17
© Munters Corporation, August 2017
QM1227r4
Electrical Wiring
Chapter 3
To operate the Munters Drive Off/Low/High with a control, slide the ‘RUN’ switch, located on the circuit
board in the Munters Drive Box, to the ‘OFF’ position. Now wire an ‘ON’ command from the ‘COMMOM’
terminal to the input relay in the control and from the output of the relay to the ‘RUN’ terminal in the Munters
Drive Box. Then connect the output of the control relay for ‘LOW’ to the ‘REDUCED FLOW’ terminal in the
Munters Drive Box.
See Figure 13E.
¡
¢
£
¤
¥
¦
§
¨
©
¨
ª
¡
Figure 13E
Off/Low/High Remotely