![MULTIQUIP DCA400SSI4F Operation Manual Download Page 63](http://html.mh-extra.com/html/multiquip/dca400ssi4f/dca400ssi4f_operation-manual_1855182063.webp)
DCA400SSI4F/DCA400SSI4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/18/22) — PAGE 63
MAINTENANCE
5. Press the
[SELECT]
button (Figure 89) to enter the
“Escape Mode” menu.
Figure 89. Main Menu (Select Button)
6. Press the
[REQUEST]
button (Figure 90) to send
“Escape Mode Request” signal to ECM.
Figure 90. Escape Mode Menu Screen
[SELECT]
BUTTON
FAULT DIAGNOSTICS
ABOUT UNIT
USER LOGIN
ESCAPE MODE
UP
DOWN SELECT
[REQUEST]
BUTTON
ESCAPE MODE REQUEST
EMERGENCY RESERVE ENGINE
RUN MAY BE POSSIBLE.
TO ATTEMPT ESCAPE MODE:
PRESS THE REQUEST SOFT KEY.
EXIT
REQUEST
7. Place the Auto Start/Stop Switch (Figure 91) in the
“Off /Reset” position.
Figure 91. Auto Off/Reset Manual Switch
(Off/Reset Position)
8. Next, place the Auto Start/Stop Switch (Figure 92) in
the “Manual” position to start the engine.
Figure 92. Auto-Off/Reset Manual Switch
(Manual Position)
9. The
Escape Mode Timer
(Figure 93) will appear on
the
main
screen. This timer displays the remaining
Escape Mode operation time.
Figure 93. Escape Mode Timer
If ESCAPE MODE is temporarily suspended, it is not
necessary to return to the ESCAPE MODE screen and
press the
[REQUEST]
button. ESCAPE MODE operation
will be available until around 30 minutes after operation
has been ended.
Once the ESCAPE MODE timer reaches zero minutes,
the engine will stop since the ESCAPE MODE time has
expired. Please perform maintenance to return the unit
to proper operating condition.
If the unit returns to Warning Level 1 while ESCAPE
MODE is running, ESCAPE MODE will be cancelled,
the ESCAPE MODE timer display will close, and normal
operation will resume.
AUTO
MANUAL
OFF/RESET
(CENTER)
AUTO
MANUAL
OFF/RESET
DEF
E
F
E
F
SCR TROUBLE-PURGE PROHIBITED
SCR SYS ERR
HOURS
00018.2
SD IN
18
MIN.
1800
SPEED
CHECK