background image

SPL/45-94117B page 2 of 4

8-7/16 in.

(214 mm)

3-3/8 in.

(86 mm)

7-7/8 in.

(200 mm)

3-15/16 in.

(100 mm)

4-1/32 in.

(102 mm)

9/32 in.
(7 mm) dia. 
3 places

*

 

SPLCE, SPLBPE, 45TEE and 45TEBPE

 versions feature square case, 

but altered to fit standard round panel mounting–not pictured.               

1/2 in.

(13 mm) 

conduit

120

120

120

5-7/16 in.

(138 mm)

2-57/64 in.

(73 mm)

1/4 in. (6 mm) dia. 
holes (3 places.) on 
5-13/64 in. (132 mm) 
b.c. (bolt circle),
120   apart, clocking
as shown

Mounting Hole

4-3/4 in.

(121 mm)

diameter.

Optional
1/2 NPT

conduit

connector

(std. with

-OS option).

7 in. 

(178 mm)

1/2 NPT

Compression Nut

Bulb Minimum Insertion

Ranges and Accuracy — Sensing Bulb Insertion 

Dimensions

Surface Mount Models

*

Sensing Bulb

Panel Mount Models

Temperature Ranges Available (dual scale dials)

Fahrenheit

Celsius

Accuracy (SPL and 45 Series Models)

Lower 1/4

Middle 1/2

Upper 1/4

15° to 250°F

9° to 121°C

±8°F/±4°C

±2°F/±1°C

±2°F/±1°C

5 in. (127 mm)

130° to 350°F

60° to 180°C

±8°F/±4°C

±2°F/±1°C

±3°F/±1.5°C

2-1/2 in. (64 mm)

260° to 450°F

127° to 232°C

±8°F/±4°C

±2°F/±1°C

±3°F/±1.5°C

2-1/2 in. (64 mm)

Minimum Sensing Bulb

Insertion into Process

Using a Thermowell

Start-Up Lockout 

Start Up Lockout

Toggle Switch

SPLC Series

Low Limit

Contact

TEMPERATURE

MURPHY

SWICHGAGE®
TULSA, U.S.A. 

270

250

220

200

170

350

340

320

300

290

°

C

°

F

START

RUN

Red

Toggle

switch

White Black

SPLC

The SPLC SWICHGAGE

®

low limit contact can be bypassed for equipment

start up. A toggle switch is provided for this purpose. The toggle switch must be
manually reset when temperature rises above the low limit.

Installing a thermowell is rec-
ommended for high pressure
applications or corrosive envi-
ronments. It also allows sens-
ing bulbs to be changed or
adjusted without opening the
connection to process.
Murphy offer thermowells for
a variety of applications. 

For details see  Murphy 
bulletin T-9003B.  

Sensing Bulb

Active Section

Thermowell

into the Process

Capillary

Tube

Application

Summary of Contents for Temperature SWICHGAGE SPL

Page 1: ...Wire Connections Surface mount models 1 2 NPT conduit and terminal block Panel mount models Wire leads 18 AWG 1 0 mm2 x 9 in 229 mm long OS models 1 2 NPT conduit and wire leads 18 AWG 1 0 mm2 x 9 in 229 mm long Item Weight 8 lb 3 6 kg approximately Explosion proof models 22 lb 10 kg approx Item Dimensions 16 x 11 x 5 1 2 in 406 x 279 x 140 mm Explosion proof models 12 x 12 x 9 in 305 x 305 x 229 ...

Page 2: ...o 121 C 8 F 4 C 2 F 1 C 2 F 1 C 5 in 127 mm 130 to 350 F 60 to 180 C 8 F 4 C 2 F 1 C 3 F 1 5 C 2 1 2 in 64 mm 260 to 450 F 127 to 232 C 8 F 4 C 2 F 1 C 3 F 1 5 C 2 1 2 in 64 mm Minimum Sensing Bulb Insertion into Process Using a Thermowell Start Up Lockout Start Up Lockout Toggle Switch SPLC Series Low Limit Contact TEMPERATURE MURPHY SWICHGAGE TULSA U S A 270 250 220 200 170 350 340 320 300 290 C...

Page 3: ...E model The 45TE series SWICHGAGE incorporates 2 SPDT snap switches instead of the pointer type contacts of the SPL Unlike the SPL that completes an elec trical circuit as soon as the pointer touches the contact the 45TE trip point indi cators will stop the pointer movement slightly before the switches operate As temperature continues to increase reaching high set point or to decrease reaching low...

Page 4: ... NOTE No designator is required for Standard configurations Also list options in alphabetical order A to Z Place a dash between each option See example below SPLBP 4 350 G 10 EX How to Order Latching Control Relay Voltage applies to BP models only Blank 120 VAC 2 12 VDC 4 24 VDC This version not covered by CE mark Warranty A limited warranty on materials and workmanship is given with this FW Murph...