12.

 

注意事项/ Notes 

12.1 安装注意事项 Precautions in installation 
(1)断路器本体、底板(板后接线用)、底座(插入式接线用)固定在安装板上。 
(2)与主电路连接必须由具有专业资格的人员进行配线作业。 

(3)确认输入电源处在完全断开的情况下,才能进行配线作业。 
(4)必须安装本体后再进行配线。  
(1) Breaker body, bottom plate (for wiring behind the plate) and base (for plug-in wiring) are 

mounted on the  

installation board. 

(2) For connection with the main circuit, the wiring should be done by professional qualified 

personnel. 

(3)Wiring should be done after confirmation of complete disconnection of input power supply.  
(4)Wiring should be done after installation of breaker body. 

12.2 运行注意事项 Precautions in operation 
(1)湿手不能操作断路器,否则可能发生电击事故。 
(2)断路器不能频繁操作,否则会缩短断路器的使用寿命。 
(3)带电动操作机构的断路器脱扣跳闸后,电操机构必须使断路器再扣,然后才能合闸。 

(1) Do not operate the breaker with wet hands, or electric shock would be resulted. 
(2) Frequent operation will shorten service life of the breaker. 
(3) For breaker with motor-operated mechanism, after it trips, the motor-operated mechanism 

should re-trip the breaker before it can be closed. 
12.3 保修期与售后服务 After-sales service and warranty 

本产品是在完善的品质管理体系下制造的,当万一发生故障时,对保修期与售后服务特作如下说明:

This product is manufactured in a sophisticated quality management system. In case of fault, 
following warranty and after services clauses are applicable: 
保修期/ Warranty period 

 

在用户遵守保管和使用条件下,从本公司发货之日起,不超过 36 个月,断路器封印完好,产品如因

制造质量问题而发生损坏或不能正常使用时,本公司负责无偿修理或更换。但是,如由于下述原因引起的
故障,即使在保修期内亦作有偿修理或更换。 

On the premise of user’s compliance with reservation and use specifications of the breaker, 

for breakers whose delivery date is within 36 months from now and whose seals are intact, Nader 
will repair or replace any of these breakers which are damaged or cannot work normally due to 
manufacture quality. However, as for faults caused by following reasons, Nader would repair or 
replace the breaker with a charge even it is still in warranty. 
(1)由于使用错误、自行改装及不适当的维修等原因。 
(2)超过标准规范的要求使用。 
(3)购买后由于摔落及安装过程中发生损坏等原因。 
(4)地震、火灾、雷击、异常电压、其他天灾及二次灾害等原因。 

(1) Misuse, unauthorized modifications and improper repair, etc 

(2) Use during which standards and specifications are violated 
(3) Damages caused by falling or improper installation, etc.  
(4) Natural disasters and secondary disasters such as earthquake, fire, thunder and abnormal 

voltage, etc 
售后服务/ After-sales service 
(1)出现故障时,请与供货商或本公司售后服务部门联系。 
(2)保修期内的修理或更换:由于本公司制造上的问题所造成的故障,作无偿修理,以至更换。 
(3)超过保修期后的修理或更换:在修理后能维持功能的场合下,作有偿修理,否则可作有偿更换。 

(1) Contact distributor or Nader after-sales department in case of breaker fault. 
(2) Breakers in warranty will be repaired or replaces; for faults caused by manufacture of Nader, 

product will be repaired for free or even replace with a new one. 

Summary of Contents for NDM3E Series

Page 1: ...000 201315 021 68586699 021 23025796 1 39 Shanghai Liangxin Electrical Co Ltd NDM3E NDM3E Series Moulded Case Circuit Breaker Product Manual IPD ENG DEV T32 A0 2019 11 05 2020 07 29 2020 07 29 2020 07...

Page 2: ...68586699 021 23025796 2 39 Revision information Version Revised contents and reasons Date Prepared Review ed Approved 5 3 2 Update the technical patameters of project 3 see table 2 for details 202007...

Page 3: ...and implication 4 3 Main technical parameters 7 4 Stand working conditions 20 5 Wiring Method 22 6 Shape dimension Dimension 23 7 Mounting Method 25 8 Accessory 26 9 Application Maintenance 27 10 Not...

Page 4: ...D Nader low voltage electric appliance 2 Product code M Molded case circuit breaker 3 Design code 3 4 Derived code E E Electronic type 5 Rated frame current 125 250 400 630 800 6 Breaking class code M...

Page 5: ...release double auxiliary contact 340 Shunt release Under voltage release 350 Two groups of double auxiliary contact 360 Under voltage release double auxiliary contact 370 Single auxiliary contact 321...

Page 6: ...auxiliary alarm right double auxiliary 368 Left shunt right single auxiliary 341 Left Under voltage right single auxiliary 371 Left single auxiliary right single auxiliary 361 Left double auxiliary ri...

Page 7: ...1000 1000 kV Uimp Rated impulse withstand voltage 8 8 V Ue AC50 60Hz Rated working voltage 380 400 415 380 400 415 660 690 660 690 Breaking capacity H M H M kA Icu AC380 400 415V Rated ultimate breaki...

Page 8: ...Ue AC50 60Hz Rated working voltage 380 400 415 380 400 415 380 400 415 660 690 660 690 660 690 Breaking capacity H M H M H M kA Icu AC380 400 415V Rated ultimate breaking capacity 100 70 100 70 100 7...

Page 9: ...rt time delay 5 Tsd Ts Setting time of short circuit short time delay 6 Ii Setting current of short circuit instant 7 Ip Setting current of pre alarm 8 IRN Protection current of neutral line 9 Ig Sett...

Page 10: ...Fig 1 NDM3E controller panel figure 3 2 2 NDM3E Functions of each part in control panel of NDM3E controller 3 2 2 1 Test port TEST NDM3E Through this TEST terminal special tester for NDM3E is connect...

Page 11: ...hall be tripped in advance If it is less than the value specified in the previous paragraph and the time until the tripping time The current is not reduced to 1 5 IR or less then the time specified in...

Page 12: ...arameters Closing and opening state of the breaker Real time current passing through each pole of the breaker NDM3E Modbus RTU The on site bus protocol of NDM3E breaker s communication port Modbus RTU...

Page 13: ...pair each communication cable can connect 32 devices at most The longest line could be 1200 meters and the communication distance can be lengthened by adding repeaters 1 2K 2 4K 4 8K 7 2K 9 6K 19 2K b...

Page 14: ...he function of alarm without tripping for overload namely in the case of overload on the circuit the breaker only outputs overload signals with tripping which can ensure continuity of powering supply...

Page 15: ...IR Notes 1 When the product is grounding type Tsd can t be set if there isn t requirement in the order the default value is 0 3s 2 When the product is grounding type Ip can t be set if there isn t req...

Page 16: ...is 1A 2 When the non communication product is grounding type G type Ts can t be set if there isn t requirement in the order the default value is 0 3s 3 When the non communication product is grounding...

Page 17: ...le and motor operated mechanism see Section Connection of communication breaker and the computer are shown as follows RS 232 RS 485 RS 485 RS 232 RS 485 RS 232 RS 485 RS 232 RS 232 RS 232 RS 485 5 Con...

Page 18: ...connected breaker Factory default settings baud rate 9600 and sub station address 3 After setting the parameters click the Connect button on software interface if communication link is working correc...

Page 19: ...ter communication link is working correctly Example IR 200A Tr 60s Isd 1000A Tsd 0 1s Ii 2000A and tick on box in front of the setting current or setting time which you want to adjust see Fig 8 Then c...

Page 20: ...e breaker cannot work normally 4 Do not install the breaker in places with vibration more than 5g 5 Do not install the breaker in places with gaseous medium corrosive to metal and aggressive to insula...

Page 21: ...957 800A 1 1 1 0 980 0 958 0 936 0 913 50 Notes When ambient temperature is less than 40 breaker can be used normally without any derating 7 Altitude derating 2000m Altitude of service conditions more...

Page 22: ...select proper wiring methods according to the Appearance Installation Dimensions and Wiring Methods 2 The copper busbar in such dimensions can t be directly connected to the noumenon connecting line...

Page 23: ...and electric operation 6 1 2 Overall dimensions With communication backpack and electric operation 13 Table 13 Overall dimensions With communication backpack and electric operation 12 Type Overall dim...

Page 24: ...les 3 4 3 4 3 4 3 4 3 4 mm Mounting plate cutout dimensions mm A 30 35 44 70 70 B 129 126 194 243 243 C 4 5 4 5 7 7 7 6 2 2 X X Y Y 13 2 Rear connected X X Y Y center for three poles breaker please re...

Page 25: ...viation not indicated with the tolerance dimensions is as per GB T 1804 m 7 Mounting Method 7 1 mm 7 1 Insulation distance mounted in the metal cabinet unit mm as shown below Mounting distance A A inl...

Page 26: ...breaker has gone through specified standard insulation test before factory delivery Because many PCBs are installed in the breaker for re testing please conduct tests according to following procedure...

Page 27: ...irect current 2 At rated control supply voltage of 35 70 Under voltage release should be reliable to trip breakers 3 At rated control supply voltage of 85 110 Under voltage release should be able to c...

Page 28: ...s of the breaker Connection status of the circuit Auxiliary contact Open or free tripping Close Mutual transferring between On and Off Alarm contact Open or closing free tripping Mutual transferring b...

Page 29: ...n hole center and hinge should not exceed 100mm 2 Install the breaker which has been fixed with the operating mechanism on surface cover on the installation board and fasten it slightly 3 Fasten the s...

Page 30: ...mmissioning 1 IR TR Isd Tsd Ii Ip 2 3 4 1 Adjust values of IR TR Isd Tsd Ii and Ip etc s in panel as needed 2 Operate the handle and connect power supply 3 After the main circuit of the breaker is ele...

Page 31: ...of controller setting values use a tester specialized for NDM3E provided by Nader to connect with TEST terminal of the breaker Check setting of each parameter to ensure that parameter setting is cons...

Page 32: ...R_AT Type of failure alarm UINT R 0x0011 P U 22 See Table 22 18 R_ST Automatic diagnosis of failure type UINT R 0x0012 P U 23 See Table 23 19 R_OT Reserved UINT R 0x0013 P U 20 R_CT Reserved UINT R 0...

Page 33: ...37 CoA L1 L1 phase current calibration coefficient UINT R W 0x0023 P U R ZOOM 38 CoA1 L1 L1 phase current calibration coefficient UINT R W 0x0024 P U R RAW 39 CoB L2 L2 phase current calibration coeff...

Page 34: ...R 0x0067 U 57 P_FP Memory failure phase of the last time UINT R 0x0068 U 20 Same with Table 20 58 P_FT Memory failure time of the last time UINT R 0x0069 U x 20ms 1 0x0000 0x0800 2 N 1 2 3 N Note 1 0x...

Page 35: ...rt time delay 1 OFF 0 ON 1 0 Grounding mode 1 tripping 0 alarming 1 0 The numbers of poles for circuit breakers 1 4 poles 0 3 poles 1 0 Usage of circuit breakers 1 distributi on 0 else 1 0 Compensatio...

Page 36: ...elay 1 OFF 0 ON 1 0 Grounding mode 1 tripping 0 alarming 1 0 Operation state 1 remote 0 local bit8 bit9 bit10 bit11 bit12 bit13 bit14 bit15 30 Table 30 Grounding mode 0 1 2 4 No grounding N N phase pr...

Page 37: ...on only programmer is available 17 0x11 Function code 17 0x11 Inquiry Answer 0 Definition of the equipment type Address 0 A B C D Bit15 Bit0 Byte descriptions A Arrangement of large class 0x03 MCCB Mo...

Page 38: ...gement system In case of fault following warranty and after services clauses are applicable Warranty period 36 On the premise of user s compliance with reservation and use specifications of the breake...

Page 39: ...familiar with technical files of this product and place order by the Ordering Specifications form according to future application of breaker 2 If customer has not put forward any requirement on prote...