SECTION 3.5: Output Power Guidelines
TOTAL
current draw from the Opus Control must not exceed 0.7A when providing power to:
X
Sensors
X
Modules
X
Accessories
X
Auxiliary Equipment
An auxiliary power supply, (e.g. NABCO Transformer 24VDC power supply p/n V-00022) must be utilized if TOTAL current draw
exceeds 0.7A.
The Opus Control must Not be used to power: Magnetic Locks nor Electric Locks
To determine if an auxiliary power supply must be used, add the total current draw of all devices. Please refer to the formula below:
Example: An Automatic Door System is to be fitted with the following devices:
2 x Acusensor M @ 150 mA = 300 mA
1 x Cp/RX Radio Control Receiver @ 50 mA = 50 mA
Total = 350 mA
350mA does not exceed total current draw .
An Auxiliary Power Supply does not need to be used .
SECTION 3.6: The Opus Control for Swing Doors
Note: The Hold Close feature is enabled when the LCD screen is OFF, or disabled when the LCD screen is LIT.
DN 2415
①
②
③
④
⑤
⑥
⑦
⑧
1 CN3
I/O Terminal Strip
5
-
LCD Screen
2 CN5
Relay Output Terminal Strip
6 CN2
Motor Connector
3 CN4
CAN Bus Communication
7
CN1
Power Connector
4
-
Rotary Dial
8 -
Fuse
SECTION 3.7: Navigate with the Rotary Dial
DN 1242
Type:
GT710 Swing
Status:
Slow Closing
Error:
-----
Ac va on: IN EXT
Posi on:
> > > > > >
Other:
BA 6B SWL
Push and Hold Dial
Go to Se ng Mode
Rotary Dial
UNIT SPECIFICATIONS
11
20
10
12
LCD Screen
Fully Closed
Figure 1
The Rotary Dial
X
Push down on the Rotary Dial:
1. Long push (2) seconds to gain access to LCD Category Screens.
2. Short push under (2) seconds to access Sub-level screens, and to selected/unselect menu items.
3. Long push (2) seconds to go back to Main screen.
4. Long push (2) seconds to go back to Main screen.
CAUTION