background image

ST-94112N page 3 of 4

ELECTRICAL

A

B

Battery

Run

Remove jumper from 
terminals 12 and 13 and 
set individual sensor Lockout 
Switch for a 25 to 35 second 
lockout time delay during
startup (see page 4

Setting Lockout Switches

). 

Sensor Lockout Switches

5

9

13

10 11 12

14

A

B

6

A

B

7

A

B

A

B

A

B

A

B

A

B

8

1

2

3

4

No Connection

No Connection

No Connection

ON/OFF
Switch

Internal Relay
(shown in
 run mode)

Jumper Wire
(customer supplied)

Engine Oil
Pressure

ST8

Shutdown 
Sensor Inputs

ST8

Shutdown 
Sensor Inputs

Push/Pull Solenoid

Solenoid Valve

Slave Relay

Start

Pushbutton

Coil

Distributor

Starter 
Motor

To B

2 Amp
Fuse

Flyback 

Diode

Flyback 

Diode

Flyback 

Diode

Flyback Diode

To Hold Coil

NOTE:

 Connect only one shutdown

device to the ST8. Wiring
for Push/Pull Solenoid, Solenoid Valve
and Slave Relay shown for clarity only. 

To Pull-in Coil

Engine Water
Temperature

Low 
Water 
Level

Differential
Pressure

No Connection

ON

1 2 3 4 5 6 7 8

The Figures below show typical customer switch wiring for the ST8.
Switch wiring should be run separately from other wires; 

DO NOT

route switch wires with AC power wires since voltages, that may
be induced into the switch wires, may exceed rating and cause
damage to circuits or cause false trips.
Figure 1

shows the wiring for a normally open (N.O.) SWICH-

GAGE

®

connected between terminal B and the negative power input.

A metal jumper is connected between A and B. When the SWICH-
GAGE

®

closes  the shutdown/alarm circuit will be initiated.

Figure 2

shows the wiring for a normally closed (N.C.) switch

connected to input terminals A and B. The factory installed

metal link must be removed to use this wiring. When the switch
opens the shutdown/alarm will be initiated.

Figure 3

shows the wiring for a N.O. SWICHGAGE

®

which is the

same as Figure 1 except two wires are run from terminals A and B to
the SWICHGAGE

®

. This Closed Loop™ wiring circuit monitors the

wires as well as the switch. If the circuit is opened due to a loose
connection or broken wire or the SWICHGAGE

®

closes, the shut-

down/alarm circuit will be initiated.

Figure 4

shows the ST8 internal SPDT relay in the “run” or operat-

ing mode.

Typical Wiring 

Below is a typical wiring diagram for the ST8 TATTLETALE

®

A

B

A

B

A

B

9

N.O.

N.C.

C

10

11

Figure 1: 

Typical N.O. 

Sensor Connection

Figure 2: 

Typical N.C. 

Sensor Connection

Figure 3: 

Typical N.O. 

Closed Loop™ Sensor Connection

Figure 4: 

Internal Relay

Circuit

Reviews: