background image

MT56DSU2 Owner’s Manual

82017502

19

Chapter 4 - Troubleshooting

4.1  Introduction

All of the indicators used in normal operation of the MultiDSU56K are on the front panel. Each
front panel LED is labeled, as explained below. The LEDs provide status and maintenance
information on the MultiDSU56K, as well as the attached network and line. There are no front
panel switches on the MultiDSU56K; refer to Chapter 2 of this manual for option configuration DIP
switch settings.

4.2  LED Indicators

The front panel contains twelve LEDs each with a two- or three-letter overlay, and a one-word
legend below the LED describing its meaning. During normal operation the LEDs light (flash or
continuously lit) to indicate a defined condition. During test mode, the LEDs light during Test
Pattern test execution (refer to the Test Pattern section later in this chapter).

The front panel LEDs are shown below.

NS

DOS

RTS

CTS

Send

Rcv

Carrier

56K

19.2K

9600

4800

Clear Request NoSgnl Outage

Test

MultiDSU56K

RD

CD

SD

96

48

19.2

56

TM

Multi-Rate DSU/CSU

Figure 4-1.   MultiDSU56K Front Panel

4.2.1  SD Indicator

The SD (Transmit) LED lights to indicate the DTE is sending data (0 or a space) across the DTE
connector.

The SD LED should appear to flash during normal data transmission.

4.2.2  RD Indicator

The RD (Receive) LED lights when the MultiDSU56K receives data (a 0 or a space) from the
network.

The RD LED should appear to flash during normal data reception.

4.2.3  CD Indicator

The CD (Carrier Detect) LED lights when the MultiDSU56K has received the data carrier from the
network. This indicator will go off when the MultiDSU56K is receiving the idle code or no signal at
all. If RTS is off on the remote DSU, the remote DSU sends an idle code to the local DSU.

4.2.4  56K Indicator

The 56K LED lights when the “Data Rate” selection is set at 56000 bps. This indicator will be off
for all other data rates. Refer to Chapter 2 for switch settings.

4.2.5  19.2 Indicator

The 19.2 LED lights when the “Data Rate” selection is set at 19200 bps. This indicator will be off
for all other data rates. Refer to Chapter 2 for switch settings.

Summary of Contents for MT56DSU2

Page 1: ...MT56DSU2 Owner s Manual 82017502 1 MultiDSU56K Model MT56DSU2 Owner s Manual...

Page 2: ...right to revise this publication and to make changes from time to time in the content hereof without obligation of Multi Tech Systems Inc to notify any person or organization of such revisions or cha...

Page 3: ...11 Normal Diagnostics 16 3 3 LED Indicators 16 3 4 Functions 17 3 4 1 LADS Applications 17 3 4 2 Off Net Extension Applications 17 CHAPTER 4 TROUBLESHOOTING 4 1 Introduction 18 4 2 LED Indicators 18...

Page 4: ...e Warranty and Tech Support defines procedures to follow if the troubleshooting steps in Chapter 4 do not fix the problem Appendix A Applications Examples illustrates several DSU CSU uses that may hel...

Page 5: ...transmit data at 56000 19200 9600 4800 and 2400 bps in multi point and point to point applications The MultiDSU56K contains the functions of a Data Service Unit DSU and a Channel Service Unit CSU in...

Page 6: ...ts direct connection to the DATAPHONE Digital Data Service DDS or compatible network selectable sync speeds of 2400 4800 9600 19200 and 56000 bps selectable async speeds of 2400 4800 9600 and 19200 bp...

Page 7: ...customer as soon as possible Also you will be advised of your right to file a complaint with the FCC if you believe it is necessary 5 The telephone company may make changes in its facilities equipmen...

Page 8: ...ormer 2 7 Lbs 1 2 Kg with power transformer Certification FCC Part 15 Class A FCC Part 68 UL Listed Compatibility AT T Pubs 62310 and 41450 FIC Codes 04DU5 24 2 4 Kbps digital interface 04DU5 48 4 8 K...

Page 9: ...MT56DSU2 Owner s Manual 82017502 9 Delay Times in secs RTS CTS DCD on DCD off 2400 8 1 7 5 7 0 4800 4 3 2 6 3 5 9600 2 2 1 6 1 5 19200 1 0 0 8 0 7 56000 0 4 0 3 0 2...

Page 10: ...may be a remote risk of electrical shock from lightning 7 Do not use the telephone to report a gas leak in the vicinity of the leak 8 To reduce the risk of fire use only No 26 AWG or larger Telecommu...

Page 11: ...section 2 3 2 2 2 4 Position DIP Switch 13 16 The 4 position DIP switch is used to select Async Word Length Elastic Store and Anti Streaming options The defaults are 10 Bit Async Word Length Elastic S...

Page 12: ...MT56DSU2 Owner s Manual 82017502 12 An adhesive backed label containing the DIP switch setting information is provided on the bottom of the MultiDSU56K a sample label is shown below for reference...

Page 13: ...on 8 Up Synchronous operation Down Asynchronous operation Normal Loopback Test Mode 9 Up Normal operation Down Loopback Test Normal Test Pattern 10 Up Normal Down Test Pattern Circuit Assurance Enable...

Page 14: ...interface connector depending on the DTE Connect the RS232C connector to the 25 pin DB25S receptacle Use the two screws to secure the connection or Connect the 34 position rectangular V 35 connector t...

Page 15: ...a transmission rate The data rate selected here must match the DDS or other 4 wire network line rate that you subscribed for with your telco The default for this function is a data rate of 56K bps Ref...

Page 16: ...eting momentary line interruptions as a communications channel failure Refer to Chapter 2 for changing the default DIP switch settings 3 2 6 Circuit Assurance This option when enabled causes the Multi...

Page 17: ...the DTE The default for this function is a 10 bit async word 1 start 8 data no parity 1 stop bit length Refer to Chapter 2 for changing the default DIP switch settings 3 2 11 Normal Diagnostics The d...

Page 18: ...an extension of the circuit for a special application In applications using the MuI1iDSU56K for an off net extension one Mu1tiDSU56K may be set for External Timing and the other set for DDS Timing ho...

Page 19: ...quest NoSgnl Outage Test MultiDSU56K RD CD SD 96 48 19 2 56 TM Multi Rate DSU CSU Figure 4 1 MultiDSU56K Front Panel 4 2 1 SD Indicator The SD Transmit LED lights to indicate the DTE is sending data 0...

Page 20: ...tion exists This occurs when there is a failure in the digital service detected by the network and the telco sends a repetitive OOS sequence If this indicator is on check the remote DSU for proper ins...

Page 21: ...ERT Tester MultiDSU56K In Local Loopback Test Mode 4 3 2 Digital Loopback Test This test allows you to test the local DTE the local MultiDSU56K the communications link and the remote MultiDSU56K Use t...

Page 22: ...ern Generator Test Pattern Detector No Signal NS LED Local MultiDSU56K In Test Pattern Mode Remote MultiDSU56K In Digital Loopback Mode 4 3 4 Test Pattern Test This test allows you to test the local M...

Page 23: ...ble description 1 Obtain a DSU Loopback cable 45640100 from Multi Tech or assemble one Refer to Appendix B for instructions on building the Loopback cable 2 Plug the Loopback cable into the back panel...

Page 24: ...from Multi Tech or assemble one Refer to Appendix B for instructions on building the Back to Back cable 2 Plug the cable into each DSU s LINE jack 3 On the good DSU set DIP switch 9 to the down positi...

Page 25: ...register Tech Support Multi Tech has an excellent staff of technical support personnel available to help you get the most out of your Multi Tech product If you have any questions about the operation...

Page 26: ...6 If you need to inquire about the status of the returned product be prepared to provide the serial number of the product sent Send DSUs to MULTI TECH SYSTEMS INC 2205 WOODALE DRIVE MOUNDS VIEW MINNES...

Page 27: ...l Area Data Set External Clocking application and Analog Off Net Extension application DDS POINT TO POINT APPLICATION In this application the MultiDSU56K provides the interface between the DDS line an...

Page 28: ...een a control station and two or more remote stations All data transmitted by the control station is sent to each remote station For data transmitted from the remote stations the MJUs combine bit stre...

Page 29: ...on wires Figure A 3 Local Area Data Set Application EXTERNAL CLOCKING APPLICATION This application is similar to the Local Area Data Set application except for the timing option setting In the example...

Page 30: ...DS circuits in an area where DDS is not available Site 3 in the example below or where the customer requires an extension of the DDS circuit for a special application Site 3 Analog Line Front End Proc...

Page 31: ...iewed from the rear DESCRIPTION This connector ties the MultiDSU56K to the DDS Network The RJ48 connector is keyed for proper insertion of a keyed RJ48 plug PIN IDENTIFICATION Pin Description Destinat...

Page 32: ...20 19 18 17 16 15 14 Transmitter Signal Element Timing As viewed from the rear DESCRIPTION This connector ties the MultiDSU56K to the DTE The DB25S connector has the following pinout configuration PI...

Page 33: ...ct Receive Data A Receive Data B Receive Timing A Receive Timing B As viewed from the connector side DESCRIPTION This connector ties the MultiDSU56K to the DTE The V 35 connector has the following pin...

Page 34: ...DSU for comparison to the original signal sent You can order this cable 45640100 from Multi Tech or build one using the instructions below Refer to Chapter 4 for test procedures SCHEMATIC RJ48S 1 2 3...

Page 35: ...instructions below Refer to Chapter 4 for test procedures SCHEMATIC RJ48S 1 2 3 4 5 6 7 8 7 RJ48S 8 7 6 5 4 3 2 1 BUILD INSTRUCTIONS 1 Strip cable installation 3 4 2 Strip wires 1 2 7 and 8 on one end...

Page 36: ...tal path on a cable on which data is transmitted A logical way to look at the path data travels when sent between locations circuit assurance an optional conditioning of the CTS signal Clear To Send C...

Page 37: ...DSR data set ready an RS232 signal that indicates the DCE and line are ready to receive data DSU Data Service Unit a device used to interface a user s DSU to a digital circuit such as DDS or Ti Used i...

Page 38: ...t directly connected with no intermediate nodes computers or branched circuits but possibly switching facilities A type of connection that links two and only two logical entities e g a phone line circ...

Page 39: ...02 39 T test pattern a diagnostic test for sending detecting and checking a pre defined pattern of bits two wire circuit A circuit in which one channel line is used for communications in both directio...

Reviews: