115159H - LV I/O OPTION
Using the arrow keys, choose the desired function, and press enter.
Using the arrow keys, choose the appropriate Active state, and press enter.
Using the arrow keys, choose the appropriate label, and press enter.
Press escape to leave the
I/O Settings
menu and the changes will be updated.
To set an output function:
Ensure that the Series LV unit is fully powered and contains an I/O Board option.
Hold down the power button on the display to power it on.
Using the arrow keys, navigate to
System Setup
in the display menu.
Using the arrow keys, navigate to
I/O Settings
in the System Setup menu.
Using the arrow keys, choose the appropriate output, and press the enter button.
Using the arrow keys, choose the desired function, and press enter.
Using the arrow keys, set the required range if needed, and press enter.
Press escape to leave the
I/O Settings
menu and the changes will be updated.
To view the status of inputs and outputs:
Ensure that the Series LV unit is fully powered and contains an I/O Board option.
Hold down the power button on the display to power it on.
Using the arrow keys, navigate to
Contact Status
in the display menu.
Using the arrow keys, navigate to through the I/O in the Contact Status menu.
The menu displays the state of the contacts as well as the function they are set too.
Default settings:
The following table outlines the default settings for different versions of the
LV series I/O Option board.
Table 2.1: Default settings
•
Default settings are factory programmed.
•
Basic LV System I/O boards are not adjustable.
6 Output Option
3 Output / 3 Input Option
I/O
Default Setting
I/O
Default Setting
OUT1
Advanced: VAC In (Function)
(Utility VAC N14% / -15%)
IN1
Isolated Power Input
Basic: AC Present (Status)
(AC Utility above 60VAC)
OUT2
Input Fuse Failed (Alarm)
IN2
Isolated Power Input
OUT3
On Battery (Status)
(Inverter On)
IN3
Isolated Power Input
OUT4
Overload (Alarm)
(AC Output Turns Off if On Battery)
OUT1
Active when IN1 Power Present or
when On Battery
OUT5
Battery Voltage (Function)
(Near Low Battery = 1.85V / Cell)
OUT2
Active when IN2 Power Present or
when On Battery
OUT6
Test Failed (Alarm)
OUT3
Active when IN3 Power Present or
when On Battery