AC•THOR®i Assembly Instructions, Version 210326
11
Do not immerse my-PV temperature sensor(s) directly in Water. Use a
thermowell!
7.
Electrical connection
The AC•THOR®i is controlled by external signal sources by way of IP protocol
using a standard Ethernet RJ45 cable.
Protection of the mains connection for the AC•THOR®i may not exceed 16 A
per phase (tripping characteristic B or C).
Pay attention to other loads on the line circuit, this may trip the circuit
breaker!
For mains leads, use a cable duct of 60 mm depth. The cut-out
measures 130 x 60 mm.
The PE conductor and the neutral conductor must be connected!
!