Trouble Shooting 

Use the table below to solve minor installation and operation problems.   

Symptom 

Possible cause 

Remedy 

Battery cannot 
discharge. 

Same  ID  code  set  in 
multiple battery packs. 

Re-set  each  battery  with 
different ID codes. 

Protection  against  under-
voltage. 

Charge battery. 

Protection  against  over-
temperature  or  under-

temperature 

(cell 

temperature is lower than 

-20°C  or  higher  than 
80°C). 

Regulate  cell  temperature 
in  the  range  of  -20°C  to 

60°C for discharge. 

Protection  against  over 

current 

Remove  some  non-critical 

load and charge battery. 

Battery output is short 

circuit 

Relieve short circuit and 

charge battery 

System failure detected 

Shut down system and 

call maintenance service 

In parallel battery packs, 

CAN communication lost 
and “parallel imbalance” 

occur on slave battery.   

Ensure communication 
wires are all correctly 

connected well.   

Battery cannot 
charge. 

Protection against over 

current. 

Ensure power shelf setting 

is not over 1C for battery. 

Protection against over-
temperature or under- 

temperature (cell 
temperature is lower than 
0°C or higher than 60°C) 

Regulate cell temperature 

in the range of 0°C to 
50°C for charge 

System failure detected 

Shut down system and 
call maintenance service. 

Communication 

failure is detected. 

Communication cable 

Check if communication 

cable is firmly connected. 

Communication address 
conflict   

Check the parallel 

batteries address setting 
and correct them. 

System failure detected 

Shut down system and 

call maintenance service. 

 

Summary of Contents for LR Series

Page 1: ...LR Series Lithium Iron Phosphate Battery Module N1C L4850EBM2U N1C L48100EBM3U Version 1 1 User Manual...

Page 2: ...ifications 5 2 5 Product Indicator Setting 6 3 Safe handling of lithium batteries guide 11 3 1 Product handling guidelines 11 3 2 Explanation of symbol 11 4 Installation 12 4 1 Installation Environmen...

Page 3: ...tentially rendering it inoperable 2 If the battery is stored for a long time it is required to charge them every six months and the SOC should be no less than 90 3 Battery needs to be recharged within...

Page 4: ...be well grounded and the resistance must be less than 1 7 Please ensure the electrical parameters of the battery system are compatible with related equipment 8 Keep the battery away from water and fi...

Page 5: ...an balance cells charging and discharging to extend cycle life These two battery modules can be used alone or in parallel to expand capacity for different requirements 2 1 Features Non Toxic non pollu...

Page 6: ...r dispose of it properly Module x1 Manual x1 Quick Installation Guide x1 Ear Kit x1 Screws x8 Battery cable x1 RJ45 cable x1 RJ11 cable x1 Signal cable x1 Optional Battery cable x 1 Rail Slide Kit Can...

Page 7: ...C Standard Charge Method 0 2C CC Constant Current chare to FC CV Constant Voltage charge till chargecurrent decline to 0 05C Inner Resistance 20m ohm Storage Temperature 20 25 18 months Max 80 RH 25 4...

Page 8: ...6 2 5 Product Indicator Setting N1C L4850EBM2U front and rear panel N1C L48100EBM3U front and rear panel...

Page 9: ...r table for the details Battery Level LEDs Indicates battery level Please refer to the LED indicator table for the details LED Indicator Battery Status Battery Status LEDs Battery Level LEDs Status SO...

Page 10: ...8 Breaker Turn the breaker ON Connect cells to BMS Turn the breaker ON Shut down energy between Cells and BMS...

Page 11: ...ctor type RJ45 Function communication between battery module and power module Pin Definition PIN Definition 1 RS485B 2 RS485A 3 NC2 4 RS485B 5 RS485A 6 PresentA 7 PresentB 8 NC1 Extension Port Connect...

Page 12: ...D switch From number 0 to 9 the number can be random no particular order If more than one battery module in the parallel system the battery pack connected to the power module is the Master battery and...

Page 13: ...11 3 Safe handling of lithium batteries guide 3 1 Product handling guidelines 3 2 Explanation of symbol...

Page 14: ...e is within the range of 0 50 C The temperature and humidity are maintained at a constant level There is minimal dust and dirt in the area Caution If the ambient temperature is out of the operating ra...

Page 15: ...d damage Caution If there is breaker installed on the battery cable between power module and battery module turn on this breaker before battery module is powered on Otherwise it may cause surge curren...

Page 16: ...45 cable into the COM port on the battery module The other end connects to BMS communication port on the power module Power Module Battery module Insert signal cable into the extension port or 4 Turn...

Page 17: ...er module via CON1 or CON2 3 Insert the supplied RJ45 cable into the COM port on the battery module The other end connects to BMS communication port on the power module Power module conneting with mul...

Page 18: ...ry modules to connect the system repeat step 4 and 5 to connect more battery modules 7 After connecting all battery modules turn the breaker switch ON of each connected battery module Now the battery...

Page 19: ...e operating mode press manual ON OFF button for 5 secs 2 Or if battery module is not operated charge or discharge for 10 hours the battery module will automatically shut off 3 Or the battery module ha...

Page 20: ...e detected Shut down system and call maintenance service In parallel battery packs CAN communication lost and parallel imbalance occur on slave battery Ensure communication wires are all correctly con...

Reviews: