background image

 

a.  Cartridge – The water flow can be adjusted using a slotted narrow blade screwdriver and turning 

clockwise to increase flow and counterclockwise to decrease flow.

TROUBLE SHOOTING:
IMPORTANT: BEFORE MAKING ANY OF THE REPAIRS LISTED, MAKE SURE THE
WATER CHILLER IS DISCONNECTED FROM THE ELECTRICAL SUPPLY AND THE
WATER SUPPLY VALVE IS SHUT OFF.
1. ADJUSTMENTS:

 

b.  Cold Water Thermostat – The water temperature can be adjusted using a slotted screwdriver and turning 

clockwise to make colder and counterclockwise to make warmer.

2. COMPRESSOR DOES NOT RUN:

 

a.  Check the electrical supply for power and correct voltage. The incoming voltage must be within 10% of 

the rated voltage on the serial nameplate.

 

c.   Bubbler Stream - Bubbler can be rotated slightly to direct the stream backwards or forwards. Adjust the 

stream to minimize splashing. Splashing may occur from bubbler stream if the unit is not level. Shim lower 
mounting point, if necessary, to level chiller.

 

b.  If the cold thermostat capillary bulb loses its charge or becomes kinked, it will fail in the open position 

causing a disruption of power to the compressor. Disconnect electrical supply to the water chiller and 
using an ohm meter, check for continuity across the two electrical terminals on the thermostat. Install a 
new thermostat if there is no continuity.

 

c.  Check for loose wires within the compressor box. The incoming power leads must be connected to the 

overload and relay.

 

d.  If all components check positive for continuity, then test the wiring harness plug for continuity to see if 

there is a broken wire within the wiring harness insulation.

3. COMPRESSOR RUNS - WATER IS WARM:

 

b.  Make sure the condenser fan motor is operative. The fan blade must turn freely to help remove the heat 

of compression.

 

c.  An incorrect refrigerant charge, restriction or defective compressor (not pumping) will also cause the 

compressor to run without producing cold water. All these signs indicate a problem within the refrigeration 
system and the water chiller must be checked by an authorized service company.

 

a.  The most common cause for a water chiller to run without producing cold water is a loss of refrigerant. 

The water chiller must be taken to a certified refrigerant technician for repairs.

 

a.  Check to make sure the fan blade is rotating freely.

 

c.  A restriction or moisture in the system will also cause intermittent cycling. A certified refrigeration 

mechanic should be contacted in this situation.

5. NOISY OPERATION:

 

a.  Ensure water supply service stop valve is fully open.

 

b.  Verify minimum 20 psig supply line flow pressure.

 

f.  Check flow adjustment. See start up note #3.

 

b.  Check the incoming voltage to make sure it is within 10% of the serial nameplate rating.

 

c.  Check for twists or kinks in outlet tubing.

 

d.  Check the water inlet “Y” strainer. Sediment from the main supply can get trapped in the screen along 

with installation materials such as pipe dope and flux. The screen should be cleaned and checked on a 
regular basis and replace if needed.

 

g.  Flow control in solenoid valve outlet elbow clogged remove & clean.

 

b.  Check the compressor mounting to make sure the pins and clips are not rattling. If the compressor 

appears to be noisy internally, it must be replaced.

 

a.  A dirty condenser or a blocked fan will cause a high head pressure and frequent cycling of the overload 

protector.

 

h.  The water chiller may also develop a freezing condition in which the water will become frozen inside the 

6. RESTRICTED OR NO WATER FLOW:

 

e.  The cartridge valve located in the water control assembly or bubbler can also become clogged with 

foreign material. The cartridge valve can only be replaced and not repaired.

4. COMPRESSOR CYCLING ON OVERLOAD PROTECTOR:

 

d.  Change the overload or relay if defective.

I N S TA L L AT I O N / M A I N T E N A N C E  I N S T R U C T I O N S

CONTEMPORARY WATER COOLERS

 

I N S TA L L AT I O N / M A I N T E N A N C E  I N S T R U C T I O N S

 DRINKING FOUNTAINS

 

 

A152.8-BF4

Page 18 of 23

Revised: 

07/18/18

7020-949-001

MURDOCK  MFG.  • 

15125  Proctor  Avenue  •  City  of  Industry,  CA  91746  USA 

Phone  800-453-7465  or  626-333-2543  •  Fax  626-855-4860  •  www.murdockmfg.com

Member of

Summary of Contents for A152 8-BF4 Series

Page 1: ...mplied Product maintenance instructions are issued with each unit and disregard or non compliance with these instructions will constitute an abnormal use condition and void the warranty Stainless steel must be protected on job site during construction and must be properly maintained after the water has been introduced into the water cooler or drinking fountain or Murdock s limited warranty is void...

Page 2: ...with Bottle Filler NOTES Dimensions shown for Adult ADA compliant installation For Child ADA compliant parallel approach installation decrease height of installation by 3 inches Provide clear floor space as required Adjust vertical dimensions as required to comply with federal state and local codes I N S TA L L AT I O N M A I N T E N A N C E I N S T R U C T I O N S CONTEMPORARY WATER COOLERS I N S...

Page 3: ...ERS I N S TA L L AT I O N M A I N T E N A N C E I N S T R U C T I O N S DRINKING FOUNTAINS A152 8 BF4 Page 3 of 32 Revised 07 18 18 7020 949 001 MURDOCK MFG 15125 Proctor Avenue City of Industry CA 91746 USA Phone 800 453 7465 or 626 333 2543 Fax 626 855 4860 www murdockmfg com Member of General Notes 1 All dimensions are in inches 2 Dimensions shown are for recommended adult height Adjust vertica...

Page 4: ...e as required Adjust vertical dimensions as required to comply with federal state and local codes A152408S BF4 Refrigerated Wall Mounted Drinking Fountain Inlet Outlet Rough Ins Note There are no mounting changes to be made for SO models 16 8 38 C L 2 1 2 TYP 35 295 8 3 8 TYP 501 2 BLOCKOUT 561 4 301 4 BLOCKOUT 31 2 1 2 3 4 General Notes 1 Dimension indicated with is for 33 drinking fountain disch...

Page 5: ...on is always on the right hand side of the shelf Installation Instructions A Provide 30 1 4 wide x 50 1 2 tall wall opening at appropriate height Provide structural support around inside of the opening for frame anchoring B Carefully remove Bi Level Mounting Frame 1 chiller mounting frame 2 panel anchoring clips 3 and screws 4 from packaging preventing damage C Center both frames within wall openi...

Page 6: ... inlet is 3 8 Outer Diameter copper tube Water line by others from in wall chiller to drinking fountain must have adequate insulation 4 Completely flush supply lines of all foreign debris before connecting to fixture Water cooler designed to not cause problems with taste odor color or sediment Optional Water Filter WF1 is available should any of these problems arise from the water supply 6 All bur...

Page 7: ...ste connection 3 FOR BF4 ONLY Make up power connections to the ground neutral hot within the electrical box 2 Place the Chiller Unit onto the basepan of the frame assembly 3 Hang upper trim panel on mounting frame Note The included 1 brackets do not get used with this installation and the plastic spacers are typically not required and can be discarded 8 Make up 1 1 4 outer diameter waste connectio...

Page 8: ...ling fan to ensure proper clearance and free fan action ŸSENSOR OPERATED Hold container to be filled just below the sensor in the center of the filler spout and then move the container upward and water flow will start automatically When the container is almost filled lower the container below the sensor until the water stops flowing See label on the bottle filler 1 Air within the bottle filler sys...

Page 9: ... City of Industry CA 91746 USA Phone 800 453 7465 or 626 333 2543 Fax 626 855 4860 www murdockmfg com Member of WATER TUBING CONNECTIONS NOTE Insulation on all water tubes not shown all PE water tubes are insulated 3 8 O D Copper Inlet 3 8 O D Copper Outlet Electrical Knockout Chiller Assembly Detail Thermal Adjustment PE Tubing PE Tubing Fill Spout 9 12VDC Solenoid Valve Solenoid Valve Outlet Elb...

Page 10: ...53 7465 or 626 333 2543 Fax 626 855 4860 www murdockmfg com Member of ITEM PART NUMBER DESCRIPTION 1 0250 006 000 10 x 5 8 Phillips Truss Head Screw 2 7014 035 199 Water Filter Bracket 3 0124 031 000 8 x 3 8 Hex Washer Head Screw 4 1895 709 000 Elbow 1 4 Push In x 1 4 Stem 5 7012 311 000 WF1 Filter 1500 Gallon 6 2169 000 000 Tubing 1 4 O D LLDPE Blue 7 7012 055 000 Foam Pipe Insulation FILTER MOUN...

Page 11: ...0 www murdockmfg com Member of ITEM PART NUMBER DESCRIPTION 1 0250 006 000 10 x 5 8 Phillips Truss Head Screw 2 7014 055 199 Bracket Dual Filter Mount 3 0124 031 000 8 x 3 8 Hex Washer Head Screw 4 1895 709 000 Elbow 1 4 Push In x 1 4 Stem 5 7012 311 000 WF1 Filter 1500 Gallon 6 2169 000 000 Tubing 1 4 O D LLDPE Blue 7 7012 055 000 Foam Pipe Insulation Not Show n 8 1895 710 000 Untion Tee 1 4 Push...

Page 12: ...e provided by others Turn valve knob 1 4 turn clockwise to close OPTIONAL WF1 WATER FILTER INSTALLATION 2 With the filter assembly secured on the unit hold before re mounting panel assembly to fixture the cap firmly turn the replaceable cartridge filter counterclockwise to remove clockwise to secure 1 Remove panel assembly this allows access to the FILTER CARTRIDGE REPLACEMENT 3 Remove and replace...

Page 13: ...OOLERS I N S TA L L AT I O N M A I N T E N A N C E I N S T R U C T I O N S DRINKING FOUNTAINS 1B For Reverse Bi Level unit will be reversed NOTE Plug in power is a standard feature 1A Plug In Operation Plug transformer provided into GFCI protected electrical service used by the semi recessed bottle filler Plug in transformer to power supply and connect to red sensor wire ELECTRICAL INSTALLATION 9 ...

Page 14: ...UNTER ADJUSTING RESETTING INSTRUCTIONS Bottle Counting Function The software applies a flow volume of approximately 16 9 fl oz volume in standard size plastic water bottle to each bottle counted If the flow volume is less than 16 9 fl oz there will be no count but the volume will accumulate so that part way through the next cycle the total bottle count will change NOTE Bottle Counter Has Multiple ...

Page 15: ...lter flow volume is reached FLTR NO means that there is no filter in the system and a REPLACE FILTER alert WILL NOT APPEAR on the display Release button when the option required is on the display Filter Yes or No NOTE This Function only applies if the system as a filter Replace old filter with new filter Depress the Reset Mode selection button for 2 SECONDS The REPLACE FILTER will no longer appear...

Page 16: ... R U C T I O N S CONTEMPORARY WATER COOLERS I N S TA L L AT I O N M A I N T E N A N C E I N S T R U C T I O N S DRINKING FOUNTAINS OPTIONAL BCD BOTTLE COUNTER DISPLAY See the following page for models with BCD Bottle Counter Display A132 BF4 BCD BOTTLE FILLER BOTTLE COUNTER CONNECTIONS Solenoid Connection Power Supply Connection Black Cables Sensor Connection Black Red Cables Sensor Connection Tra...

Page 17: ...re Tube should not come free from the fitting Water test the connection assembly prior to leaving the site to ensure there are no leaks DISCONNECTING THE TUBE To disconnect the tube from the fitting ensure that the water line is depressurized Push collet square towards the push in fitting body and hold While holding the collet in pull on the PE tubing to remove from the push in fitting TO CUT TUBE...

Page 18: ...igeration system and the water chiller must be checked by an authorized service company a The most common cause for a water chiller to run without producing cold water is a loss of refrigerant The water chiller must be taken to a certified refrigerant technician for repairs a Check to make sure the fan blade is rotating freely c A restriction or moisture in the system will also cause intermittent ...

Page 19: ...r or two holes in convolution of the water diaphragm Remove and clean 1 Motors have lifetime lubrication and do not require scheduled maintenance 2 Excess dirt or poor ventilation will cause the compressor overload protector to turn the compressor off and it will cycle on and off with no cold water coming out of bubbler Periodically clean with vacuum cleaner air hose or brush the condenser fins an...

Page 20: ... PART NUMBER DESCRIPTION 1 7000 005 199 Drain Adapter 10 0308 009 000 Nylon Insert Locknut 2 0116 016 000 Phillips Truss Head Screw 11 0331 004 000 Flat Washer 3 7000 006 000 Flat Drain Adapter Gasket 12 7001 008 001 Valve Activation Assembly 4 7000 015 000 1 1 4 OD P Trap 13 0341 100 000 Wire Clip 5 7000 021 001 Y Strainer 14 7000 100 199 Black Delrin Shaft 6 0152 010 000 10 32 x 1 2 Hex Flat Hea...

Page 21: ... PART NUMBER DESCRIPTION 1 7000 005 199 Drain Adapter 10 0308 009 000 Nylon Insert Locknut 2 0116 016 000 Phillips Truss Head Screw 11 0331 004 000 Flat Washer 3 7000 006 000 Flat Drain Adapter Gasket 12 7001 008 001 Valve Activation Assembly 4 7000 015 000 1 1 4 OD P Trap 13 0341 100 000 Wire Clip 5 7000 021 001 Y Strainer 14 7000 100 199 Black Delrin Shaft 6 0152 010 000 10 32 x 1 2 Hex Flat Hea...

Page 22: ...RDOCK MFG 15125 Proctor Avenue City of Industry CA 91746 USA Phone 800 453 7465 or 626 333 2543 Fax 626 855 4860 www murdockmfg com Member of Repairs must be made with Murdock Manufacturing parts only Please order through your local representative or distributor The phone number to locate your local representative is 1 800 591 9360 37A 45 32 33 34 35 46 47 40 44 43 42 41 39 40 38 36 10 11 12 13 24...

Page 23: ... 2 Stainless Steel Truss Head Screw 17 7013 238 199 Y Strainer Clamp 18 7013 235 001 3 Way Divider Assembly 1 4 x 1 4 19 0112 021 000 10 32 x 1 2 Stainless Steel Button Head Hex Screw 20 7013 231 199 3 Way Divider Bracket Assembly 1 4 x 1 4 21 0331 042 000 6 Helical Spring Lock Washer 22 0302 011 000 6 32 UNC Stainless Steel Hex Nut 23 7000 245 000 Back Panel Spacer 24 7014 150 001 Frame Assembly ...

Reviews: