![mySmart MWS7 Product Manual Download Page 5](http://html1.mh-extra.com/html/mysmart/mws7/mws7_product-manual_1863204005.webp)
page 5
All the following functions can be programmed using the remote control DD-LCDHS-LR handset:
1.
Detector Parameters (factory default in brackets):
1.1
Time adjustment
(20 min)
10 seconds to 99 minutes time delay (select 0 for 10 second
delay
–
use for commissioning only).
1.2
Sensitivity On
(9)
Sensitivity level when the detector is already operational
adjustable between 1 (min.) and 9 (max.)
1.3
Sensitivity Off
(9)
Sensitivity level for switching the detector on
–
adjustable
between 1 (min.) and 9 (max.).
1.4
Range (m)
(25)
Sensor range (in metres). Can be set from 0-999, but only
the values 5-30 are effective. Other values are used for
sensor testing and debugging.
1.5
Power Up On
(Y)
Select No for a 10 second delay on start up. If Yes is selected,
there will be no delay on start up and the detector will always
power up detecting.
1.6
Walk Test
(N)
LEDs behind the detector lens will illuminate to show
movement has been detected (use for commissioning).
1.7
Disable Detector
(N)
Disables detection, leaving the relay output permanently off
with the dimming output operational. This mode is used when
the unit is for maintained illuminance only.
1.8
Factory Default
Restores factory default settings.
2.
Modes (factory default in brackets):
2.1 Channel Modes
2.1.1 Switch only
Usually used for absence detection - in this mode the dimming
channel is not used.
2.1.2
Switch and dim together
(default)
The detector will switch and dim the lighting together.
2.1.3
Switch and dim separate
Relay and dimming channels are controlled separately.
2.2 Switch Modes
2.2.1
2 position switch together
(default) A single centre-biased retractive switch will be used to
control both channels together.
2.2.2
2 position switch separate
A single centre-biased retractive switch will be used to
control only the dimming channel.
2.2.3
1 position switch together
A single-position retractive switch controls both channels
together.
2.2.4
1 position switch separate
Two single-position retractive switches, controlling the
channels separately.
3.
Switching Channel 1 functions (factory default in brackets):
3.1
Presence detection
Auto switch on with detection, auto off after movement ceases
(default)
and time delay ends.
3.2
Absence detection
Manual switch on, auto off after movement ceases and time
delay ends.
3.3
Switch level on
(9)
Lux level setting to prevent the luminaires being switched on if
the ambient light level is sufficient (adjustable between 1
and 9). The luminaires will always be switched on at level 9.
3.4
Switch level off
(9)
Lux level setting to switch the luminaires off during occupancy
if the ambient light level goes above the setting (adjustable
between 1 and 9). Level 9 will always keep the lights on.
5. Programming