F.
Pump:
1.
Circulating pump shall be stainless steel with high efficiency enclosed motor.
2.
Unit shall have chilled liquid solution piping to the exterior of the cabinet.
G.
Evaporator:
1.
Evaporator shall have one independent refrigerant circuit and one liquid solution circuit.
2.
Rated for a refrigerant side working pressure of 450 psig and a maximum water side working
pressure of 150 psig.
3.
Single pass, ANSI type 316 stainless steel, brazed plate construction.
4.
Externally insulated with closed cell, elastomeric foam. (ASTM518)
H.
Condenser:
1.
Condenser coil shall be air-cooled with integral subcooler.
2.
One independent refrigerant circuit.
3.
Constructed of rifled copper tubing mechanically bonded to aluminum fins.
4.
Cleaned and dehydrated.
5.
Factory leak tested to 450 psig.
I.
Refrigerant Circuits:
1.
Each circuit shall contain a sight glass, liquid line filter, thermal expansion valve,
refrigerant charge of R407c and POE compressor oil.
Part 3-Controls and Safeties
3.01 Controls
A. Chiller shall be completely factory wired and tested.
B. Capacity control shall be based on leaving chilled liquid solution temperature.
1. Temperature accuracy shall be + - 1.0
°
F.
2. Controls shall be capable of staging the two compressors.
C. Controls shall include the following components.
1. 24vac transformer to serve all controllers relays and control components.
2. Microprocessor based liquid solution temperature controller.
3. Leaving water temperature thermistor.
4. Pump bypass timer.
5. Compressor recycle timer.
6. Optional low pressure bypass timer for low ambient operation.
7. Optional fan cycling control for low ambient operation.
8. Chilled liquid solution flow switch.
3
.02 S
afeties
A. Unit shall be equipped with thermistors and all necessary components in conjunction with the
control system to provide the following protectants.
1.
Low refrigerant pressure.
2.
High refrigerant pressure.
3.
Low chilled liquid solution temperature.
4.
Low chilled liquid solution flow.
5.
Thermal overload.
6.
Short cycling.
Part 4-Operating Characteristics:
4.01 Temperatures
A. Unit shall be capable of starting and running at outdoor temperatures from 55
°
F to 120
°
F.
B.
Optional Low Ambient Kit shall allow starting and running at outdoor temperatures to -20
°
F. A
field supplied and installed crankcase heater must be used when operating at these temperatures.
C. Unit shall be capable of starting up with a maximum 80
°
F and a sustained 70
°
F entering fluid
solution temperature to the evaporator.
D. Minimum 10% Glycol solution is required. For outdoor temperatures below 32
°
F, reference
MAC Glycol Solution Data table.
4.02 Electrical Requirements
A. Primary electrical power supply shall enter the unit at a single location.
B. Electrical power supply shall be rated to withstand 120
°
F operating ambient temperature.
C. Units shall be available in 1 or 3-phase power at the voltages show
n in the equipment electrical data.
D. Control points shall be accessed through terminal block.
47
Summary of Contents for CFFWA Series
Page 1: ......
Page 8: ...3...
Page 22: ...17...
Page 35: ...Notes Banked Chiller Configuration Installing Multiaqua chillers in parallel is recommended 30...
Page 39: ...34 MAC120 3 Ladder Wiring Diagram 380 460 3 50 60...
Page 42: ...37 MAC120 2 Ladder Wiring Diagram 208 230 3 50 60...
Page 43: ...38 MAC120 2 Wiring Diagram 208 230 3 50 60...
Page 44: ...39 MAC120 2 L with Low Ambient Kit Wiring Diagram 208 230 3 50 60...
Page 45: ...40 MAC120 1 Ladder Wiring Diagram 208 230 1 50 60...
Page 46: ...41 MAC120 1 Wiring Diagram 208 230 1 50 60...
Page 47: ...42 MAC120 1 L with Low Ambient Kit Wiring Diagram 208 230 1 50 60...
Page 48: ...MAC120 CERTIFIED DRAWING 43...
Page 62: ...57...
Page 79: ...74 MAC060 3 Ladder Wiring Diagram 380 460 3 50 60...
Page 80: ...75 MAC060 3 Wiring Diagram 380 460 3 50 60...
Page 81: ...76 MAC060 3 L with Low Ambient Kit Wiring Diagram 380 460 3 50 60...
Page 82: ...77 MAC036 048 060 2 Ladder Wiring Diagram 208 230 3 50 60...
Page 83: ...78 MAC036 048 060 2 Wiring Diagram 208 230 3 50 60...
Page 84: ...79 MAC036 048 060 2 L with Low Ambient Kit Wiring Diagram 208 230 3 50 60...
Page 85: ...80 MAC036 048 060 1 Ladder Wiring Diagram 208 230 1 50 60...
Page 86: ...81 MAC036 048 060 1 Wiring Diagram 208 230 1 50 60...
Page 87: ...82 MAC036 048 060 1 L with Low Ambient Kit Wiring Diagram 208 230 1 50 60...
Page 88: ...83 MAC036 048 060 CERTIFIED DRAWING...
Page 103: ...97...
Page 108: ...102...
Page 119: ...113 MHCCW Without Electric Heat Wiring Diagram 208 230 1 50 60...
Page 120: ...114 MHCCW With Electric Heat Wiring Diagram 208 230 1 50 60...
Page 121: ...115 MHCCW Without Electric Heat Wiring Diagram 120 1 50 60...
Page 122: ...116 MHCCW CERTIFIED DRAWING...
Page 123: ...117 4 Pipe Heat Cool Fan Coil 12 000 36 000 BTUH Ceiling Concealed MHNCCW Chilled Hot Water...
Page 140: ...134...
Page 151: ...145 MHNCCW xx 01 Wiring Diagram 208 230 1 50 60...
Page 152: ...146 MHNCCW xx 03 Wiring Diagram 120 1 60...
Page 153: ...146...
Page 154: ...147 MHNCCW CERTIFIED DRAWING...
Page 155: ...148 2 Pipe Heat Cool Fan Coil 48 000 60 000 BTUH Ceiling Concealed MCCW Chilled Hot Water...
Page 165: ...158...
Page 176: ...169 MCCW xx 01 Wiring Diagram 208 230 1 50 60...
Page 177: ...170 MCCW CERTIFIED DRAWING...
Page 178: ...2 Pipe Heat Cool Fan Coil 9 000 36 000 BTUH Hi Wall Fan Coil 171 MHWW Chilled Hot Water...
Page 194: ...187...
Page 209: ...202 MHWW 09 H 1 MHWW 12 H 1 Wiring Diagram 208 230 1 50 60...
Page 210: ...203 MHWW 18 H 1 Wiring Diagram 208 230 1 50 60...
Page 211: ...204 MHWW 24 H 1 Wiring Diagram 208 230 1 50 60...
Page 212: ...205 MHWW 36 H 1 Wiring Diagram 208 230 1 50 60...
Page 213: ...206 MHWW CERTIFIED DRAWING...
Page 231: ...223...
Page 233: ...225...
Page 239: ...231 CFFWA xx 1 U Wiring Diagram 208 230 1 50 60...
Page 240: ...232 CFFWA CERTIFIED DRAWING...
Page 257: ...249...
Page 265: ...257 CWA2 00 Wiring Diagram 208 230 1 60...
Page 266: ...258 CWA2 CERTIFIED DRAWING...
Page 267: ...4 Pipe Heat Cool Fan Coil 24 000 60 000 BTUH 259 CWA4 Chilled Hot Water Fan Coil...
Page 279: ...271...
Page 287: ...279 CWA4 Wiring Diagram 120 1 60...
Page 288: ...280 CWA4 CERTIFIED DRAWING...