HVAC Guide Specifications 

Direct Expansion Hi-Wall Fan Coil 
 
Nominal Size:  

               9,000 – 36,000 BTUH 
 

Multiaqua Model Number: 
               

MHWX-09 

              

 

MHWX-12 

               

MHWX-18 

               

MHWX-24 

               

MHWX-36 

 
Part 1-General 
1.01

 

System Description 

Multiaqua Direct Expansion Fan Coils are manufactured with high impact molded polymers.   

 

1.02

 

Quality Assurance 

A.

 

Certified in accordance with U.L. Standard 95, latest version  (U.S.A.) 

B.

 

Manufactured in a facility registered to ISO 9002, Manufacturing Quality Standard.  

C.

 

Fully load tested at the factory. 

D.

 

Damage resistant packaging.  

 

1.03

 

Delivery, Storage and Handling 

A.

 

Packaged and readied for shipment from the factory. 

B.

 

Controls shall be capable of withstanding 150

°

F storage temperatures in the control compartment. 

C.

 

Stored and handled per manufacturer’s recommendations.  

 

Part 2-Product 
2.01 Equipment 

        A.   General: 
                      1.     Unit shall be a factory assembled direct expansion fan coil.  
                      2.     Shall be assembled with high quality. 

              3.     Contained with the unit shall be all factory wiring, piping, associated controls and special   
                      accessories required prior to start up. 
B.

 

Unit Cabinet: 

1.

 

Composed of high impact polymers. 

2.

 

Shall be internally insulated to insure quiet operation. 

C.

 

Fan Motors: 

              1.     Shall be available in 208/230-1-50/60 vac.  

1.

 

Fan motors shall be three speed, direct drive, and PSC type.  

2.

 

Totally enclosed.  

3.

 

Internal overload protected. 

4.

 

Unit shall contain a swing motor to modulate the discharge air.   

D.

 

Blower Wheels:  

1.

 

Blower wheels are tangential and dynamically balanced.  

E.

 

DX Coil:  

1.

 

Coils manufactured with 3/8” rifled copper tubing mechanically bonded to aluminum fins.  

2.

 

Coils shall be factory tested to 350 psig. 

F.

 

Drain Pan:  

1.

 

All drain pans shall be molded with high impact polymers.  

2.

 

The exterior of all drain pans shall be insulated with closed cell to prevent condensation.  

3.

 

Pans shall contain a flexible drain tubing that is accessible from the back of the unit.    

 
 
 

346 

Summary of Contents for MHWX-09-C-1

Page 1: ...Direct Expansion Fan Coil 9 000 36 000 BTUH Hi Wall Fan Coil 344 MHWX Direct Expansion...

Page 2: ...HWX 18 H 1 MHWX 24 C 1 MHWX 24 H 1 MHWX 36 C 1 MHWX 36 H 1 345 09 9 000 12 12 000 18 18 000 Available Model Numbers MHWX NOMENCLATURE BREAKDOWN Direct Expansion Direct Expansion Hi Wall Fan Coil MHWX...

Page 3: ...ory assembled direct expansion fan coil 2 Shall be assembled with high quality 3 Contained with the unit shall be all factory wiring piping associated controls and special accessories required prior t...

Page 4: ...ansformer and wireless remote D Controls shall be capable of incorporating an optional hard wired thermostat 3 02 Safeties A Fan coil shall contain a non reusable fuse on the secondary voltage side of...

Page 5: ...0 57 10 8 50 54 00 3 18 3 8 3 8 5 8 3 4 Electrical Data Fuse or HACR Circuit Breaker Per Circuit Model Number Hi Speed CFM Volts Phase Hertz Motor HP Full Load Ampacity Minimum Amps Maximum Amps MHWX...

Page 6: ...349...

Page 7: ...gned and manufactured to permit installation in accordance with national codes It is the installer s responsibility to install the product in accordance with national codes and or prevailing local cod...

Page 8: ...plied Hole L Field Supplied Hole MHWX 09 34 6 11 7 7 5 7 5 3 5 2 7 1 6 0 8 1 8 0 8 2 8 2 8 MHWX 12 39 0 12 0 7 5 7 5 3 6 2 7 1 5 1 1 1 7 1 0 2 8 2 8 MHWX 18 46 0 14 2 3 8 3 8 6 1 2 4 2 4 1 7 2 4 1 8 2...

Page 9: ...3 2 Drill the holes for the type of mounting hardware to be used Check local building codes for correct mounting hardware Secure the mounting plate and check for stiffness 3 Drill a diagonal piping ac...

Page 10: ...mproper insulation could result in voided warranty and or building damage Figure 6 2 There is a piping channel in the bottom portion of the back of the units for crossover piping drain condenser contr...

Page 11: ...ounting plate by first sliding the fan coil onto the two notches provided on the mounting plate Figure 9 10 6 Push the bottom of the fan coil towards the wall in order to engage the locking clips Figu...

Page 12: ...355 INSTALLATION OPERATING MANUAL MHWW Hi Wall Fan Coils 9 000 36 000 BTUH MHWX CONTROLS OPERATION GUIDE Wireless Control Standard Control Package Page 355 Optional Wired Control EG 003 Page 361...

Page 13: ...direct sunlight or any place where it is very hot Remove batteries when the remote controller is not in use for extended periods of time The remote controller should be placed 3 or more feet away from...

Page 14: ...Fan only No cooling or heating capability AUTO Operation mode will be selected automatically between HEAT and COOL mode depending upon the room temperature and SET temperature 4 FAN To select fan spee...

Page 15: ...ur up to a maximum of 18 hours To set the OFF DELAY With the system in operation enter the system OFF time by pressing the button to the desired number of hours ahead that the system will be allowed t...

Page 16: ...hours of the SLEEP CYCLE SLEEP FUNCTION DISPLAY 10 DRY This function operates to control humidity within a conditioned space It measures the difference between set point and the actual room temperatur...

Page 17: ...sent auto mode is heating a switch to cooling operation will begin only when the room temperature is 3 above selected control set point 12 TRANSMISSION INDICATOR Blinks twice to indicate that transmis...

Page 18: ...er as shown COOL Cooling operation HEAT Heating operation FAN Fan only No cooling or heating capability AUTO Operation mode will be selected automatically between HEAT and COOL mode depending upon the...

Page 19: ...VER Two different functions are available 1 To set the louver stop position There are 4 angles available The sequence is as follows 2 To set the louver swing continuous motion The sequence is as follo...

Page 20: ...363 MHWX 09 H 1 MHWX 12 H 1 Wiring Diagram 208 230 1 50 60...

Page 21: ...364 MHWX 18 H 1 Wiring Diagram 208 230 1 50 60...

Page 22: ...365 MHWX 24 H 1 Wiring Diagram 208 230 1 50 60...

Page 23: ...366 MHWX 36 H 1 Wiring Diagram 208 230 1 50 60...

Page 24: ...367 MHWX 09 C 1 MHWX 12 C 1 Wiring Diagram 208 230 1 50 60...

Page 25: ...368 MHWX 18 C 1 Wiring Diagram 208 230 01 50 60...

Page 26: ...369 MHWX 24 C 1 Wiring Diagram 208 230 1 50 60...

Page 27: ...370 MHWX 36 C 1 Wiring Diagram 208 230 1 50 60...

Page 28: ...371 MHWX CERTIFIED DRAWING...

Reviews: