page 28 — DCa40sskU/kU4i 60 hz generaTor • operaTion anD parTs manUal — rev. #1 (03/11/13)
inspeCtiOn/setup
CirCUiT Breakers
To protect the generator from an overload, a 3-pole, 100
amp, main circuit breaker is provided to protect the
U,v, and
W
output terminals
from overload. In addition two single-
pole, 20 amp
gFCi
circuit breakers are provided to protect
the GFCI receptacles from overload. Two 50 amp circuit
breakers have also been provided to protect the auxiliary
receptacles from overload. Make sure to switch
all
circuit
breakers to the
oFF
position prior to starting the engine.
lUBriCaTion oil
Fill the engine crankcase with lubricating oil through the
filler hole, but
Do noT
overfill. Make sure the generator is
level and verify that the oil level is maintained between the
two notches (Figure 28) on the dipstick. See Table 11 for
proper selection of engine oil.
Figure 28. Engine Oil Dipstick
When checking the engine oil, be sure to check if the oil
is clean. If the oil is not clean, drain the oil by removing
the oil drain plug, and refill with the specified amount of oil
as outlined in the
kUBoTa engine owner’s manual
. Oil
should be warm before draining.
Other types of motor oils may be substituted if they meet
the following requirements:
API Service Classification CC/SC
API Service Classification CC/SD
API Service Classification CC/SE
API Service Classification CC/SF
Table 11. recommended motor oil
FUel CheCk
refilling the Fuel system
This generator has an internal fuel tank located inside
the trailer frame and may also be equipped with an
environmental fuel tank (Figure 29).
alWaYs
fill the fuel
tanks with clean fresh
#2 diesel fuel. Do noT
fill the fuel
tanks beyond their capacities.
Pay attention to the fuel tank capacity when replenishing
fuel. The fuel tank cap must be closed tightly after filling.
Handle fuel in a safety container. If the container does not
have a spout, use a funnel. Wipe up any spilled fuel
immediately.
Figure 29. Internal Fuel Tank System
Danger
Fuel spillage on a
hot
engine can cause
a
fire
or
explosion
. If fuel spillage occurs,
wipe up the spilled fuel completely to
prevent fire hazards.
never
smoke
around or near the generator.
CaUTion
onlY properly trained personnel
who have read
and understand this section should refill the fuel tank
system.
TRAILER
FUEL TANK
(OPTION)
45
FUEL
TANK
INTERNAL
Summary of Contents for Whisperwatt dCa40ssKu
Page 47: ...DCA40sskU ku4i 60 hz Generator operation and parts manual rev 1 03 11 13 page 47 notes...
Page 62: ...page 62 DCA40sskU ku4i 60 hz Generator operation and parts manual rev 1 03 11 13 BATTERY ASSY...
Page 64: ...page 64 DCA40sskU ku4i 60 hz Generator operation and parts manual rev 1 03 11 13 Muffler Assy...
Page 77: ...DCA40sskU ku4i 60 hz Generator operation and parts manual rev 1 03 11 13 page 77 notes...