background image

WARNING:

READ BEFORE INSTALLATION

Fluid hammer and surges can destroy any pressure transmitter/transducer
and must always be avoided. A pressure snubber should be installed to
eliminate the damaging hammer effects.
Fluid hammer occurs when a liquid flow is suddenly stopped, as with
quick closing solenoid valves. Surges occur when flow is suddenly begun,
as when a pump is turned on at full power or a valve is quickly opened.
Liquid surges are particularly damaging to pressure transmitter/trans-
ducer if the pipe is originally empty. To avoid damaging surges, fluid
line should remain full (if possible), pumps should be brought up to
power slowly and valves operated slowly. To avoid damage from both
fluid hammer and surges, a surge chamber should be installed, and a
pressure snubber, such as Murphy PD-8100 Series (adjustable) or
PM6203 Series (fixed) call Murphy for details, should be installed on
every transmitter/transducer.  

Symptoms of fluid hammer and surges damaging effects:
a. 

Pressure transmitter exhibits an output at zero pressure (large zero offset).

b. 

Pressure transmitter output remains constant regardless of pressure.

c. 

In severe cases, there will be no output.

Noise

For minimum noise susceptibility avoid running the transmitters/transduc-
ers cable in a conduit that contains high current AC power cables or igni-
tion loom on engine. Where possible avoid running the cable near induc-
tive equipment. Shielded cable is always recommended. Earth the shield
at one end only.

Mounting

CAUTION:

THESE ARE PRECISION INSTRUMENTS. 

DO NOT INSTALL IN ANY MANNER THAT CAN CAUSE
SIDE STRESS OR IS SUBJECT TO EXCESSIVE VIBRATION.

The transmitter/transducer requires no special mounting hardware and
can be mounted in any plane with negligible position error.
Although the unit can withstand substantial vibration without damage
or significant output effects, it is always good practice to mount the
transmitter where there is minimum vibration.

Apply Teflon tape/sealant to the pressure fittings threads before
installing. When tightening, apply a wrench to the hex wrench flats
located just above the pressure fitting. 

DO NOT

tighten by using a

pipe wrench on the housing.

PXT Series Electrical Connections

Hold when attaching

to pressure source

Do NOT twist body

1/4 NPTF

2.08 in.

(53 mm)

7/8 Hex

316 Stainless

Steel Housing

2  in.

(51 mm)

2.30  in.

(58 mm)

2.30  in.

(58 mm)

.86 in.
(22 mm)

.866 A/F

1/2 NPTM

7/8 Hex

316 Stainless

Steel Housing

60 in. (1524 mm)
long cable-std.

.86 in.
(22 mm)

1.18 in. Dia.
(30 mm)

1/4 NPTF

1.18 in. Dia.
(30 mm)

.866 A/F

1/2 NPTM

60 in. (1524 mm)
long cable-std.

High Pressure Units

Isc

93 mA

La

Ca

0.12  F
3 mH

POWER BARRIER

Voc

28 V

USE THE FOLLOWING PARAMETERS IF CABLE
PARAMETERS ARE UNKNOWN.

CABLE CAPACITANCE: 60 pF/ft

µ

F)

HAZARDOUS AREA

SAFE AREA

Class I, Groups A, B, C, D
Class II, Groups E, F, G

PXT SERIES

ALL INTRINSICALLY SAFE WIRING SHALL BE KEPT
SEPARATE FROM NON-INTRINSICALLY SAFE WIRING.
REFER TO ARTICLE 504 OF THE NATIONAL 
ELECTRICAL CODE OR THE CANADIAN ELECTRICAL CODE.

TRANSMITTER ENTITY PARAMETERS

TERMINALS

VMAX

IMAX

CI

LI

POS - NEG

28 V

93 mA

0.11  F

O.22 mH

BUSBAR

OUTPUT CURRENT MUST BE LIMITED BY A
RESISTOR SUCH THAT THE OUTPUT VOLTAGE
Vs CURRENT PLOT IS A STRAIGHT LINE
BETWEEN Voc AND Isc

BARRIER MUST BE INSTALLED AS
INSTRUCTED BY THE MANUFACTURER

SELECTED BARRIER INTRINSICALLY SAFE
CIRCUITS SHALL BE APPROVED FOR
CLASS I, II, III DIV 1 & 2, GROUPS A-G

TERMINATE BARRIER EARTH GROUND TO THE
GROUND BUS OF THE POWER DISTRIBUTION
PANEL.  RESISTANCE TO GROUND MUST NOT
BE GREATER THAN 1 OHM

1

2

3

4

BARRIER NOTES

CONTROL EQUIPMENT

MUST NOT BE CONNECTED TO
EQUIPMENT WHICH USES OR
GENERATES MORE THAN
250 VRMS WITH RESPECT TO
EARTH GROUND

POWER

RETURN

V SUPPLY

EARTH GND

Vmax >= Voc
I max >= Isc
Ci + C cable =< Ca
Li + L cable =< La

CABLE INDUCTANCE: 0.2

µ

H/ft

(EX.L Cable=1000ft x 0.2

µ

H/ft=0.2mH)

INSTALLATION INSTRUCTIONS FOR CLASS I DIV 2

UNITS MEET CLASS I DIV 2 WHEN INSTALLED IN ACCORDANCE

WITH CLASS I DIV 2 METHODS. EITHER BY USING THE CONDUIT
AND GROUND CONNECTION PROVIDED OR BY INSTALLING IN A

SUITABLE ENCLOSURE ACCEPTABLE TO THE LOCAL AUTHORITY
HAVING JURISDICTION.

INSTALLATION INSTRUCTIONS FOR CLASS I DIV 1

µ

 F

 F

µ

 F

 F

Reviews: