background image

 

Section 80

 

1900003

 

2019-01-18 

USB Overview / Requirements 

PowerCore

 Products 

The PowerCore

 products include the MPC20, MPC10, and the TEC-10. The MPC’s are also 

used in the ML series panels; ML2000 and ML1000 respectively.  

USB Configuration Loading Methods 

There are two methods used to load configurations; USB or CAN bus.  However, the TEC-10 

can only be loaded over the CAN bus. 

NOTE: 

When loading a new configuration, the original setpoints will be changed 

to the setpoints in the new configuration.

 

USB Thumb Drive 

1.  UDISK devices are not supported by PowerCore. With the Thumb drive installed, go to: 

control panel\device manager\disk drives. Expand disk drives to verify UDISK is not in 

the description.  

2.  Thumb Drive file system must be formatted for FAT. FAT32, EXFAT and NTFS are not 

supported by PowerCore. With the Thumb drive installed, go to: computer\removable 

disk. Right click on removable disk, click on Format. Check under File System to verify 

the format is compatible.  

Necessary PowerCore Harnessing for USB Loading 

MPC20 

Along with the 40000554 3’ 90 pin whip harness, the 40000566 USB programming 

harness is required. The 40000566 harness plugs in to the Molex connector on the 

40000554 harness. 

ML2000 

The 40000566 programming harness is included in the ML2000. Remove the four 

screws holding the black inner panel to the enclosure. Gently pull the inner panel away 

from the enclosure far enough to expose the 40000556 programming harness.  

MPC10 

Along with the 40000598 3’ 3x12 whip harness, the 78000668 USB programming 

harness is required. The 78000668 harness plugs in to the USB receptacle on the back 

of the MPC10. 

ML1000 

The 78000668 programming harness is not included in the ML1000. Remove the four 

screws holding the black inner panel to the enclosure. Gently pull the inner panel away 

from the enclosure far enough to expose the back of the MPC10. The 78000668 

harness plugs in to the USB receptacle on the back of the MPC10.  

Summary of Contents for PowerCore MPC-20

Page 1: ...1900003 Section 80 2019 01 18 Murphy PowerCore Configurations Installation Manual...

Page 2: ...designs at any time The latest version of this manual can be found at enovationcontrols com BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT Read and follow all installation instructions Observe a...

Page 3: ...ments 5 PowerCore Products 5 USB Configuration Loading Methods 5 USB Thumb Drive 5 Necessary PowerCore Harnessing for USB Loading 5 Loading Configurations with USB 6 MPC20 MPC10 Older Method 7 CAN Ove...

Page 4: ...Section 80 4 1900003 2019 01 18 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 5: ...ight click on removable disk click on Format Check under File System to verify the format is compatible Necessary PowerCore Harnessing for USB Loading MPC20 Along with the 40000554 3 90 pin whip harne...

Page 6: ...figuration is an older version that choice is not there and the older method must be used MPC20 MPC10 LOCAL METHOD The file name can be customized for easy reference but the file must have gciBin as t...

Page 7: ...ntroller to return to normal operations NOTE If the loading process is interrupted or the power or thumb drive are removed the older method detailed below must be used MPC20 MPC10 Older Method Using t...

Page 8: ...essing for CAN Loading The 40000625 programming kit or equivalent is required to load programs in to the TEC 10 This same kit can be used on the ML PowerCore panels Loading Configurations with CAN Ste...

Page 9: ...01 18 Step Action 6 Click on Load Firmware This process takes about 3 to 4 minutes During the load the amber LED will blink on the controller When the load is finished the controller will reset and r...