page 14 — gaC6HZR 60 HZ geNeRaTOR• OpeRaTiON aNd paRTs maNual — Rev. #1 (03/31/10)
installatiOn
CONNeCTiNg THe gROuNd
The nut and ground terminal on the generator should always
be used to connect the generator to a suitable ground. The
ground cable should be #8 size wire minimum.
At the generator, connect the terminal of the ground cable
between the lock washer and the nut (Figure 2) and tighten
the nut fully. Connect the other end of the ground cable to
a suitable earth ground (ground rod).
120V
240V
120
V
6000
OFF
ON
OFF
ON
OFF
MARCHE
MARCHE
INTERRUPTEUR
DE OPERATION
OPERATION
SWITCH
CONTROL
DE RALENTI
IDLE
CONTROL
ARRET
ARRET
AC CIRCUIT
BREAKER
(for main)
INTERRUPTEUR DE
COURANT PRINCIPAL
AC VOLTMETER
VOLTOMETRE CA
GFCI CIRCUIT
BREAKER
INTERRUPTEUR DE
COURANT
GAC-6HZR
POWERED by
Honda Engines
211052
GROUND ROD
FOR EARTH
GROUND
GENERATOR
GROUND LUG
CONNECT TO
BUILDING
GROUND
IF REQUIRED
8 FT. MINIMUM
REFERENCE
NEC 250-52(C)
GROUND
CABLE
#8 MINIMUM
Figure 2. Generator Grounding