5.   ELECTRIC WIRING 

5.2 Power supply specification 

Table 5-1 

Outdoor power supply 

Power 
supply 

Manual  
 switch 

Fuse 

Wiring 

Item 

Model 

380-415V 
3N~50Hz 

100A 

 70A 

16mm

(<20m) 

 

 MUEN-65-H6T

5.3.1 No additional control components are required in the 
electric cabinet (such as relay, and so on), and the power supply 
and control wires not connected with the electric cabinet are not 
allowed to go through the electric box. Otherwise, electromag-
netic interference may cause failure of the unit and control 
components and even damages to them, which thus lead to 
protective failure.  
5.3.2 All cables led to the electric box should be supported 
independently but by the electric box.  
5.3.3 The strong current wires generally pass the electric box, 
and 220-240V alternating current may also pass the control 
board, so wiring connection should conform to the principle of 
separation of strong current and weak current, and the wires of 
power supply should be kept more than 100 mm away from the 
control wires.  
5.3.4 Only use 380-415V 3N~50Hz rated power supply for the 
unit, and the maximum allowable range of voltage is 342V~456V.  
5.3.5 All electric wires must conform to local wiring connection 
norm. The suitable cables should be connected to power supply 
terminal through wiring connection holes at the bottom of the 
electric cabinet. According to Chinese standard, the user is 
responsible for providing voltage and current protection for the 
input power supply of the unit.  

5.3 Requirements of wiring connection 

5.3.6 All power supplies connected to the unit must pass one 
manual switch, to ensure that the voltages on all nodes of 
electric circuit of the unit are released when the switch is cut off.  
5.3.7 The cables of correct specification must be used to supply 
power for the unit. The unit should use independent power 
supply, and the unit is not allowed to use the same power supply 
together with other electric devices, to avoid over-load danger. 
The fuse or manual switch of the power supply should be 
compatible with working voltage and current of the unit. In case 
of parallel connection of multiple modules, the requirements of 
wiring connection mode and configuration parameters for the 
unit are shown in the following figure.  
5.3.8 Some connection ports in the electric box are switch 
signals, for which the user needs to provide power, and the rated 
voltage of the power should be 220-240VAC. The user must be 
aware that all power supplies they provided should be obtained 
through power circuit breakers (provided by the user), to ensure 
that all voltages on the nodes of the provided power supply 
circuit are released when the circuit breakers are cut off.  
5.3.9 All inductive components provided by the user (such as 
coils of contactor, relay, and so on) must be suppressed with 
standard resistance-capacitance suppressors, to avoid 
electromagnetic interference, thus leading to failure of the unit 
and its controller and even damages to them.  
5.3.10 All weak current wires led to the electric box must apply 
shielded wires, which must be provided with grounding wires. 
The shield wires and power supply wires should be laid 
separately, to avoid electromagnetic interference.  
5.3.11 The unit must be provided with grounding wires, which 
are not allowed to be connected with the grounding wires of gas 
fuel pipelines, water pipelines, lightning conductors or 
telephones. Improper earth connection may cause electric 
shock, so please check whether earth connection of the unit is 
firm or not frequently.  

Outdoor  
  unit 1 

Outdoor  
  unit 2 

Outdoor  
  unit 3 

Outdoor  
  unit 4 

Outdoor  
  unit N 

Manual switch 

Manual switch 

Manual switch 

Manual switch 

Manual switch 

Only 16 modular units can be combined at most.  

NOTE 

5.4 Wiring steps 

Step 1. Check the unit and ensure that it is connected with 
grounding wires correctly, to avoid leakage, and the grounding 
devices should be mounted in strict accordance with the 
requirements of electrical engineering rules. The grounding 
wires can prevent electric shock.  
Step 2. The control box of the main power switch must be 
mounted in a proper position. 
Step 3. Wiring connection holes of the main power should be 
provided with glue cushion.  
Step 4. The main power and neutral wires and grounding 
wires of power supply are led into the electric box of the unit.   
 

Fig. 5-1 

5.1 Electric wiring 

1. The air-conditioner should apply special power supply, whose 
voltage should conform to rated voltage. 
2. Wiring construction must be conducted by the professional 
technicians according to the labeling on the circuit diagram.
3. The power wire and the grounding wire must be connected 
the suitable terminals.
4. The power wire and the grounding wire must be fasten up by 
suitable tools. 
5. The terminals connected the power wire and the grounding 
wire must be fully fastened and  regularly checked, in case to 
become flexible.  
6. Only use the electric components specified by our company, 
and require installation and technical services from the 
manufacturer or authorized dealer. If wiring connection fails to 
conform to electric installation norm, failure of the controller, 
electronic shock, and so on may be caused. 
7. The connected fixed wires must be equipped with full 
switching-off devices with at least 3mm contact separation. 
8. Set leakage protective devices according to the requirements 
of national technical standard about electric equipment.
9. After completing all wiring construction, conduct careful check 
before connecting the power supply. 
10. Please carefully read the labels on the electric cabinet. 
11. The user’s attempt to repair the controller is prohibited, since 
improper repair may cause electric shock, damages to the 
controller, and so on. If the user has any requirement of repair, 
please contact the maintenance center.

CAUTION 

  

Installation & owner's manual

11

Modular Chiller MUEN-H6

Summary of Contents for MUEN-65-H6T

Page 1: ...MODULAR CHILLER MUEN H6 English CL25617 MUEN 65 H6T Installation Owner s manual www mundoclima com ...

Page 2: ...ontrol box Water inlet MAIN PARTS OF THE UNIT Temperature testing compo nents of total water outlet Purpose Shape Qty Unit Wire control assembly ACCESSORIES Installation Operation Manual Use for installation only need for setting the main module Installation manual of wire controller AUXILIARY 1 1 1 1 ...

Page 3: ...atically conduct energy control according to the magnitude of load to achieve optimal matching and thus actually realizing optimal energy saving operation The product is modularized unit and parallel connection of 16 modules can be realized at most so the user can adopt module combination according his own demands The product can be widely applied in air conditioning engineering of various newly b...

Page 4: ...g injuries Never inspect or service the unit by yourself Ask a qualified service person to perform this work Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary Keep far away from high frequency equipment Keep away from the following places a place where it is full of oil gas places where salty air surrounding near the coas...

Page 5: ... health of those who are hypersensitive to chemicals Do not place appliances which produce open fire in places exposed to the air flow from the unit or under the indoor unit It may cause incomplete combuston or deformation of the unit due to the heat Do not install the air conditioner at any place where flammable gas may leak out If the gas leaks out and stays around the air conditioner a fire may...

Page 6: ...oid affecting the people due to transfer of noise and vibration The base of the unit is provided with installation holes which can be used to connect the unit and the foundation firmly 3 1 7 In case of installation on the roof the roof must possess enough strength to sustain weight of the unit and maintenance personnel The unit can be supported on concrete foundations or channel steel frames simil...

Page 7: ...nd the space between adjacent modular units should not be less than 300mm the installation can also follow the direction B and C as shown in Fig 3 2 the spaces between the unit and the obstacle are given in Table 3 1 and the space between adjacent modular units should not be less than 600mm the installation can also follow the direction combina tion of A and D and B and C the spaces between the un...

Page 8: ...mance of the unit will decline c The inlet pipe of the evaporator must be provided with a target flow controller to realize flow break protection for the unit Both ends of the target flow controller must be supplied with horizontal straight pipe sections whose diameter is 5 times that of the inlet pipe The target flow controller must be installed in strict accordance with Installation Regulation G...

Page 9: ...in winter For the water pipeline network including filters and heat exchangers dreg or dirt may seriously damages the heat exchangers and water pipes The installation persons or the users must ensure the quality of chilled water and de icing salt mixtures and air should be excluded from the water system since they may oxidize and corrode steel parts inside the heat exchanger o The common outlet pi...

Page 10: ...ater flow in terms of multi connect the units that water flow must no less than total units rated water flow b Select the left of the pump H h1 h2 h3 h4 H The lift of the pump h1 Main unit water resistance h2 Pump water resistance h3 Water resistance of the longest water loop distance includes pipe resistance different valve s resistance flexible pipe resistance pipe elbow and three way resistance...

Page 11: ... adjustment is done c When wiring connection is conducted adjustment of other screws except connection terminals of micro switches and ground screws is prohibited In the meanwhile over great force should not applied when wires of micro switches are connected otherwise micro switches may suffer displacement thus leading to failure of flow switches Fig 4 3 Fig 4 4 4 10 Installation of single module ...

Page 12: ...No n module No n 1 address No 1 module No n 1 module No n 2 address No 0 address Water flow switch Pump Fig 4 6 less than 6 modules b Installation mode II recommended installation mode No n module No n 1 address No 1 module No n 1 module No n 2 address No 0 address Pump Fig 4 7 installation mode A less than 16 modules Water flow switch Drill dead hole at the position and move the total effluent te...

Page 13: ...ensing bulb target flow controller and auxiliary electric heater are under control of the main module One wired controller and one target flow controller are required and connected on the main module The unit can be started up through the wired controller only after all addresses are set and the aforementioned items are determined The wired controller is 500m away from the outdoor unit ŏ4ŏ ψ4ŏ ψ4ŏ...

Page 14: ...apacitance suppressors to avoid electromagnetic interference thus leading to failure of the unit and its controller and even damages to them 5 3 10 All weak current wires led to the electric box must apply shielded wires which must be provided with grounding wires The shield wires and power supply wires should be laid separately to avoid electromagnetic interference 5 3 11 The unit must be provide...

Page 15: ...it as shown in Fig 5 2 Step 11 Connection of control wires of pump the control wires of AC contactor of pump must pass the connection terminals p1 and P2 of the main unit as shown in Fig 5 3 Step 12 The connection way of the wire controller connects with every signal wires from package units signal wires P Q E are connected in the same way of main wires connection method and accordingly connect to...

Page 16: ... and OFF Total outlet water temperature sensor fault code E3 Only the main unit is valid and the subordinate units are invalid Under refrigerating mode and heating mode conduct adjustment according to the magnitude of total outlet watertemperature Adjustment range Load stabilize unload Emergency Stop 7 8 No Table 5 2 Detection of current of the compressor B1 protection code P5 Current is not detec...

Page 17: ... pressure protection of the system A and discharge temperature switch protection protection code P0 high pressure protection of the system B and discharge temperature switch protection protection code P2 low pressure protection of the system A protection code P1 low pressure protection of the system B protection code P3 Constant speed compressor connection of discharge temperature switch and high ...

Page 18: ... or protection code is displayed Four way valve of the system B Neutral wire Four way valve of the system A Neutral wire Outdoor fan A controlled by T4 Outdoor fan B controlled by T4 PWM pressure relif valve control for digital compressor Input of three phase four wire power supply fault code E1 Three phases A B and C of power supply should exist simultaneously and the difference of phase angle sh...

Page 19: ...Check item table after installation Checking item Description Yes No Whether installing site is meet for requirements Whether water system is meeting for requirements Whether electric wiring system is meeting for requirements Units are fixed mounting on level base Ventilating space for heat exchanger at the air side is meeting for requirement Maintenance space is meeting for requirement Noise and ...

Page 20: ...ty Do not re start the unit within 10 min after the unit is shut down during trial run When the unit is used frequently do not cut off the power supply after the unit is shut down otherwise the compressor cannot be heated thus leading to its damages If the unit is not in service for a long time and the power supply needs to be cut off the unit should be connected to the power supply 12 hours prior...

Page 21: ...oller the check sequence is as follows ON OFF key On and Off functions Right Left key Under main page to press this key can query the setting water temperature setting timing etc during timing setting press the right key then shift to the next step setting during spot check they are used to turn over the unit parameter information OK key After setting the parameter then press this key to confirm A...

Page 22: ...nate incrustant Check water temperature See Excessive high air suction pressure Check chilling water temperature Refrigerant leakage or insufficient refrigerant volume Test leakage or charge sufficient refrigerant to the system See Excessive low air suction pressure Check ambient temperature around it Discharge the excessive refrigerant Charge sufficient refrigerant to the system Check fan rotatin...

Page 23: ...pressor Replace damaged assembly Control circuit without power though Check the wring of control system Hi voltage or lo voltage protection Reference to mention in above the parts of air suction and discharge pressure error Replace damaged assembly Find out the error type and carry out the corresponding measure to settle Check the running state Replace a new one if necessary Settle the short circu...

Page 24: ...on 0 F indicating protection code P is displayed when there is no failure e Unit number display It is used for displaying the address number of the currently selected modular unit with display scope 0 15 and indication point is on at the same time 21 Modular Chiller MUEN H6 E0 E1 E2 E3 E4 E5 E6 E7 E8 E9 EA Eb EC Ed EF P0 P1 P2 P3 P4 P5 No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23...

Page 25: ...sor IB Outdoor pipe temperatureT3A Outdoor ambient temperatures T4 Outdoor pipe temperatureT3B 6 7 8 9 10 11 Anti frozen temperature T6 Electronic expansion valv opening FA 12 Last third error or protection Outlet water temperature Tou Last one error or protection Electronic expansion valv opening FB Last second error or protection 13 1 8 5 Care and maintenance Maintenance period It s recommended ...

Page 26: ... connect the ON OFF port of the main unit s electric control box then connect the ON OFF signal provide by user to the ON OFF port of main unit as follows If the ON OFF port is effective the Net on icon of the wire controller will be flashing First corresponding parallel connect the HEAT COOL port of the main unit s electric control box then connect the ON OFF signal provide by user to the HEAT CO...

Page 27: ...n 5 Check temperature of chilled water or hot water Inlet Outlet 6 check air temperature of air side heat exchanger Inlet Outlet 7 Check refrigerant suction temperature and superheating temperature Refrigerant suction temperature Superheating temperature 8 Check pressure Discharge pressure Suction pressure 9 Check running current 10 Whether unit has been through refrigerant leakage test 11 Whether...

Page 28: ...Shutdown Outdoor temperature Compressor Air temperature of air side heat exchanger Temperature of chilled water or hot water Current of cooling water pump or hot water pump Dry bulb Wet bulb Indoor temperature High pressure Low pressure Voltage Current Inlet dry bulb Outlet dry bulb Inlet Outlet Note 25 Modular Chiller MUEN H6 ...

Page 29: ...in coil model Shell tube type heat exchanger Control of wired controller manual auto startup running state display failure alert etc High or low pressure switch freeze proof device water flow volume controller Overcurrent device power phase sequence device etc Table 9 1 9 APPLICABLE MODELS AND MAIN PARAMETERS Standard heating input kW Heating rated current 36 5 Notes the above data is measured bas...

Page 30: ...e wiring diagram of auxiliary heater and pump is just for reference please follow the instructions of corresponding auxiliary heater products Please choose such accessory as power wire switch of auxiliary heater according to the actual parameter of products and national Standards 3 3 3 3 3 3 3RZHU 1Њ 3RZHU 1Њ 3RZHU 1Њ 3RZHU 1Њ ...

Page 31: ... 4 16 11 15 5 6 7 8 9 10 11 12 1 Operation icon 2 Mode area 3 Setting temperature 4 Timing On Off 5 Function Icon 6 On line Unit Qty Indication 7 Reserved 8 Clock 9 Water temp 10 ON OFF Key 11 Right Left Right Key 12 OK key 13 Setting key 14 Add Reduce key 15 Cancel key 16 Reserved key Press for 3sec to cancel timer Press for 3sec to unlock AUXILIARY 1 2 3 4 5 Operation icon Indicate the ON and OF...

Page 32: ...r 7 seconds then the setting to be effective and the LCD will display the effective timing information as the following display This time the hour of the clock will flash it means the current setting is the hour of Timer 1 Off press the or to adjust press key when finished and then the minute of the clock will flash it means the current setting is the minute of Timing 1 Off press the or to adjust ...

Page 33: ...tings and return to the main page During setup press the Cancel key does not save the parameters and exit The factory default δ 2 C Simultane ously press Press for 3sec to cancel timer Press for 3sec to unlock AUXILIARY 2 ADDRESS setting function The address of wire controller can be set by pressing this button The address range 0 15 therefore 16 wire controller could be parallel at most Operation...

Page 34: ...ric control box Please purchase the 3 Core Shield Cable of 0 5mm2 x3 by the customer during installation Black Yellow Grey Communicate with upper unit if there is no upper unit it is no need to be wired E X Y P Q A B P Q E P P Q E Q E 3 core shielding wire 3 core shielding wire E AC22OV Screw Front cover Control panel 3 Wiring figure 1 During installation make sure correctly wiring the 5 wiring te...

Page 35: ...ole x o b n a i c i r t c e l E 6 8 Diameter Φ8 Φ10 Wall hole and wiring hole Putty Trap Putty Trap Putty Trap Avoid the water enter into the wired remote controller use trap and putty to seal the connectors of wires during wiring installation Fig 5 2 6 Front cover installation Fig 6 2 Fig 6 1 After adjusting the front cover and then buckle the front cover avoid clamping the communication switchin...

Page 36: ... ASK FOR MORE INFORMATION Phone 34 93 446 27 81 eMail info mundoclima com TECHNICAL ASSISTANCE Phone 34 93 652 53 57 www mundoclima com ...

Reviews: