CAUTION: NEVER 

connect a laser printer or scanner to the UPS unit. This may cause the 

damage of the unit.   

4. Installation and Initial Startup 

NOTE: 

Before installation, please inspect the unit. Be sure that nothing inside 

the package is damaged.   
 

Placement & Storage Conditions 

Install the UPS in a protected area that is free of excessive dust and has adequate air flow. 
Please place the UPS away from other units at least 20 cm to avoid interference. Do NOT 
operate the UPS where the temperature and humidity is outside the specific limits. 
(Please check the specs for the limitations.) 

                       

 

 

Connect to Utility and Charging 

Before initial use, please plug in the AC input cord to the wall 
outlet and turn on the UPS for charging. For the best results, 
suggest to charge the battery at least 8 hours before initial use.   
 

Connect the Loads 

Plug in the loads to output receptacles on the rear panel of the 
UPS. Simply turn on the power switch of UPS unit, then devices 
connected to the UPS will be protected by UPS unit. 

Turn On/Off the Unit 

Turn on the UPS unit by pressing the power switch.    Turn off the UPS unit by pressing 
again the power switch.     
 

Indicators & Alarm Table for Operation   

Conditions Visual 

Indicator 

Alarm 

AC Mode 

Green LED lighting 

Off 

Battery Mode 

Green LED flashing every 10 

seconds 

Sounding every 10 

seconds 

Low battery at battery 
mode 

Green LED flashing every second 

and Red LED lighting 

Sounding every second 

Fault 

Red LED lighting 

Continuously sounding 

Alarm for 
over-temperature 
protection 

Red LED flashing every 0.5 

seconds 

Off 

 

5. Important Safety Warning (SAVE THESE INSTRUCTIONS) 

CAUTION! 

To prevent the risk of fire or electric shock, install in a temperature and 

humidity controlled indoor area free of conductive contaminants. (See the specifications for 
the acceptable temperature and humidity range.) 

CAUTION! 

To reduce the risk of overheating the UPS, do not cover the UPS' cooling vents 

and avoid exposing the unit to direct sunlight or installing the unit near heat emitting 
appliances such as space heaters or furnaces. 

CAUTION! 

Do not attach non-computer-related items, such as medical equipment, 

life-support equipment, microwave ovens, or vacuum cleaners to UPS. 

CAUTION! 

Do not plug the UPS input into its own output. 

CAUTION!

 Do not allow liquids or any foreign object to enter the UPS. Do not place 

beverages or any other liquid-containing vessels on or near the unit.   

CAUTION!

 In the event of an emergency, press the OFF button and disconnect the power 

cord from the AC power supply to properly disable the UPS. 

CAUTION! 

Do not attach a power strip or surge suppressor to the UPS. 

CAUTION! 

If the UPS is with metal chassis, for safety purpose, grounding is a must during 

UPS installation in order to reduce leakage current below 3.5A. 

Attention

 hazardous through electric shock. Also with disconnection of this unit from the 

mains, hazardous voltage still may be accessible through supply from battery. The battery 
supply should be therefore disconnected in the plus and minus pole at the quick connectors 
of the battery when maintenance or service work inside the UPS is necessary. 

CAUTION! 

Servicing of batteries should be performed or supervised by personnel 

knowledgeable of batteries and the required precautions.    Keep unauthorized personnel 
away from batteries.   

CAUTION! 

When replacing the batteries, use the same number and type of batteries. 

CAUTION! 

Internal battery voltage is 12VDC. Sealed, lead-acid, 6-cell battery. 

CAUTION! 

Do not dispose of batteries in a fire. The battery may explode. Do not open or 

mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. 

CAUTION!

 Unplug the UPS prior to cleaning and do not use liquid or spray detergent. 

CAUTION! 

A battery can present a risk of electric shock and high short circuit current. The 

following precaution should be observed before replacing batteries: 
1) 

Remove watches, rings, or other metal objects. 

2) 

Use tools with insulated handles. 

3) 

Wear rubber gloves and boots. 

4) 

Do not lay tools or metal parts on top of batteries. 

5) 

Disconnect charging source prior to connecting or disconnecting batteries terminal. 

EN 

EN 

Summary of Contents for POWERMUST 424 OFFLINE

Page 1: ...n a small and economic package The UPS is more compact and offers greater comprehensive power protection against surges and spikes This UPS will continue providing stable power to connected equipment...

Page 2: ...installing the unit near heat emitting appliances such as space heaters or furnaces CAUTION Do not attach non computer related items such as medical equipment life support equipment microwave ovens o...

Page 3: ...VA 360 W 800 VA 480 W INPUT Voltage 220 230 240 VAC Voltage Range 180 270 VAC Frequency 50 Hz OUTPUT Voltage Regulation 10 Transfer Time Typical 2 6 ms Waveform Simulated Sine Wave BATTERY Type Number...

Page 4: ...eit an die nichts mit Computern zu tun haben wie z B medizinische Ger te lebenserhaltende Ausr stungen Mikrowellenger te oder Staubsauger ACHTUNG Schlie en Sie das Netzkabel der USV niemals an ihren e...

Page 5: ...blinkt Netzkabel ist locker Verbinden Sie das Netzkabel richtig 7 Spezifikationen Modell PowerMust 424 Offline PowerMust 636 Offline PowerMust 848 Offline LEISTUNG 400 VA 240 W 600 VA 360 W 800 VA 48...

Page 6: ...n HUOMAA l kytke UPS laitteeseen tietokoneisiin kuulumattomia laitteita kuten l ketieteellisi laitteita elintoimintoja yll pit vi laitteita mikroaaltouuneja tai p lynimureita HUOMAA l kytke UPS laitte...

Page 7: ...V A 360 W 800 V A 480 W TULO J nnite 220 230 240 V AC J nnitealue 180 270 V AC Taajuus 50 Hz L HD T J nnitteen s tely 10 Siirtoaika Tyypillinen 2 6 m s Aalltomuoto Simuloitu siniaalto AKKU Tyyppi ja...

Page 8: ...vitez de l exposer la lumi re directe du soleil Ne l installez pas non plus proximit d un appareil mettant de la chaleur tel que chauffage ou four ATTENTION Ne reliez pas l appareil des quipements no...

Page 9: ...ation 7 Caract ristiques techniques Mod le PowerMust 424 Offline PowerMust 636 Offline PowerMust 848 Offline CAPACIT 400 VA 240 W 600 VA 360 W 800 VA 480 W ENTR E Tension 220 230 240 V c a Plage de te...

Page 10: ...ecte exclusivamente dispositivos inform ticos No lo utilice nunca para mantener funcionando material m dico equipos para el soporte vital hornos microondas ni aspiradoras ATENCI N No conecte la entrad...

Page 11: ...bien conectado Vuelva a conectarlo firmemente 7 Caracter sticas t cnicas Modelo PowerMust 424 Offline PowerMust 636 Offline PowerMust 848 Offline POTENCIA 400 VA 240 W 600 VA 360 W 800 VA 480 W ENTRA...

Page 12: ...prekrivajte otvore za prozra ivanje ne izla ite ure aj izravnoj sun evoj svjetlosti i ne postavljajte ure aj u blizinu izvora topline poput grijalica i pe i OPREZ Ne priklju ujte druge ure aje na UPS...

Page 13: ...KAPACITET 400 VA 240 W 600 VA 360 W 800 VA 480 W ULAZ Napon 220 230 240 V Raspon napona 180 270 V Frekvencija 50 Hz IZLAZ Regulacija napona 10 Vrijeme prijenosa Naj e e 2 6 ms Valni oblik Simulirana s...

Page 14: ...it vicino a fonti di calore quali termosifoni o forni AVVERTENZA Non collegare al gruppo di continuit dispositivi di tipo non informatico quali apparecchi medici macchine di supporto alla vita forni a...

Page 15: ...line PowerMust 848 Offline POTENZA 400 VA 240 W 600 VA 360 W 800 VA 480 W INGRESSO Tensione 220 230 240 VAC Range di tensione 180 270 VAC Frequenza 50 Hz USCITA Regolazione di tensione 10 Tempo di tra...

Page 16: ...ch ani nara a urz dzenia na bezpo rednie dzia anie wiat a s onecznego Ponadto zasilacza nie nale y instalowa w pobli u urz dze emituj cych ciep o takich jak grzejniki lub piece grzewcze UWAGA Nie pod...

Page 17: ...ania Pod czy poprawnie przew d zasilania 7 Dane techniczne Model PowerMust 424 Offline PowerMust 636 Offline PowerMust 848 Offline MOC 400 VA 240 W 600 VA 360 W 800 VA 480 W WEJ CIE Napi cie 220 230 2...

Page 18: ...quipamento m dico ou de apoio vida fornos microondas ou aspiradores ATEN O N o ligue a entrada da UPS sua pr pria sa da ATEN O N o permita que l quidos ou objectos estranhos entrem na UPS N o coloque...

Page 19: ...ust 848 Offline CAPACIDADE 400 VA 240 W 600 VA 360 W 800 VA 480 W ENTRADA Tens o 220 230 240 VAC Intervalo de Tens es 180 270 VAC Frequ ncia 50 Hz SA DA Regula o de Tens o 10 Tempo de Transfer ncia Ti...

Page 20: ...medical echipament de supravie uire cuptoare cu microunde sau aspiratoare ATEN IE Nu conecta i cablul de intrare al sursei n ie irea acesteia ATEN IE Nu permite i p trunderea de lichide sau alte obie...

Page 21: ...este n suprasarcin Elimina i echipamentele care nu sunt esen iale Tensiunea acumulatorului este prea mic nc rca i sursa cel pu in 8 ore La pan de curent timpul de alimentare a consumatorilor este mai...

Page 22: ...4 20 UPS 8 10 10 0 5 5 c OFF 3 5 12 6 1 2 3 4 5 8 RU RU...

Page 23: ...kompaktni ure aj koji pru a bolju za titu od prenapona i udara Ovaj UPS pru a stabilno napajanje povezanim ure ajima i omogu ava bezbedno isklju ivanje ra unara prilikom nestanka struje Ugra eni mikr...

Page 24: ...vljati blizu toplotnih izvora poput grejalica i pe i POZOR Nemojte spajati druge ure aje osim ra unarske opreme poput medicinske opreme opreme za odr avanje ivota mikrotalasnih pe nica i usisava a na...

Page 25: ...owerMust 424 Offline PowerMust 636 Offline PowerMust 848 Offline KAPACITET 400 VA 240 W 600 VA 360 W 800 VA 480 W ULAZ Napon 220 230 240 V AC Opseg napona 180 270 VAC Frekvencija 50 Hz IZLAZ Regulacij...

Page 26: ...NG Koppla inte in icke datorrelaterade enheter som exempelvis medicinsk utrustning livsuppeh llande utrustning mikrov gsugnar eller dammsugare till UPS en VARNING Plugga inte in UPS ing ngen i dess eg...

Page 27: ...ndiga Batterisp nningen r f r l g Ladda UPS en i minst tta timmar Backuptiden r f rkortad vid str mavbrott Batteri defekt Kan bero p att driftsmilj n har f r h g temperatur eller att batteriet anv nd...

Page 28: ...In Wohnansiedlungen kann dieses Erzeugnis Funkst rungen hervorrufen dann muss der Benutzer zus tzliche Ma nahmen ergreifen WARNING This is a UPS Class C2 In residential subdivision the product may ca...

Reviews: