Indoor
unit
More than 50mm
More than 25mm
Plug
Water storage pipe
5.2.7 Lifting pipe setting of indoor unit with water pump
The length of lifting pipe should not exceed the pump head of indoor unit water pump.
Pump head of big four way cassette: 750mm
Pump head of compact four way cassette: 500mm
The drainage pipe should be set down inclined after the lifting pipe immediately to avoid wrong
operation of water level switch.
Refer the following picture for installation reference.
Flexible pipe 300mm
Hanger
A
A:Length of horizontal pipe
≤
150mm
B: Lift height
≤
the pump head of water pump
Down incline pipe
B
5.2.8 Blowhole setting
For the concentrated drainage pipe system, there should design a blowhole at the highest point of main
pipe to ensure the condensate water discharge smoothly.
The air outlet shall face down to prevent dirt entering pipe.
Each indoor unit of the system should be installed it.
The installation should be considering the convenience for future cleaning.
Blowhole
Plug
Indoor unit
Plug
Indoor unit
5.2.9 The end of drainage pipe shall not contact with ground directly.
Service manual
Inverter HF
57
Summary of Contents for MUCR-HF
Page 5: ...Part 2 Indoor Units Super Slim Cassette Type 6 Duct Type 20 Service manual Inverter HF 5 ...
Page 11: ...2 Dimensions Model A H MUCSR 48 HF 287 317 287 317 MUCSR 60 HF Service manual Inverter HF 11 ...
Page 12: ...3 Service Space 1000mm 1000mm 1000mm 1000mm Service manual Inverter HF 12 ...
Page 13: ...4 Wiring Diagrams MUCSR 48 HF UI20605 MUCSR 60 HF UI20606 Service manual Inverter HF 13 ...
Page 26: ...4 Wiring Diagrams MUCR 48 HF UI20601 MUCR 60 HF UI20602 Service manual Inverter HF 26 ...
Page 64: ... Part 5 1 Troubleshooting 65 Troubleshooting Service manual Inverter HF 64 ...
Page 69: ...3 E3 malfunction Service manual Inverter HF 69 ...
Page 70: ...4 E4 malfunction NOTA Revisar todas las sondas Service manual Inverter HF 70 ...
Page 73: ...7 P1 malfunction Service manual Inverter HF 73 ...
Page 74: ...8 P2 malfunction Service manual Inverter HF 74 ...
Page 75: ...9 P3 malfunction Service manual Inverter HF 75 ...