RANGE FOR CONTROL PARAMETER
ERROR
OPEN
SRE
MEANING
When an error has occurred the display indicates error codes
as given below.
Check the sensor and the input wiring. If problem still exists,
replace the sensor. And still if problem is not solved yet by the
user, then please contact company person
Sensor is not connected or
Over range condition or
sensor break
Sensor connection is reversed
ERROR DISPLAY
CORRECTIVE ACTION:
SOAK TIME FUNCTION
Soak feature can be use to hold the process at a preset
temperature for a preset time.
(Range : selectable up to 0 to 999 hour)
When soak time is completed, then display indicate
message as shown below.
2345
END
To restart process
press key for 3 sec.
MEMO
YES
/
NO
YES
: In case of power supply failure, remaining soak time
counting will be continued at next power on.
NO
: In case of power supply failure, soak time counting will
be restarted at next power on.
Soak time memory (
MEMO
)
END
SAVE
/
NO
In case of soak time end, if user apply
SAVE
in
configuration then soak time end (
END
) display will still
indicate after power supply failure. And that will only reset
by pressing key for 3 sec.
Soak time end (
END
)
PARAMETER
RANGE FOR J.1,K.1,PT.1
RANGE FOR J, K, R, S
PT-100
IT
CT
Ct2
Pb2
PB
0.0 to 999.9°C
0.0 to 999.9°C
0 to 9999
0 to 9999
0 to 9999
0 to 9999
4 to 99 sec
4 to 99 sec
1 to 100°C
0.1 to 100.0°C
0.1 to 100.0°C
1 to 100°C
1 to 20 sec
1 to 20 sec
2.0 to 25.0°C
2.0 to 25.0°C
5 to 200 sec
5 to 200 sec
0.0 to 99.59 (mm.ss)
0.0 to 99.59 (mm.ss)
0.0 to 99.59 (mm.ss)
0.0 to 99.59 (mm.ss)
0 to 999 sec
0 to 999
Unit As Per Soak Unit
Selected
0 to 999 sec
0 to 999
2 to 20°C
2 .0 to 20.0°C
4 to 99 sec
4 to 99 sec
-9.0 to 9.0°C
-9 to 9°C
-20.0 to +20.0°C
-20 to 20°C
DT
MR
OFFSET
HYS1
HYS2
C-PB
C-ON
C-OFF
R1DL
R2DL
ALTM
SKTM
Unit As Per Soak Unit
Selected
Page -4