17
115159H - LV I/O OPTION
SECTION 8
Zone Monitor
Figure 8 illustrates a zone monitor application where a separate zone and/or fire
alarm panel can force the Emergency Lighting Inverter into an emergency state
even if its AC power is within acceptable limits. The AC input that is feeding the
room lighting is connected directly to the Isolated I/O Board Input Sense or in the
case of a fire alarm panel connected through a normally closed dry contact from
the fire alarm panel as shown.
Note: The fire alarm contact must be rated for the input voltage and be able
to switch 100 mA. The voltage range for the I/O Board Input Sense is
100-300 VAC or VDC.
The lighting load is connected to the optional output circuit breaker, if supplied, or
the common terminal of the I/O Board Output Relay.
FIGURE 8