7.2 Motor specifications
Model
Nominal Power
[W] [hp]
Phases
Speed
frequency
[Hz]
voltage
[v]
Current
[A]
rpm
Poles
EDX18
EDC
18
240
0.33
3
single
50
230/400
1.7/1
1,400
4
240
0.33
3
single
60
230/400
1.7/1
1,700
4
240
0.33
1
single
50
220
2.5
1,400
4
180
0.25
1/3
single
50
230/400
1.12/0.65
900
6
180
0.25
3
single
60
230/400
1.12/0.65
1,100
6
EDX26
EDC24
370
0.5
3
multi*
50
230/400
2.5/1.5
900
6
370
0.5
3
multi*
60
230/400
2.5/1.5
1,100
6
370
0.5
1
multi*
50
220
4
900
6
370
0.5
1
single
60
220
4
1,100
6
370
0.5
3
single
50
230/400
2.1/1.2
925
6
370
0.5
3
single
60
230/400
2.1/1.2
1,100
6
* Multi speed motors must be regulated with auto-transformer which is not supplied.
7.3 Technical specifications
EDC18
6 poles
EDC18
4 poles
EDX18
4 poles
EDC24
EDX26
Weight of fully equipped air circulator*
[kg]
15
16
17
22
26
Nominal propeller speed 50/60Hz
[rpm]
900/1,100
1,400/1,700
1,400/1,700
900/1,100
900/1,100
Airflow at 0 Pa*
[m
3
/h] [cfm]
2,600
[1,530]
3,950
[2,325]
4,027
[2,370]
7,400
[4,350]
10,300
[6,060]
Specific performance at 0 Pa*
[m
3
/Wh] [cfm/W]
16.1 [9.5]
9.2 [5.4]
11 [6.5]
11.2 [6.6]
17.9 [10.5]
Propeller diameter
[mm] [inch]
450 [18]
450 [18]
450 [18]
600 [24]
650 [26]
Number of blades
6
6
6
6
6
IEC protective class of electric motor
IP55
IP55
IP55
IP55
IP55
Technical data