Installation
15
DryCool HD Operator and Maintenance Manual
P00960167-1
Before performing maintenance or service on fixture, ensure unit is
unplugged. Electrical shock may cause injury or death.
Never expose eyes or skin to UVC light from any source. Wear gloves, face shield/glasses (per
ANSI Z87.1) and cover all exposed skin.
Do not touch Emitter glass without gloves. Damage to Emitter may result. Oil from fingerprints
will permanently etch glass of Emitter. If necessary, clean Emitter using optional cleaning kit.
Voltages outside of the range designed for the unit will void the warranty and do permanent
damage to the entire unit.
Emitter contains a small quantity of mercury. If an Emitter breaks, clean and dispose with care.
Note:
Ensure that emitter is installed before power is applied. Installing emitter after the power has been
applied will trigger the “end of lamp life circuit” and emitter will fail to light! If this happens, shut off/de-
energize power for 10 minutes and then turn power back on. Emitter will then light.
Disconnect power from unit
Remove installation hole plug. This black plastic plug is located on the same end of unit as the control
panel and is above the condensate drain outlet.
Install UVC lamp emitter according to installation instructions included with the emitter.
Attach UVC emitter power pack to the side of the DRYCOOL™ HD unit with sheet metal screws
provided with UVC emitter. Installation location noted in illustration below.
Plug power supply into the outlet on unit labeled “UV Light”.
Power can now be reconnected to unit.
16.5”
10”
24”
12.5”
7.5”
Approx. 4”
UVC
POWER
PACK
DRAIN
POWER
CORD
Figure 7: UVC Power Pack Installation