N-Tron 100-POE-SPL User Manual & Installation Manual Download Page 10

(Revised 2010-11-15) 

10 

N-TRON SWITCH GROUNDING TECHNIQUES FOR THE 100-POE-SPL-XX 

 
 

The grounding philosophy of any control system is an integral part of the design.  N-Tron switches are designed 
to  be  grounded,  but  the  user  has  been  given  the  flexibility  to  float  the  switch  when  required.    The  best  noise 
immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to earth ground via 
a drain  wire.  Some N-Tron switches  have metal  din-rail brackets  that can ground the switch if the din-rail is 
grounded.  In some cases, N-Tron switches with metal brackets can be supplied with optional plastic brackets if 
isolation is required. 

Users may run a drain wire & lug from the screw provided on the back face of the 
enclosure.   In the event the provided grounding screw has been lost, care should 
be taken to limit the penetration of the outer skin by less than 1/4".  Failure to do 
so may cause irreversible damage to the internal components of the switch.  
 

Note:

 

Ensure the power supply is grounded properly before applying power to the 

grounded switch.  This may be verified by using a voltmeter to determine that there 
is no voltage difference between the power supply’s negative output terminal and 
the chassis grounding point of the switch.   

 

 
 
As  an  alternative  grounding  method,  both  V-  legs  of  the  power  input 
connector are connected to chassis internally on the PCB.  Connecting 
a  drain  wire  to  earth  ground  from  one  of  the  V-  terminal  plugs  as 
shown here  will ground  the switch and the  chassis.   The power leads 
from the power source should be limited to 3 meters or less in length. 

 

 
 

Note:

 

Before  applying  power  to  the  grounded  switch,  you  must  use  a  volt  meter  to  verify  there  is  no  voltage 

difference between the power supply’s negative output terminal and the switch chassis grounding point.  

 

If the use of shielded cables is required, it is generally recommended to only connect the shield at one end to 
prevent  ground  loops  and  interfere  with  low  level  signals  (i.e.  thermocouples,  RTD,  etc.).    Cat5e  cables 
manufactured to EIA-568A or 568B specifications are required for use with N-Tron Switches.  
 

 

 
In  the  event  all  Cat5e  patch  cable  distances  are  small  (i.e.  All  Ethernet  devices  are  located  the  same  local 
cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to 
chassis ground at both ends in systems void of low level analog signals. 
 
 

DRAIN WIRE WITH LUG CONNECTING SWITCH 
CHASSIS TO KNOWN GOOD GROUNDING POINT. 

DRAIN WIRE WITH 
LUG CONNECTING 
SWITCH CHASSIS 
TO KNOWN GOOD 
GROUNDING 
POINT. 

METALLIC 
DIN-RAIL CLIP 

Summary of Contents for 100-POE-SPL

Page 1: ...Revised 2010 11 15 1 100 POE SPL Industrial Power Extractor User Manual Installation Guide...

Page 2: ...tractor Installation Guide 100 POE SPL XX Unmanaged Industrial PoE Power Extractor Where XX is 12 for 12VDC output voltage option 24 for 24VDC output voltage option 48 for 48VDC output voltage option...

Page 3: ...ion contained in this document is subject to change without notice N TRON Corp makes no warranty of any kind with regard to this material including but not limited to the implied warranties of merchan...

Page 4: ...TRON Corp the protection provided by the equipment may be impaired WARNING Do not perform any services on the unit unless qualified to do so Do not substitute unauthorized parts or make unauthorized m...

Page 5: ...Cat5e cable connected to a PoE sourcing device The 100 POE SPL allows legacy devices which are not PoE capable to be deployed without the need to provide a dedicated power supply The 100 POE SPL can b...

Page 6: ...emove all the equipment from the packaging and store the packaging in a safe place File any damage claims with the carrier CLEANING Clean only with a damp cloth INSTALLATION Read the following warning...

Page 7: ...unit from the 35mm industrial DIN rail pull forward on the unit until it disengages from the bottom of the DIN rail Rotate the bottom of the unit towards you and up at an approximate 15 upward angle...

Page 8: ...48VDC connector Model dependent Green LED lights when Power is present POE IN RJ45 connector for data and PoE in DATA OUT RJ45 connector for data only out LEDs The table below describes the operating...

Page 9: ...ource device into the POE IN port Verify the Power LED stays ON GREEN Note Either V1 or V2 can be connected to power for minimal operation For redundant power operation V1 and V2 plugs must be connect...

Page 10: ...gative output terminal and the chassis grounding point of the switch As an alternative grounding method both V legs of the power input connector are connected to chassis internally on the PCB Connecti...

Page 11: ...voltage to 12 24 48VDC for the legacy end device Warning The 100 POE SPL XX is not a switch and will not actively boost the Ethernet signals So the total max segment length is a combined 100meters Mea...

Page 12: ...cause harmful interference in which case the user will be required to correct the interference at his own expense INDUSTRY CANADA This Class A digital apparatus meets all requirements of the Canadian...

Page 13: ...DC Max Full Load Output Wire Size 16 28 AWG Max Capacitive Load 400uF Assuming 50ohm DC Load Max Inrush 700mA 50ms 24VDC Environmental Operating Temperature 40 C to 85 C Storage Temperature 40 C to 85...

Page 14: ...2 Groups A B C D hazardous or non hazardous locations temperature code of T4 EMI EN61000 6 4 EN55022 Class A FCC Title 47 Part 15 Subpart B Class A ICES 003 Class A EMS EN61000 6 2 EN61000 4 2 ESD EN6...

Page 15: ...RANTIES EXCLUSIVE IF AN N TRON PRODUCT DOES NOT OPERATE AS WARRANTED ABOVE CUSTOMER S SOLE REMEDY FOR BREACH OF THAT WARRANTY SHALL BE REPAIR REPLACEMENT OR REFUND OF THE PURCHASE PRICE PAID AT N TRON...

Reviews: