9) Cton (Maximum cooler on hours when defrost)
- Setting range : 0
–
9999 min.
* Examples for use
It is time of cooler working for defrost. It indicate with minute and if you set up Cton=600 &
Ctof=15, cooler working 600min and start again after rest on 15min. If you want to display fixing
present temperature at screen during defrost hours, please set as below 12) dTon. This time just
start after cooler off. Please see using examples on the back of manual for more details.
10) CtoF (Defrost time with Defrost ability (COOLER OFF))
- Setting range : 0
–
9999 min.
It is cooler off time but you set up '0', the defrost ability is gone. (Because of Time off)
11) CdLy (Cooler delay time : Delay time of power outage or beginning power on)
- Setting range : 0
–
9999 min.
It just can use when cooler working delay time with (mode N3=1)
12) dTon ( Fixing temperature time for defrost ability on the screen)
- Setting range : 0
–
9999 min.
Fixing time for do not change temperature on the screen when defrost.
The timer start working defrost upon cooler off.
13) drAn (Fixing temperature range)
- Setting range : 0.0
–
99.9 degree (Celsius)
This ability fix the temperature within regular range when temperature has change.
* Examples for use
The temperature work get out of from 0.1'c when control the temperature with cooler only. If
you want to set up the temperature to +/- 0.6'c range, Please fix to 0.6'c. In other word, if you
set up 4.0'c, the screen just display 4.0'c for 3.4'c ~4.6'c. It's possible for no use decimal point.
3.4'c - 4.6'c --> 4.0
’c
14) Aoff ( 'END' display point - type 'B' & 'C' selected)
- Setting range : pt : -99.9 _ 299.9 degree
## ca : -99.9 _ 999.9 degree
## ca : -99.9 _ 1359 degree