11. P5 malfunction
When condenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe
temp. less than 52°C.
P5 display
High temperature protection of
condenser
Check whether the
condenser temperature is
more than 65°C
Yes
Judge 1: Check whether the
outdoor ambient
temperature is higher than
50
℃
No
Judge 3: The refrigerant
pipe is blocked
Let the refrigerant out, then use the high
pressure nitrogen or refrigerant to blow pipe,
vacuumize and charge the refrigerant again
Yes
Judge 2: Check whether the
heat exchanger is dirty
No
Clean the heat exchanger
Yes
Replace outdoor main board
Yes
Check whether the
resistance of condenser
temp. sensor is correct
refer to the
Appendix
1
Replace the temperature sensor
Stop the unit
Yes
No
No
No
Service manual
Inverter HF
77
Summary of Contents for MUCR-HF
Page 5: ...Part 2 Indoor Units Super Slim Cassette Type 6 Duct Type 20 Service manual Inverter HF 5 ...
Page 11: ...2 Dimensions Model A H MUCSR 48 HF 287 317 287 317 MUCSR 60 HF Service manual Inverter HF 11 ...
Page 12: ...3 Service Space 1000mm 1000mm 1000mm 1000mm Service manual Inverter HF 12 ...
Page 13: ...4 Wiring Diagrams MUCSR 48 HF UI20605 MUCSR 60 HF UI20606 Service manual Inverter HF 13 ...
Page 26: ...4 Wiring Diagrams MUCR 48 HF UI20601 MUCR 60 HF UI20602 Service manual Inverter HF 26 ...
Page 64: ... Part 5 1 Troubleshooting 65 Troubleshooting Service manual Inverter HF 64 ...
Page 69: ...3 E3 malfunction Service manual Inverter HF 69 ...
Page 70: ...4 E4 malfunction NOTA Revisar todas las sondas Service manual Inverter HF 70 ...
Page 73: ...7 P1 malfunction Service manual Inverter HF 73 ...
Page 74: ...8 P2 malfunction Service manual Inverter HF 74 ...
Page 75: ...9 P3 malfunction Service manual Inverter HF 75 ...