11
When delivered as components
1. Place the reservoir in the unit and assemble the side posts,
cross beam and rubber sealing.
Insert the cassette bridge.
2. Secure the cover plate against the unit casing and the
humidifier casing, using self tapping stainless-steel
sheet-metal screws. The cover plate size is shown in the
dimensioned drawing below. Make sure unit is mounted
level.
3. Insert the cassettes and the droplet separator, if any, accord-
ing to the disassembly instructions of cassettes and droplet
separator page 15.
Note the direction of the air flow.
4. Mount the Discharge pipe, see page 12, and connect it to
the drain. Don’t tighten the hose clip so tight that the dis-
charge pipe is deformed. A water trap is recommended.
5. Assemble the distribution header and connect water hose to
distribution pipe. The cassette is locked in place by pressing
the snap catches straight down, causing the distribution
header to lock into the cassette. Check that the distribution
head cannot be lifted upwards.
6. Attach the hoses to the distribution header and connect the
bleed-off valve to the discharge pipe.
7. For units with circulating water, install the pump assembly.
Direct water units install distribution pipe.
8. Connect FA6 unit to BMS/Control system. Please note that
all electrical wiring must be done according to national
standards by qualified personnel.
25 mm
25 mm
25 mm
25 mm
Note! Do not drill any holes in
the water tray!