background image

Programmable functions

The Autostart 705 has over 40 programmable functions:-

Timers:-

Start delay; preheat, crank and crank cool (dwell) times;
fault override time; warm-up delay, mains restore delay;
engine cool (run on, off load) time, speed signal delay.

Inputs:-

Inputs 1 and 2 are dedicated for use with low oil pressure
and high engine temperature switch sensors. Inputs 3, 4
and 5 may be programmed for a range of uses, including
shutdown or warning faults, lamp test, manual restore (of
mains), test off load, alarm mute, etc. The inputs may be
set up to work with remote contacts which either open or
close when active, with wiring to ve or –ve DC.

Outputs:-

6 programmable outputs, each of which may be set to
give one of over 30 signalling or control ‘actions’,
including: Preheat (4 types), Energised to Stop Fuel,
Louvre Control, Generator Available, Common Alarm,
Alarm (muteable), Shutdown Fault, Warning Fault,
Overspeed, Start Fail, individual input faults (1 - 5), etc.

LED indicators:-

5 programmable LED indicators, each of which may be
set to display extra status information (e.g. ‘generator on
load’, ‘fuel on’) or specific faults which are not indicated by
the dedicated LEDs (e.g. low/high/faulty battery voltage,
low generator volts, magnetic pickup failure, etc.).

Next to the 5 LEDs is a windowed 'pocket' in the front
label, into which a custom message label may be inserted.
A sheet of typical fault and status messages
is supplied with each unit.

Other System parameters:-

Crank release (by engine RPM, generator Hz. or charge
alternator WL voltage), underspeed and overspeed trip
levels (Hz. or RPM); maximum number of start attempts;
high and low battery voltage warning levels; enable or
disable loading of generator in manual mode.

Each Autostart is programmed by use of Murphy-Modex
communication software running on an IBM compatible PC
or lap-top. The computer is connected to the Autostart
through a small interface unit and serial lead. Autostart
program ‘profiles’ may be created, edited or saved on the
computer’s hard disk, up-loaded from or down-loaded to
any number of Autostarts, quickly and error-free.
The software also has a real-time monitoring feature,
allowing the PC to display data such as operating mode,
engine running status, speed/ frequency, hours run, fault
conditions, battery voltage, input/output status, etc.

When ordering, please specify:-

AS705S

Generator AC voltage:-

Switch option:-

K = keyswitch
R = rotary (knob) switch

D = 230 VAC
C = 110 VAC

 Rear Facia & Electrical Connection

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

22

23

24

25

26

27

28

29

30

21 Index Pin

– ve DC supply

Charge fail input

+ ve DC power supply

+ ve DC (relays)/Emerg. stop

Magnetic pickup input

Output 1

Output 2

A800 enable (engine running)

Output 3:       –ve, < 250mA

Output 4: –ve DC, 5A max.

5 – 40 VDC

+ ve DC

250mA max.

Fuel output

Starter output

Output 5 (alarm): +ve, 5A max.

NO

CO

Live 

Neutral

Man. Stop

Man. Start

+ ve DC

16A max.

Generator AC 

300 VAC max.

– ve

Output 6 (gen. contactor)

volt free, 5A max.

Input 1: low oil pressure

Input 2: high engine temp.

Input 3: programmable

Input 4: programmable

Input 5: programmable

Remote start/mains fail input

Off output: – ve DC, < 250mA

Manual output

Auto output

No connection -

– ve DC

250mA max.

For a typical connection circuit, please see Autostart 710
data sheet (the Autostart 705 and 710 are pin compatible).

 Front Facia

10 pre-set status
and fault LEDs

5 programmable
status LEDs
(2 amber, 3 red)

3 position operating
mode switch:-

 

Off/reset
Auto

  

Manual

MODEX

START DEMAND
ENGINE RUNNING

START FAIL

LOW OIL PRESSURE

HIGH ENGINE TEMP
OVERSPEED

UNDERSPEED

CHARGE FAIL

PLANT FAIL

EMERGENCY STOP

Accessories:-

AS7CA

9 way (interface) to 9 way (PC) comms lead

AS7CB

9 way (interface) to 25 way (PC) comms lead

AS7CC

interface for local RS232 communications

AS7CK

AS7xx communication and programming software

Since 1939

Frank W. Murphy Manufacturer

PO Box 470248, Tulsa, Oklahoma 74147, USA

Tel: + 1 918 627 3550  Fax:  + 1 918 664 6146

email: [email protected]

web: http://www.fwmurphy.com

Frank W. Murphy Southern Division

PO Box 1819, Rosenberg, Texas 77471, USA

Tel: + 1 281 342 0297   Fax: + 1 281 341 6006

email: [email protected]

Frank W. Murphy Ltd.

   Incorporating

 

Modex Automation

Church Road, Laverstock, Salisbury U.K.

Tel: + 44 1722 410055  Fax + 44 1722 410088

Pour service en Français, tél: + 44 1722 410697

email: [email protected]

web: http://www.fwmurphy.co.uk

Macquarrie Corporation

1620 Hume Highway, Campbellfield, Vic. 3061 Australia

Tel: + 61 3 9358 5555   Fax: + 61 3 9358 5558

email: [email protected]

Murphy Switch of California

41343 12th Street West, Palmdale, CA 93551, USA

Tel: + 1 661 272 4700   Fax: + 1 661 947 7570

email: [email protected]

web: http://www.murphyswitch.com

Murphy de Mexico S.A. de C.V.

Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje

San Luis Potosí, S.L.P. México 78384

Tel: + 52 48 206264  Fax: + 52 48 206336

email: [email protected]

Frank W. Murphy Pte, Ltd.

No. 2 Tuas South Street 2, Sprintecs Building

02-01/02, Singapore 637895

Tel: + 65 863 1398    Fax:  + 65 863 0208

email: [email protected]

Frank W. Murphy Ltd. en France

Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89

Direct usine Tel: + 44 1722 410697

email: [email protected]

Reviews: