19.6
Defining the Heat
Central Corridor enables heating the air before it enters the rooms. Heaters act as zone heaters.
Define up to six relays and/or ports as heaters. Refer to the Installation Manual.
1. Go to Control > Heat. In the following example, four heaters are enabled, two on off heaters
and two 0 – 10VDC variable heaters.
•
In this example, Heaters 1 and 2 and on off heaters. Heaters 3 and 4 are variable heaters.
2. Define:
NOTE
The temperatures here are absolute temperatures; there is no temperature band.
o
On Temperature: Below this temperature, the heaters turn on. Range: -40⁰ to Off
temperature
o
Off Temperature: Above this temperature, the heaters turn off. Range: Off temperature to
90⁰ C.
o
Max Heat Temperature: Set the temperature at which heaters work at maximum
capacity. Range: -40⁰ to On temperature
o
Minimum Output: Set the voltage at which heaters work at their minimum level.
o
Maximum Output: Set the voltage at which heaters work at their maximum level.