Operation
User manual 59719_hdb_en_12
51 / 65
7.2.2.2
Art.-No. 59818
ISDU
index
Object name
Access Length
in Byte
Meaning
Default
value
0x0040
Status: Power Supply Sta-
tus US
R
1
Returns status of US
- 0x00 = OK
- 0x01 = Undervoltage
- 0x02 = Overvoltage
-
0x0041
Status: Power Supply Value
US
R
1
Returns measured voltage of US in 0.1 V steps.
Update every 10 ms.
-
0x0042
Status: Power Supply Sta-
tus UA
R
1
Returns status of UA
- 0x00 = OK
- 0x01 = Undervoltage
- 0x02 = Overvoltage
- 0x03 = OFF / not connected
-
0x0043
Status: Power Supply Value
UA
R
1
Returns measured voltage of UA in 0.1 V steps.
Update every 10 ms.
-
0x0044
Status: Internal Tempera-
ture Value °C
R
1
Returns the internal device temperature, in 0.1 °C
steps, update every 10 ms.
- Range: -25°C … +70°C
- Value: 0x0000 (Bit 16 = sign)
-
0x0045
Status: Internal Tempera-
ture Value °F
R
1
Returns the internal device temperature from -13
°F to +158 °F in 0.1 °F steps. Update every 10 ms.
-
0x0050
Diagnosis: Short Circuit De-
tection DO
R
1
Allows reading of a short circuit that has occurred
on a specific channel.
- Subindex 1 = X0 Pin 4
- Subindex 2 = X0 Pin 2
...
- Subindex 15 = X7 Pin 4
- Subindex 16 = X7 Pin 2
-
0x0060
Identification: Identification
ID
R/W
1
Identification number for module identification.
The value is shown inside the input process data.
0x0000
0x0061
Identification: User Defined
Serial Number
R/W
16
User defined serial number. This can be used to
ensure that a device is not connected to the
wrong master.
0x0000
0x0062
Diagnosis: Disable General
Diagnosis
R/W
2
Configurable diagnosis:
0 = active
1 = disabled
- Subindex 1: IO-Link Event Code transmission to
Master
- Subindex 2: US - Diagnosis low voltage
- Subindex 3:US - Diagnosis Over voltage
- Subindex 4: US - LED status
- Subindex 5: UA - Diagnosis `not connected´
- Subindex 6: UA - Diagnosis low voltage
- Subindex 7: UA - Diagnosis over voltage
- Subindex 8: UA - LED status
- Subindex 9: TEMP - Diagnosis low temperature
- Subindex 10: TEMP - Diagnosis over tempera-
ture
- Subindex 11: TEMP - LED status
- Subindex 12 ... 16: Reserved
0
0x0064
Module: Clear L+ Current
Limit Overload
R/W
2
Overcurrent protection for US (L+) active:
0 = Automatic reset after 60 sec.
1 = Manual reset via output process dataFor a
manual reset, set the affected bit in the process
data from 0 to 1.
0
0x0070
In-/Outputs: Bitmapping
Layout
R/W
16
Bitmapping layout of the process data.
0 = Port based bit mapping
1 = Pin based bit mapping
0