Operation
User manual 59507_hdb_en_12
35 / 51
0x0011
VendorText
R
64
www.murrelektronik.com.
0x0012
ProductName
R
64
MVP8-P3 DIO8 8xM8-3 IO-
LA12 B0
MVP8-P3 DIO8 8xM8-3 IO-
LA12 E0
0x0013
ProductID
R
64
59507
59607
0x0014
ProductText
R
64
Digital I/O hub
MVP8-P30 - IO-Link Class A
DIO8 8xM8-3P
Basic Firmware Edition:
2 bytes IN / 1 byte Out
Digital I/O hub
MVP8-P30 - IO-Link Class A
DIO8 8xM8-3P
Extended Firmware Edition:
4 bytes IN / 1 byte Out
0x0015
SerialNumber
R
16
Running serial number
set during production
0x0016
HardwareRevision
R
64
e.g. “01.00”
0x0017
FirmwareRevision
R
64
e.g. “V.1.00.00”
0x0018
ApplicationSpe-
cificTag
R
16 ... 32
User-specific designation
e.g. “System 3 / Port 4”
0x0019
FunctionTag
R
32
0x001A
LocationTag
R
32
Diagnosis
0x0020
Error Count
R
2
0x0024
DeviceStatus
R
1
0: Device is operating properly
1: Maintenance Required
2: Out of Specification
3: Functional Check
4: Failure
5 ... 255: Reserved
0x0025
DetailedDeviceSta-
tus
R
variable
6 x (octet 1: EventQualifier,
octet 2, 3: EventCode)
0x0028
ProcessDataInput
R
PD
length
0x0029
ProcessDataOutput R
PD
length
0x0031
...
0x003F
Reserved for pro-
files
ISDU
index
DPP
index
Object name
Access Length
in bytes
Meaning / default value