N-TRON SWITCH GROUNDING TECHNIQUES 

 

The grounding philosophy of any control system is an integral part of the design.  N-Tron switches are designed 
to  be  grounded,  but  the  user  has  been  given  the  flexibility  to  float  the  switch  when  required.    The  best  noise 
immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to earth ground via 
a drain  wire.  Some N-Tron switches  have  metal  din-rail brackets  that can ground the switch if the din-rail is 
grounded.  In some cases, N-Tron switches with metal brackets can be supplied with optional plastic brackets if 
isolation is required. 
 

Both  V-  legs  of  the  power  input  connector  are  connected  to 
chassis  internally  on  the  PCB.   Connecting  a  drain  wire  to 
earth ground from one of the V- terminal plugs as shown here 
will ground the switch and the chassis.  The power leads from 
the  power  source  should  be  limited  to  3  meters  or  less  in 
length. 
 

As an alternate, users can run a drain wire & lug from any of the Din-Rail 
screws or empty PEM nuts on the enclosure.   When using an unused PEM 
nut  to  connect  a  ground  lug  via  a  machine  screw,  care  should  be  taken  to 
limit the penetration of the outer skin by less than 1/4 in.  Failure to do so 
may cause irreversible damage to the internal components of the switch.  
 
Note:  Before  applying  power  to  the  grounded  switch,  you  must  use  a  volt 
meter  to  verify  there  is  no  voltage  difference  between  the  power  supply’s 
negative output terminal and the switch chassis grounding point.  
 
If the use of shielded cables is required, it is generally recommended to only connect the shield at one end to 
prevent  ground  loops  and  interfere  with  low  level  signals  (i.e.  thermocouples,  RTD,  etc.).    Cat5e  cables 
manufactured to EIA-568A or 568B specifications are required for use with N-Tron Switches.  

 

 

 
In  the  event  all  Cat5e  patch  cable  distances  are  small  (i.e.  All  Ethernet  devices  are  located  the  same  local 
cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to 
chassis ground at both ends in systems void of low level analog signals. 

Summary of Contents for 302MC-SC

Page 1: ...300 Series Media Converter Industrial Ethernet Switches Installation Guide...

Page 2: ...Revised 2011 11 29 2 Industrial Ethernet Switch Installation Guide 302MC XX 302MCE XX YY 304TX 305FX XX 305FXE XX YY 306TX 306FX2 XX 306FXE2 XX YY 308TX Where XX ST or SC and YY 15 40 or 80...

Page 3: ...limited to the implied warranties of merchantability or fitness for a particular purpose In no event shall N TRON Corp be liable for any incidental special indirect or consequential damages whatsoeve...

Page 4: ...See the grounding technique section of this user manual for proper ways to ground the unit WARNING Do not work on equipment or cables during periods of lightning activity WARNING Do not perform any s...

Page 5: ...lations require that power connections must be current limited at the power source with an in line fuse rated at 0 5A 4 Class I Div 2 installations require that all devices connected to this product m...

Page 6: ...he use of repeaters The 305FXE and 306FXE2 switches are unmanaged and similar to the 305FX and 306FX2 respectively However these models use singlemode transceivers with extended range capability The N...

Page 7: ...NING FXE units contain a class 1 laser Do not stare into the laser beam fiber optic connector when installing or operating the product Never install or work on electrical equipment or cabling during p...

Page 8: ...rd force on the clip until it disengages from the bottom of the unit from the DIN Rail Rotate the bottom of the unit towards you and up at an approximate 15 upward angle to completely remove the unit...

Page 9: ...ections Green LED lights when Power is connected NOTE Each RJ45 data port has two LED s for each connector The lower LED indicates LINK status and the upper LED indicates ACTIVITY LED s The table belo...

Page 10: ...is 0 22 Nm 0 162 Pound Foot All LED s will flash ON Momentarily Verify the Power LED stays ON GREEN Note Either V1 or V2 can be connected to power for minimal operation For redundant power operation...

Page 11: ...users can run a drain wire lug from any of the Din Rail screws or empty PEM nuts on the enclosure When using an unused PEM nut to connect a ground lug via a machine screw care should be taken to limit...

Page 12: ...Revised 2011 11 29 12 RJ45 CONNECTOR CRIMP SPECIFICATIONS Please reference the illustration below for your Cat5 cable specifications...

Page 13: ...rts are working correctly by installing the N View OPC Server software The software is freely distributed on the ProductCD and our website http www n tron com pdf setup_nviewopc zip Once the software...

Page 14: ...re 40 C to 70 C Storage Temperature 40 C to 85 C Operating Humidity 10 to 90 Non Condensing Operating Altitude 0 to 10 000 ft Network Media 10BaseT Cat 3 Cable 100BaseT Cat 5 Cable 100BaseFX Multimode...

Page 15: ...A EMS EN61000 6 2 EN61000 4 2 ESD EN61000 4 3 RS EN61000 4 4 EFT EN61000 4 5 Surge EN61000 4 6 Conducted Disturbances Conducted Low Frequency IEC60533 Shock IEEE 1613 250 mm Vibration IEEE 1613 V S 4...

Page 16: ...RANTIES EXCLUSIVE IF AN N TRON PRODUCT DOES NOT OPERATE AS WARRANTED ABOVE CUSTOMER S SOLE REMEDY FOR BREACH OF THAT WARRANTY SHALL BE REPAIR REPLACEMENT OR REFUND OF THE PURCHASE PRICE PAID AT N TRON...

Reviews: