background image

There are two types of precautions as described below:

         Warning: Failure to comply may lead to death or serious injury.

         Caution: Failure to comply may lead to injury or damage of the unit. 

Depending on the situation, this may also lead to serious injury.

Once the installation is completed, please keep the manual properly for future 

reference. When this air conditioner is handed over to other users, make sure 

that the manual is included with the handover.

Operation Manual

 

 

 

Warning

$

Do not use this unit in locations where flammable gas may exist. If 

flammable gas comes into contact with the unit, a fire may occur, which 

could result in serious injury or death.

$

%&!\!˜&!!Z&!\&!!#`&!

a danger of serious injury. Disconnect the power supply and contact your 

supplier or service engineer immediately.

$ }&!#!&!\!!;&\;`!&Z

is designed and installed properly. However, if a large amount of refrigerant 

leaks into a room, the oxygen concentration will decrease rapidly, which can 

cause serious injury or death. The refrigerant used in this unit is heavier 

than air, so the danger is greater in basements or other underground 

spaces. In the event of a refrigerant leak, turn off any devices that produce

       a naked flame and any heating devices, ventilate the room, and contact your 

supplier or service engineer immediately.

$

}˜! \ Z  ?;\; ! & !# ! &! \!  !

contact with naked flames (such as from a heater, gas stove/burners, or 

electric appliances).

$

% &! \! ! \; ! &     `Y Y &Y  \Y

ventilation for sufficient fresh air must be ensured, otherwise the oxygen 

concentration will fall, which may cause injury.

$

!?  &! \!™ ?`#!# \ZY  &!;  ?Z €!& !

Packaging, especially plastic packaging, can be dangerous, can cause serious 

injury or death. Screws, staples and other metal packaging components can 

be sharp and should be disposed of carefully to avoid injury.

$

?!??!&!\!Z\}&!\!&\;Z

serviced and maintained by a professional air conditioning service 

engineer. Incorrect servicing or maintenance can cause electric shocks, fire 

or water leaks.

$

}&! \! &\; Z  Š?!!;  Š!; Z  ?!

technician. Incorrect installation can lead to electric shocks, fire or water 

leaks. The installation and grounding of electrical appliances should only be 

carried out by licensed professionals. Ask your supplier or installation 

engineer for further information.

$

€&!\!!!€!&€Y

as this can lead to electric shocks or fire.

$

}\&\!!#!!;!&`&€!Y

electric shock and injury may result.

$

}!;!&`;!Y!&`#;

$

  \ ?!Y !&Y &! ?ZY &  ?Z  &

liquids that may give off flammable fumes/vapor near this unit, as doing so 

can cause fires.

$

‚&?!#\Y\&&€\!;?Z

complies with requirements.

$

  ?   & \!š ? €& & \! ! ?€; 

Touching the unit's internal components while the unit is powered on can lead 

to electric shocks or injuries caused by moving parts such as the unit's fan.

$

›\ & & ?€ \??Z ! ;!;  Z !!# 

maintenance is carried out.

$

\&&\!!€!&€&;Y;!#

can lead to electric shocks.

$

€&!;?Z&!\!Y;!#!`!“\Z

$

!Z\!#&“!&\!™!!!\

to avoid injury or damage to the equipment.

$

?ZZ!{\!;&\!€Z!{\!;;!?&\!

$

?&!{\!;!&\!!?€&

liquid could drip onto it. Water or other liquids that come into contact with the 

unit can lead to electric shocks or fires.

$

&™`;;\&&

™!?Y;!#\!“\Z%&

remote controller stops working, contact your supplier or service engineer.

$

›\&&\!!??Z#\;;Y&€!!&`!

may result. Electrical surges (such as those that can be caused by lightning) 

can damage electrical equipment. Ensure that suitable surge protectors and 

circuit breakers are properly installed, otherwise electric shocks or a fire 

may result.

$

!?&!\!??Z;!;€!&#\!%!

appliances are disposed of in landfills or dumps, hazardous substances can 

leak into the groundwater and thus enter the food chain.

$

\&\!\!&{\!!;&!!!\Z\&!!

to do so.

$

???!&?;\`;!&?&&!€

from the unit. The airflow from the unit may increase the rate of combustion, 

which may cause a fire and cause serious injury or death. Alternatively, the 

airflow may cause incomplete combustion which can lead to reduced 

oxygen concentration in the room, which can cause serious injury or death.

Caution

$

Z\&!;!!!!;;?\?}&!\!&\;

used to provide refrigeration or cooling for food, plants, animals, machinery, 

equipment or art.

$

!Z\!#&“!&\!™!!!\

to avoid injury or damage to the equipment.

$

}& !  & \!™ & ˜&#  &? ;  \ !“\Z !

touched. To prevent injury, when the unit is being serviced, gloves should 

be worn or the heat exchanger should be covered.

$

?!€&!&!#&;#;Z!\\;&\!‚&

the humidity is greater than 80% or if the drain pipe is blocked or the air filter is 

dirty, water could drip from the unit and damage objects placed under the unit.

$

›\&&;!?!?\!??Z%&;!?!?!`;Z

dirt or dust, water leaks may occur when the unit is running in cooling mode. 

If this happens, turn the unit off and contact your supplier or service engineer.

$

  \& & ! ?  &     & front 

panel. Some internal parts may cause injury or be damaged.

$

›\ & &!;Y ? ; !   ;!Z ˜?;  &

airflow from the unit.

$

‚&\!#!#€!&!!!;&&!Y&\!

well and do not run it. Failure to observe this caution could lead to chemicals 

getting deposited inside the unit and later emitted from the unit when it 

running, endangering the health of any room occupants.

$

  ;!?  &! ?;\  \; € % \  ?Z

collected and processed. Ensure that all applicable legislation regarding the 

disposal of refrigerant, oil and other materials is adhered to. Contact your 

local waste disposal authority for information about disposal procedures.

$

To avoid damaging the remote controller, exercise caution when using it and 

replacing its batteries. Do not place objects on top of it.

$

???!&&`;\;&\!Y

heat from the appliance can damage the unit.

$

?&\!™!;!\!#&!\!#&

;#&™;!?Z

$

  \ # &!    & \!Y  ;!#  

;#&\!™;!?Z&\%&\!!;!Z;\ZY\

a slightly damp cloth with very diluted and mild detergent to wipe the unit. 

Then, dry it with a dry cloth.

$

&!;&?Z€!&&??!

10. Part Names

The figure shown above is for reference only and may be slightly different from 

the actual product.

Air Outlet Louver (adjustable)

For in-situ adjustment to three-direction or two-direction, please contact the 

local dealer.

œ

High static pressure duct type

Air Outlet 

Air Intake 

Electric Control Box

Figure 10.1

39

Summary of Contents for MVD DC2 CL23530

Page 1: ...ci n y usuario High Pressure Duct Installation and owner s manual FR Manual d utilisation et d installation voir www mundoclima com fr DE Benutzer und Installationshandbuch sehen www mundoclima com de...

Page 2: ...ES EN 1 23 Manual de instalaci n y usuario Installation and owner s manual...

Page 3: ...i n debe ser MONOF SICA una fase L y una neutro N con conexi n a tierra GND o TRIF SICA tres fases L1 L2 L3 y un neutro N con conexi n a tierra GND y con interruptor manual El no cumplimiento de estas...

Page 4: ...ondicionado as como fugas de agua descargas el ctricas e incendios Monte el aire acondicionado en un lugar que sea lo suficientemente resistente para soportar su peso Si la base no est bien asegurada...

Page 5: ...cobre Elija y compre tubos de cobre que correspondan a la longitud y tama o calculados para el modelo seleccionado en el manual de instalaci n de la unidad exterior y a los requisitos reales de su pro...

Page 6: ...es y requisitos del usuario para instalar la unidad de aire acondicionado Bien ventilado Flujo de aire sin obstrucciones Debe ser lo suficientemente fuerte para soportar el peso de la unidad El techo...

Page 7: ...aci n de orejas de suspensi n Arandela abajo Figura 3 4 Techo Tuerca abajo Figura 3 5 Figura 3 6 Precauci n Todos los pernos deben estar hechos de acero al carbono de alta calidad con superficie galva...

Page 8: ...L 243 933 L 34 139 250 394 638 391 128 36 49 338 W 88 299 47 1151 171 1322 4 12 25 9 52 OD 15 9 OD Caja de control el ctrico Brida de impulsi n de aire Tama o de impulsi n de aire Brida de impulsi n...

Page 9: ...rante lado Tuber a de refrigerante lado l quido Caja de control el ctrico Posiciones de los pernos 4 12 25 Brida de retorno de aire Brida de entrada de aire de retorno Agujero de conexi n para el cond...

Page 10: ...680 905 905 750 500 590 316 Unidad mm Aire de retorno Impulsi n de aire Caja de control el ctrico Tuber a de refrigerante lado gas Tuber a de refrigerante lado gas Posiciones de los pernos 4 12 25 Bri...

Page 11: ...es o cuatro veces antes de apretar vea Fig 4 3 Aplique aceite refrigerante Precauciones a tomar al soldar las tuber as de refrigerante Antes de soldar los tubos de refrigerante llene primero los tubos...

Page 12: ...la prueba aseg rese de que la tuber a de condensados no tenga pliegos ni pinzamientos y verifique que cada conexi n est sellada correctamente Realice la prueba antes de pavimentar el techo Figura 5 1...

Page 13: ...cepto para el aire acondicionado Figura 6 1 6 2 Rendimiento del ventilador Precauci n Una vez que el cuerpo del acondicionador de aire y las superior se debe asegura con tornillos Los tornillos M6 x 1...

Page 14: ...ustar el valor del par metro la tabla siguiente proporciona las presiones est ticas correspondientes de los valores Memorizar los par metros con la tecla OK y finalizar los ajustes de par metros 4 Pul...

Page 15: ...y conecte firmemente el cable de alimentaci n Para evitar que el cable se extraiga por una fuerza externa aseg rese de que est bien sujeto Si no se puede utilizar terminales de cable circular con el...

Page 16: ...n del cableado el ctrico Una vez realizado el cableado y las conexiones utilice correas de sujeci n para asegurar el cableado correctamente de modo que la uni n de conexi n no pueda separarse por la...

Page 17: ...s unidades que tienen la misma direcci n pueden funcionar mal SW2 Presi n est tica externa 1 ESP1 Presi n est tica externa 2 ESP2 Presi n est tica externa 3 ESP3 Presi n est tica externa 4 ESP4 Posici...

Page 18: ...as de refrigerante 4 La descarga de agua de condensados es fluida 5 El aislamiento es completo 6 La l nea de tierra ha sido conectada correctamente 7 Se han registrado la longitud de la tuber a y la...

Page 19: ...dad No coloque jarrones u otros recipientes para l quidos sobre la unidad ni en lugares donde pueda gotear l quido sobre ella El agua u otros l quidos que entren en contacto con la unidad pueden provo...

Page 20: ...un funcionamiento m s eficiente 1 Desmonte el filtro de aire Consulte la Figura 13 1 2 Limpie el filtro de aire El polvo se acumular en el filtro junto con la operaci n de la unidad y necesitar ser r...

Page 21: ...espu s de un largo per odo de inactividad a Revise y retire todo lo que pueda estar bloqueando las rejillas de entrada y salida de las unidades interiores y exteriores b Limpie la carcasa de la unidad...

Page 22: ...aci n Los compresores de la unidad exterior no funcionan correctamente La tensi n de alimentaci n es demasiado alta o demasiado baja Hay una obstrucci n en el sistema de tuber as Bajo efecto en refrig...

Page 23: ...locidad del ventilador se puede seleccionar durante COOL ONLY FAN y HEAT La se al del mando a distancia no se transmite aunque se pulse el bot n ON OFF Se ha producido un corte en el suministro el ctr...

Page 24: ...iado largo PCB principal da ada Error del sensor de temperatura ambiente T1 E2 El sensor de temperatura no est conectado correctamente o falla PCB principal da ada Error del sensor de temperatura del...

Page 25: ...a professional according RD 795 2010 RD 1027 2007 and RD 238 2013 The power supply must be SINGLE PHASE one phase L and one neutral N with his grounded power GND switch Any breach of these specificati...

Page 26: ...he water discharge is smooth and the piping is properly insulated to prevent condensation Improper installation of the water discharge piping may lead to water leakage and damage the indoor furniture...

Page 27: ...connect indoor refrigerant piping Use to discharge condensed water from the indoor unit To purchase based on actual project requirements To purchase based on actual project requirements Note Protect p...

Page 28: ...lowing conditions and user requirements to install the air conditioning unit 2 2 Install with M10 or W3 8 lifting bolts 2 3 The space required for installation unit mm is shown in Figure 2 1 and Figur...

Page 29: ...asher bottom Ceiling Figure 3 6 Make sure the connections are tight Spirit Level Z galvanized surface or other rust prevention treatment or stainless steel Z building For specific measures please cons...

Page 30: ...nlet Size of Air Outlet Refrigerant piping gas side Refrigerant piping liquid side Connect to water piping Position of lifting bolt Return Air Inlet Flange Return Air Inlet Flange Connection hole Elec...

Page 31: ...as side Refrigerant piping liquid side Connect to water piping Return Air Inlet Flange Air Outlet Flange Return Air Inlet Air Outlet Positions of 4 12 25 lifting bolts Electric control box assembly Co...

Page 32: ...et Flange Repair hole Electric control box assembly Return Air Inlet Air Outlet Refrigerant piping gas side Refrigerant piping liquid side Positions of 4 12 25 lifting bolts 1937 1905 1940 2010 990 16...

Page 33: ...ace of the heat insulation material may be exposed Before the works are carried out verify that the refrigerant is R410A If the wrong refrigerant is used the unit may malfunction Other than the specif...

Page 34: ...charge piping accessory to bind them firmly to make sure air does not enter and condense 4 In order to prevent the back flow of water into the interior of the air conditioner when the operation stops...

Page 35: ...rn and air outlet ducts to prevent vibrations from the indoor unit transferring to the ceiling 4 Use heat insulation materials at a thickness of 25 mm or more to prevent condensation on the air duct 5...

Page 36: ...el to return to the previous layer until exiting the parameter settings or exit the parameter settings when there 5 On the parameter settings interface the wired controller does not respond to the rem...

Page 37: ...in the network are interconnected and will eventually connect to earth at the same point Do not bind the refrigerant piping power cords and communication wiring together When the power cord and commu...

Page 38: ...ail 1 Main Board SW5 SW4 SW3 SW2 SW1 ENC1 SW6 SW7 Figure 7 8 Master wired controller Slave wired controller X1 X2 Indoor unit 1 Wired Controller 2 X1 X2 D1 D2 Wired Controller 1 X2 X1 D1 D2 Indoor uni...

Page 39: ...sation is 6 C Heating mode temperature compensation is 0 C use follow me function SW2 Note The capacity DIP switches have been configured before delivery Only a professional maintenance personnel shou...

Page 40: ...vibration and strange sounds during operation 2 If the wind noise and condensation affect the neighbours 3 Any refrigerant leakage 9 1 Things to Note Before Test Run 9 2 Test Run Once the power is con...

Page 41: ...d out Y can lead to electric shocks Z Y Z Z to avoid injury or damage to the equipment Z Z Z liquid could drip onto it Water or other liquids that come into contact with the unit can lead to electric...

Page 42: ...er air falls the distribution of warmed cooled air around a room can be improved by positioning the unit s louvers The louver angle can be adjusted by pressing the SWING button on the remote controlle...

Page 43: ...itted from the unit This can occur when the unit first runs after a long idle period Symptom 5 The unit gives off a strange odor If smells such as those of strong smelling food or tobacco smoke are pr...

Page 44: ...k has occurred Low heating effect Doors or windows are not completely closed Close doors and windows Arrange for a professional technician to check the following A refrigerant leak has occurred 15 2 U...

Page 45: ...goes off after a certain time No receiving soundfrom the indoor unit when the ON OFF button is pressed Check whether the MODE indicated on the display is AUTO Check whether the MODE indicated on the d...

Page 46: ...Power supply abnormal EEPROM mismatch E7 Damaged main PCB EEV error Eb Line loosened or broken The electronic expansion valve in stuck Outdoor unit error Ed Outdoor unit error Water level error EE Wat...

Page 47: ......

Page 48: ...www mundoclima com SAT 34 93 652 53 57 C N POLES 249 P1 ESPA A SPAIN 34 93 446 27 80 08013 BARCELONA...

Reviews: