Specifications
Crankcase Balance Vent Connection:
1/2 NPTF (top).
Inlet Connection:
1/2 NPTF with removable screen (side).
Outlet Connection:
LM2000 3/4 NPTF (bottom).
LM2000S 2 x 3/8 NPTF (side)
1 x 3/4 NPTF (bottom)
Thumb-Valve™ Material:
Viton.
Snap-switch:
SPDT rating 10 A, 125 VAC; 0.5 A, 125 VDC; 10 A, 30 VDC.
Wire leads:
18 AWG x 14 in. ± 2 in. (355 mm) length.
Conduit Connection:
1/2 inch conduit (female, top).
Case:
Die cast aluminum
Lens:
Clear “Frog Eye” non-staining, high impact, high temperature nylon; UV and heat stabilized.
Dial:
High visibility white background with green and white “index” lines for normal level indication.
Maximum Inlet Pressure:
9.50 psi/25 ft. oil (head pressure).
Maximum Case Pressure:
15 psi (103 kPa).
Maximum Differential:
2 in. (51 mm) between running and stopped.
Maximum Ambient Temperature:
250°F (121°C).
Float:
Brass
Flow Rates:
SAE 40 motor oil @ 32°F (0°C) with 2 ft. head pressure: 0.5 GPH (1.9 LPH).
NOTE:
Friction losses due to piping not considered.