PAGE 28 — DCA-25SSAI — PARTS AND OPERATION MANUAL—FINAL COPY (06/30/01)
DCA-25SSAI — OUTPUT TERMINAL PANEL
Output Terminal Panel
The output control panel is located on the rear (control panel)
end of the generator. The UVW lugs are protected by a face
plate cover that can be secured in the close position by a
pad lock.
120 Volt Receptacle
One GFCI Duplex NEMA 5-20R (120V, 20 Amp) receptacle
is located on the output terminal. This receptacle can be
used anytime the generator is in operation. The receptacle
is controlled by the circuit breaker located on the control
panel.
The reset button will reset the receptacle after being tripped.
Pressing the "Test Button" (See Figure 8) in the center of
this receptacle will check the GFCI function. The receptacle
should be tested at least once a month.
Figure 8. GFCI Test Button
Connecting Load
Loads can be connected to the generator by the UVW Lugs or
the duplex receptacle. (See Figure 9). Make sure to read the
operation manual before attempting to connect a load to the
generator.
Figure 9. Connecting Loads
Circuit Breakers
To protect the generator from an overload, a 3-pole, 60 amp,
main
main
main
main
main circuit breaker is provided to protect the UVWO output
terminals from overload. In addition two single-pole, 20 amp
GFCI
GFCI
GFCI
GFCI
GFCI circuit breakers are provided to protect the GFCI
receptacles from overload. Three 50 amp load
load
load
load
load circuit
breakers have also been provided to protect the load side of
the generator from overload. Make sure to switch ALL
ALL
ALL
ALL
ALL circuit
breakers to the "OFF" position prior to starting the engine.
Maximum Output
The entire load connected to the UVW l ugs and all four slots in
the duplex receptacle must not exceed 22 kW in standby or 20
kW in prime output.
120V Receptacles -
These receptacles can be used
anytime the generator is in operation. They are controlled
by the circuit breakers above them.
Twist Lock Dual Voltage Receptacles -
To use these
receptacles, place the voltage selector switch in the single
phase 240/120 voltage position and adjust the output
voltage to 240 volts with the voltage regulator on the
control panel (see Figure 6, page 24). Place the voltmeter
change-over switch to the U-W position and the ammeter
change-over switch to the U or W to read the output.
Summary of Contents for POWER WHISPERWATT DCA-25SSAI
Page 2: ...PAGE 2 DCA 25SSAI PARTS AND OPERATION MANUAL FINAL COPY 06 30 01...
Page 18: ...PAGE 18 DCA 25SSAI PARTS AND OPERATION MANUAL FINAL COPY 06 30 01 DCA 25SSAI GENERATOR DECALS...
Page 23: ...PAGE 23 DCA 25SSAI PARTS AND OPERATION MANUAL FINAL COPY 06 29 01 NOTE PAGE...
Page 47: ...PAGE 47 DCA 25SSAI PARTS AND OPERATION MANUAL FINAL COPY 06 29 01 NOTE PAGE...
Page 55: ...PAGE 55 DCA 25SSAI PARTS AND OPERATION MANUAL FINAL COPY 06 29 01 NOTE PAGE...
Page 84: ...PAGE 84 DCA 25SSAI PARTS AND OPERATION MANUAL FINAL COPY 06 30 01 DCA 25SSAI DECALS DECAL ASSY...
Page 141: ...PAGE 141 DCA 25SSAI PARTS AND OPERATION MANUAL FINAL COPY 06 29 01 NOTE PAGE...