Power and Control Cable

The S1400 module is connected to the power supply via the 9-conductor
shielded cable. The cable is factory-sealed on the power supply end, and
has a D-sub miniature connector on the monitor end. Outputs from the
module are transmitted to control relay drivers in the power supply via
four conductors of the 9–conductor shielded cable.

System Power Backup Battery

The backup power is provided by a 12 VDC, 600 MAh rechargeable Ni-
cad battery pack. A temperature compensated, constant current battery
charger maintains full charge on the battery pack when primary power is
on. If the battery is fully discharged when primary power is turned on, it
will take approximately 24 hours to bring batteries up to full charge. At
full charge the battery pack will maintain operation of the S1400 system
for approximately 5 hours after primary power failure. The battery out-
put is regulated to 6 VDC for the monitor supply voltage.

Sensor Inputs

The sensor inputs are divided into three major groups identified as class
“A”, class “B”, or class “C”.
Class “A” inputs are operative (armed) all the time. 
Class “B” inputs are enabled after the preset Start-Run time period.
Class “C” inputs are armed only after the fault has been cleared 
for (2) seconds. (Example: Process Variables).

Opto-isolated Input

The Opto-isolated input is a special input in the explosion-proof power
supply which can be preprogrammed as:

1. Remote Reset Input (standard programs): Resets Start-Run timer and 

enables the Class “B” lockouts.

2. Explosion-proof Shutdown (optional): for Normally Open or for 

Normally Closed systems.

Permissive Function 

This function was designed to monitor prelube pressure input. 
Terminal 32 of the sensor terminal block is reserved for a permissive pre-
lube input. The pressure signal can be obtained from a pressure switch
with normally open or normally closed contacts that indicates whether or
not sufficient oil pressure has been reached during prelubing. If permissive
pressure has not been reached, the system will not allow start-up.

Intrinsically Safe Barrier

The power supply circuit is isolated from the S1400 module by the
intrinsically safe barrier located on the printed circuit board (power sup-
ply enclosure), between the power supply output and the 

power and

control cable terminal block.
The intrinsically safe barrier consists of seven (7) separate barriers. The
power output to the module is isolated by a Fuse Barrier (FB barrier)
mounted inside a sub-module attached to the power supply circuit board.
The four (4) control outputs from the S1400 module are isolated by
zener diode shunt barriers.

Remote Reset Function in terminal block

The S1400 can be configured for Remote Reset through sensor input ter-
minal #32 (must connect to dry contact mechanical switches, or an
approved explosion-proof barrier must be used).    
NOTE:  To make a selection for channel configuration, output relay
options, opto-isolator option, and to assist you with your selection, just
give us a call. (Phone and fax numbers on back page.)

Specifications

Power Consumption: 120 VAC (8 watts), 24 VDC (7.2 watts) or 

12 VDC (2.5 watts).

Sensor Inputs: For up to 32 normally open (NO) and/or normally closed

(NC) sensor inputs such as Murphy SWICHGAGE

®

control instru-

ments. Each input is factory programmed as a class A, B, or C for
shutdown, alarm, or control function.

Opto-isolated Input: 12-120 VDC or 24-120 VAC, the opto-isolated

input i typically used as a run input. 

NOTE: For connection of the S1400 with a CD ignition system use the
S14RSA92 adapter. Connect the adapter in series between the ignition
lead and the opto-isolator input.

Outputs: Four (4) SPDT relays, 4A, 1/20 HP, 125/250 VAC/3A, 30 VDC.

Timers: Four (4) adjustable timers designated for: lockout at start-up,

test timer, prelube, and postlube.

Time Delay: A delay before ignition ground or electric motor stop, for

up to 0.9 minutes each. 

Program Memory: Memory held in EPROM, 4k, 192 bytes of RAM.

Backup Battery: Recharged during normal operation. Provides up to 

5 hours backup time.

Operating Temperatures: 32° to 122°F (0° to 50°C).

Storage Temperatures: -4° to 158°F (-20° to 70°C).

Case:  ABS, 1/4 DIN (90 x 90 mm).

Interface Output: Digital, 7 bit straight binary code. (Requires an

S1400SP module, this option is not CSA approved). 

Display: Alphanumeric Dot Matrix, 2 line 32-character display.

Power Supply: Enclosure: Explosion-proof, Class I, Division 1.

Barrier: Intrinsically safe barrier built into power supply, 120 VAC
and 12 or 24 VDC power supply barrier.

GENERAL INFORMATION 

Continue from page 1

SPECIFICATIONS