
(6)控制器整定值测试:应使用我公司的 NDM3E 专用测试仪器与断路器的 TEST 端口连接,检验各
个设定参数,以保证参数设定与旋钮指示一致;
(7)如果断路器还装有其它内、外部附件,应逐一检查各个附件,以确保其处于正常工作状态。
(按照 8 附件说明 详细内容进行测试)
(1)
Re-trip the breaker, close and open the breaker, use tripping button to trip the breaker when it is
closed;
repeat for 5 times to check that the breaker can reliably re-trip, open, close and trip.
(2)Clean dust on breaker surface and connections (wipe with clean and dry cloth).
(3)Clean the flash barrier; replace it if necessary.
(4)Carry out insulation test (see Section 7.1).
(5)Check condition of all connections. Wipe away oxidations with abrasive cloth and clean with
soluble agent
. Screw bolts and nuts tight.
(6)Test of controller setting values: use a tester specialized for NDM3E provided by Nader to
connect with TEST terminal of the breaker. Check setting of each parameter to ensure that
parameter setting is consistent with knob indication.