MODULE CONFIGURATION SETTINGS 

 

In order for the 900 Series modules to communicate properly the chassis must be populated with modules from 
the top

 slot down as shown below.  In addition, JP1 and JP2 jumpers (located on top side of all modules) 

must

 be 

configured as indicated below. 

 
Note: The power source must be disconnected from the 900B chassis prior to removing and inserting modules.  This 
unit is not hot swappable. 
 

 

One Slot Configuration - 

When installing a 

single

 902FX, 904FX, or 

908TX module in the top slot of the 900B chassis… 

Configure the 

module as follows:

 

JP1: pins 1 & 2 shorted 
JP2: pins 1 & 2 shorted  
 

 
 

 

Two Slot Configuration - 

When installing 

two

 902FX, 904FX, and/or 

908TX modules in the top two slots of the 900B chassis…  

Configure 

both modules as follows: 

JP1: pins 1 & 2 shorted 
JP2: pins 3 & 4 shorted 
 
 

 
 

Three Slot Configuration - 

When installing 

three

 902FX, 904FX, and/or 

908TX modules in all three slots of the 900B chassis… 

Configure  all 

modules as follows:

 

JP1: pins 3 & 4 shorted 
JP2: pins 3 & 4 shorted 

 
 
 

908TX Module - 

At power cycle, all LED’s flash on for approximately two seconds, and 

then return to proper state.  

 Green LED will light when Power is connected. 

 
 

902FX & 904FX Modules - 

At power cycle, only the LED’s on the first 

port flash on to indicate the reset condition, and then return to their proper 
state. All other reports remain off during reset. This is normal behavior. 

 

Green LED will light when Power is connected.

 

 

In order to verify the module jumper (JP1 & JP2) settings have been set correctly, for units which have the  

N-View option turned on

, you should install N-ViewOPC Server software on a PC connected to the LAN.  

The software is freely distributed on the ProductCD and our web site ( http://n-tron.com/nview.zip ).  Once N-
ViewOPC is installed, you should view the Ports Counter page to remotely monitor each connected port.  You 
may find it helpful to Copy [Alt]+[PrintScreen] the Port Counter information for each port and Paste 
[C[V] into a Windows document for further review.  Please consult your N-View OPC Server Manual 
for additional information. 

 

Summary of Contents for 900B

Page 1: ...900 Series Industrial Ethernet Switch Installation User s Guide...

Page 2: ...Rev050908 2...

Page 3: ...900B 900N 3 Slot Enclosure and Backplane 900B FP Filler Panel for empty slots 908TX Module 902FX SC Module 902FX ST Module 902FXE SC YY Module 902FXE ST YY Module 904FX SC Module 904FX ST Module 904F...

Page 4: ...limited to the implied warranties of merchantability or fitness for a particular purpose In no event shall N TRON Corp be liable for any incidental special indirect or consequential damages whatsoever...

Page 5: ...es during periods of lightning activity WARNING Do not perform any services on the unit unless qualified to do so WARNING Do not block the air vents WARNING Observe proper DC Voltage polarity when ins...

Page 6: ...with Local National Codes of Authorities Having Jurisdiction 4 Power must be supplied by an isolating source and a 3 3A max rated UL recognized fuse must be installed immediately before the unit 5 Cla...

Page 7: ...o supports MDIX auto sensing for auto connector of straight through or crossover cables and provides 8 Category 5 compliant 10 100 BaseT connections for high performance network design and hub repeate...

Page 8: ...n WARNING The 902FXE and 904FXE unit contain a class 1 laser Do not stare into the laser beam fiber optic connector when installing or operating the product Never install or work on electrical equipme...

Page 9: ...If Half Duplex operation is desired then follow these steps using proper wrist strap grounding techniques 1 Remove the power power plugs from the unit 2 Loosen all thumbscrews remove all modules 3 Rem...

Page 10: ...ssembly P N urface bly P N 90 Rail Recess for TX mode al DIN Rail lange of the aps into plac m industrial unit from t ely remove i were designe y not be su N 900 PM 00 RM may the unit to els Note Pla...

Page 11: ...sis Configure all modules as follows JP1 pins 3 4 shorted JP2 pins 3 4 shorted 908TX Module At power cycle all LED s flash on for approximately two seconds and then return to proper state Green LED wi...

Page 12: ...he table below describes the operating modes LED Color Description GREEN Power is Applied OFF Power is OFF LNK GREEN Link between ports established OFF No Link between ports ACT GREEN Data is active b...

Page 13: ...remain off during reset This is normal behavior LED s The table below describes the operating modes LED Color Description GREEN Power is Applied OFF Power is OFF LNK GREEN Link between ports establis...

Page 14: ...the Voltage Input Plug s back into the side header All 10 100BaseT LED s will flash ON Momentarily For fiber optic ports only port 1 will flash momentarily 5 Verify the Power LED stays ON GREEN Note O...

Page 15: ...can run a drain wire lug from any of the Din Rail screws or empty PEM nuts on the enclosure When using an unused PEM nut to connect a ground lug via a machine screw care should be taken to limit the...

Page 16: ...Rev050908 16 RJ45 CONNECTOR CRIMP SPECIFICATIONS Please reference the illustration below for your Cat5 cable specifications...

Page 17: ...a port to port connection on the same switch i e loop is an illegal operation and will create a broadcast storm which will crash the network TROUBLESHOOTING 1 Make sure the Power LED is ON 2 Make sur...

Page 18: ...rage Temperature 20o C to 85o C 0 F to 185o F Operating Humidity 10 to 90 Non Condensing Operating Altitude 0 to 10 000 ft Shock and Vibration Bulkhead Mounting Shock 200g 10ms Vibration 1g 10 500Hz 3...

Page 19: ...dous Locations Class I Zone 2 Group IIC T4A EMI EN50081 1 1992 EN55022 Class A FCC Part 15 Class A EMS EN55024 1998 EN61000 4 2 1995 EN61000 4 3 1995 EN61000 4 4 1995 EN61000 4 5 1995 EN61000 4 6 1995...

Page 20: ...ode fiber 904FXE XX YY Four ports 100BaseFX singlemode fiber Where XX is ST for ST style fiber connector SC for SC style fiber connector Where YY is 15 for 15km max fiber segment length 40 for 40km ma...

Page 21: ...ES EXCLUSIVE IF AN N TRON PRODUCT DOES NOT OPERATE AS WARRANTED ABOVE CUSTOMER S SOLE REMEDY FOR BREACH OF THAT WARRANTY SHALL BE REPAIR REPLACEMENT OR REFUND OF THE PURCHASE PRICE PAID AT N TRON S OP...

Reviews: